background image

Page  2

7033-277N

August 3, 2015

R

3100 Wood Stove Series (ACC)

Hearth & Home Technologies welcomes you to our tradi-
tion of excellence!  In choosing a Quadra-Fire appliance, 
you have our assurance of commitment to quality, durabil-
ity, and performance.

This commitment begins with our research of the market, 
including ‘Voice of the Customer’ contacts, ensuring we 
make products that will satisfy your needs. Our Research 
and Development facility then employs the world’s most 
advanced technology to achieve the optimum operation of 

our stoves, inserts and fi replaces.  And yet we are old-fash-
ioned when it comes to craftsmanship.  Each unit is meticu-
lously fabricated and surfaces are hand-fi nished for lasting 
beauty and enjoyment.  Our pledge to quality is completed 
as each model undergoes a quality control inspection. 

We wish you and your family many years of enjoyment in 
the warmth and comfort of your hearth appliance.  Thank 
you for choosing Quadra-Fire.

and Welcome to the Quadra-Fire Family

!

INSTALLATION: FULL VERTICAL OR HORIZONTAL WITH MINIMUM 2 FOOT VERTICAL OFF STOVE TOP
INSTALLATION: ENTIÈREMENT VERTICALE OU HORIZONTALE AVEC 609mm VERTICAL MINIMUM DU HAUT DU POÊLE

SINGLE WALL PIPE

 

A B C D E F  G  H

 

Flat Top Model

 

15.25 (387) 11.75 (298)  25.5 (648)  16 (406)  8 (203) 

17 (432) 

48 (1220) 

12 (305)

 Step Top Model  

12 (305)  8.5 (216) 

22 (559)  12.5 (318)  5.5 (140)  14.5 (368) 

48 (1220) 

12 (305)

DOUBLE WALL PIPE
 Flat Top Model

 

10.5 (267)  6.5 (165) 

22 (559) 

13 (330)  6.5 (165)  15.5 (394) 

48 (1220) 

9 (229)

 Step Top Model  

10

 (254) 

6 (152) 

20.5 (521)  11 (279)  4 (102) 

13 (330) 

48 (1220) 

9 (229) 

INSTALLATION:  90

ELBOW OFF TOP OF STOVE THROUGH BACKWALL

INSTALLATION:  90

DU COURBURE AU DESSUS DE HAUT DU POÊLE A TRAVERS LE MUR ARRIÈRE

SINGLE WALL PIPE

 

Flat Top Model

 

12 (305)  8.5 (216) 

22 (559) 

13 (330)  8 (203) 

17 (432) 

48 (1220) 

12 (305)

 Step Top Model  

10 (254) 

6 (152) 

20.5 (521)  11 (279)  5.5 (140)  14.5 (368) 

48 (1220) 

12 (305)

DOUBLE WALL PIPE

 

Flat Top Model

 

8 (203) 

4.5 (114)  17.5 (445)  8.5 (216)  6.5 (165)  15.5 (394) 

48 (1220) 

9 (229)

 Step Top Model  

10 (254) 

6 (152) 

20.5 (521)  11 (279)  4 (102) 

13 (330) 

48 (1220) 

9 (229)

INSTALLATION:   

ALCOVE - Six inch (6 inches) (152mm) diameter listed DOUBLE WALL air insulated connector pipe with UL103 HT* listed factory-built Class "A" chimney, or a masonry 

chimney. (Mobile Home must be equipped with a spark arrestor.) Maximum depth of Alcove shall be no more than 48 inches (1220mm) with a minimum height of 48 inches (1220mm) to top of 
unit, and the referenced clearances.  

INSTALLATION:

 

ALCÔVE 

De six (6

 inches) 

(152mm) de diamètre, le connecteur du conduit d'air isolé pour mur double avec une cheminée bâtit en usine UL103HT de Classe "A", ou une 

cheminée de briques. (Les maisons mobiles doivent être équipées d'un arrêt d'étincelle). La profondeur maximum de l'alcôve ne doit pas être de plus de 48

 inches (

1220mm) avec une hauteur 

minimum de 48 inches (1220mm) du haut de l'appareil, et des espaces libres alloués. 

DOUBLE WALL PIPE

 

Flat Top Model

 

 11.75 (298)  8.25 (210)  23.5 (597)  14.5 (368) 

N/A 

N/A 

48 (1220) 

*

 Step Top Model  

10 (254) 

6 (152) 

20.5 (521)  11 (279) 

N/A 

N/A 

48 (1220) 

*

 

*In Canada must comply with Standard CAN/ULC-S629-M87 for the 650

o

C Factory-built chimney.

*Au Canada doit conformer a CAN/ULC-S629-M87 la norme pour 650

o

C cheminée bâtit en usine.

 

* SEE PIPE MANUFACTURERS CLEARANCES - NOT TESTED / VOIR LE FABRICANT POUR LES ESPACES LIBRES DES CONDUIT - PAS TESTÉ

SPÉCIFICATIONS DE LA VENTILATION:

MUR SIMPLE: 

De six (6

 inches)

 (152mm) de diamètre le connecteur de conduit de 

minimum d'acier noir ou bleu de minimum de 24MSG, avec une cheminée bâtit en 
usine UL103HT* de Classe "A", adéquate pour usage avec les combustions solides, 
ou une cheminée de briques, avec espaces libres référés.

MUR DOUBLE

: De six (

6 inches) 

(152mm) de diamètre, le connecteur du conduit 

d'air isolé pour mur double avec une cheminée bâtit en usine UL103HT* de Classe 
"A:, ou une cheminée de briques, avec espaces libres alloués.

MAISON MOBILE:

  Utiliser un conduit de mur double par Dura-Vent DVL, Selkirk 

Metalbestos DS ou Security DL. Doit être équipé d'un arrêt d'étincelle. Utiliser les 
espaces libres pour mur double comme mentionné ci-bas.

MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS: In Inches & (Millimeters)

NOTE:  All "A" , "C" and "F" Dimensions are to inside diameter of the flue collar.

LISTED ROOM HEATER, SOLID FUEL TYPE.   
ALSO FOR USE IN MOBILE HOMES. (UM) 84 
HUD .  

"For Use with Solid Wood Fuel Only" 

1445 N. Highway, Colville, WA 99114

Install and use only in accordance with 
manufacturer's installation and operating 
instructions.  Contact local building or fire 
officials about restrictions and installation 
inspections in your area. Do not obstruct the 
space beneath heater.

WARNING - For Mobile Homes

:  Do not 

install in a sleeping room.  An outside 
combustion air inlet must be provided and 
unrestricted while unit is in use.  The 
structural integrity of the mobile home floor, 
ceiling and walls must be maintained.  The 
stove needs to be properly grounded to the 
frame of the mobile home.  Components 
required for mobile home installation: 
Outside Air Kit, Part Number OAK-ACC..

Refer to manufacturer's instructions

 and 

local codes for precautions required for 
passing chimney through a combustible 
wall or ceiling and maximum offsets.
Inspect and clean chimney frequently - 
Under Certain Conditions of Use, Creosote 
Buildup May Occur Rapidly.
Do not connect this unit to a chimney 
serving another appliance.
Optional Blower, Part BK-ACC.
Electrical Rating:  115 VAC, 1.2 Amps, 60 Hz.
Route power cord away from unit.  Do not 
route cord under or in front of appliance.

DANGER: Risk of electrical shock.

  

Disconnect power supply before servicing.
Replace glass only with 5mm ceramic 
available from your dealer.
Do not use grate or elevate fire.  Build 
wood fire directly on hearth.
Do not overfire - if heater or chimney 
connector glows, you are overfiring.
Operate only with the fuel loading door 
closed.  Open only to add fuel to the fire.

CAUTION

:

 

U.S. ENVIRONMENTAL PROTECTION AGENCY

Certified to comply with 2015 particulate emission standards at 1.1 G/HR 

EPA Method 28 and 5G. Not approved for sale after May 15, 2020.

This wood heater needs periodic inspection and repair for proper 

operation. Consult the owner’s manual for further information. It is against 

federal regulations to operate this wood heater in a manner inconsistent 

with the operating instructions in the owner’s manual.

2015 2016 

2017 Jan. Feb. Mar. Apr. May 

June 

July Aug. 

Sept. 

Oct. 

Nov. 

Dec.

PREVENT HOUSE FIRES

   

FLOOR PROTECTION

:

Floor protector for Millennium and Pedestal Step Top Models 
must be a 3/8

 inch 

min. thickness, non-combustible material or 

equivalent, (Step Top Leg Model only must be 1/2 inch [13mm] 
min thickness, “k” value 0.84, R value 0.59 or non-combustible 
floor protector 1-1/4 inch [32mm] thick) extending beneath 
heater and to front/sides/rear as indicated on the diagram 
below.  Exception: Non-combustible floor protections must 
extend beneath the flue pipe when installed with horizontal 
venting and extend 

2 inches (51

mm) beyond each side.  

Report 

Rapport

#061-S-66-6

TESTED TO:

TESTÉ À:

   UL 1482-11 ,  ULC S627

-

00. 

HOT WHILE IN OPERATION DO NOT TOUCH, KEEP CHILDREN AND CLOTHING AWAY. CONTACT MAY CAUSE SKIN BURNS.  KEEP 
FURNISHINGS AND OTHER COMBUSTIBLE MATERIAL FAR AWAY FROM THE APPLIANCE. SEE NAMEPLATE AND INSTRUCTIONS.

VENT SPECIFICATIONS:

SINGLE WALL:

 Six inch (6 inches) (152mm) diameter, minimum 24 MSG black or 

blued steel connector pipe, with a listed factory-built UL103HT* Class "A" chimney, 
suitable for use with solid fuels, or a masonry chimney, and the referenced 
clearances.

DOUBLE WALL:

 Six inch (6 inches) (152mm) diameter, listed double wall air 

insulated connector pipe with listed factory-built UL103HT* Class "A" chimney, or  a 
masonry chimney and the referenced clearances

MOBILE HOME:

  Use double wall pipe by Dura-Vent DVL, Selkirk Metalbestos DS or 

Security DL double wall connector pipe. Must be equipped with a spark arrestor.  
Apply double wall clearances below when installing unit.

R

7033-278H

CHAUD LORS DE L'OPÉRATION. NE PAS TOUCHER. GARDEZ LES ENFANTS ET LES VÊTEMENTS LOIN DE L'ESPACE DÉSIGNÉ DE L'INSTALLATION. LE CONTACT PEUT CAUSER DES 

BRÛLURES À LA PEAU. GARDEZ LES MEUBLES ET LES MATÉRIAUX COMBUSTIBLES LOIN DE L'ESPACE DÉSIGNÉ DE L'APPAREIL. VOIR L'ÉTIQUETTE ET LES INSTRUCTIONS.

ATTENTION:

APPAREIL DE CHAUFFAGE DE PIÈCE, DE TYPE DE 

COMBUSTIBLE SOLIDE, POUR USAGE DANS LES 

MAISONS MOBILES. (UM) 84 HUD. 

"Pour Usage Avec 

Bois Solide Seulement"

I

nstallez et utilisez en accord avec les instructions 

d'installation et d'opération du fabricant. Contactez le 

bureau de la construction ou le bureau des incendies au 

sujet des restrictions et des inspections d'installation dans 

votre voisinage. Ne pas obstruez l'espace en dessous de 

l'appareil.

AVIS - Pour Les Maisons Mobiles:  Ne pas installer dans 

une chambre à coucher. Un tuyau extérieur de combustion 

d'air doit être installé et ne doit pas être obstrué lorsque 

l'appareil est en usage. La structure intégrale du plancher, 

du plafond et des murs de la maison mobile doit être 

maintenue intacte. L'appareil de chauffage doit être fixé à 

la charpente de la maison mobile. Les composants requis 

pour l'installation des maisons mobiles: Assemblage d'air 

extérieur, Numéro de Pièce OAK-ACC.

Référez vous aux instructions du fabricant et des codes 

locaux pour les précautions requises pour passer une 

cheminée à travers un mur ou un plafond combustibles, et 

les compensations maximums.

Inspectez et nettoyez la cheminée fréquemment. Sous 

certaines conditions, il se peut que la créosote s'accumule 

rapidement.

Ne pas connecter cet appareil à une cheminée servant un autre 

appareil.

tVentilateur Optionnel, Pièce BK-ACC.

Puissance Électrique: 115 VAC, 1.2 Amps, 60 Hz.

Éloignez le fil électrique de l'appareil. Ne pas faire passer 

le fil électrique au dessus ou en dessous de l'appareil.

DANGER: Il y a risque de décharge électrique.  

Déconnectez le fil électrique de la prise de contact avant 

le service.

Remplacez la vitre seulement avec une vitre céramique de 

5 mm disponible chez votre fournisseur.

N'élevez pas le feu. Bâtissez le feu de bois directement 

sur l'âtre.

Ne pas surchauffer. Si l'appareil de chauffage ou le tuyau 

de cheminée rougissent, vous surchauffez.

Opérez l'appareil seulement lorsque la porte de 

chargement est fermée. Ouvrez la porte seulement 

lorsque vous devez ajouter des combustibles dans le feu.

PRÉVENTION DES FEUX DE MAISON

PROTECTION DU PLANCHER:

Le protecteur de plancher doit être 

(Modèles  Millennium et au 

dessus en escalier socle) d'un minimum de 3/8 inch (9.5 mm) 

d'épaisseur, de matériel incombustible ou équivalent, (Modèle au 

dessus en escalier pied d’un minimum de 1/2 inch [13mm] 

d'épaisseur, “k” =0.84, R value 0.59 au le protecteur de 

plancher de matériel incombustible 1-1/4 inch [32mm] 

d’épaisseur).  s'étendant du dessous de l'appareil de chauffage 

à l'avant, aux co

tés et à l'arrière comme indiqué sur le 

diagramme suivant. Exception: Les protections incombustibles 

du plancher doivent s'étendre en dessous du conduit de 

cheminée lorsqu'installées avec une ventilation à l'horizontale et 

s'étendre de 2 inches (51mm) de chaque côté. 

ESPACES LIBRES MINIMUM DES MATÉRIAUX COMBUSTIBLES:En Pouces & (millimètres)

NOTE:  Toutes les dimensions "A", "C", et "F" sont à partir du diamètre intérieur de l'entrée du conduit.

BACKWALL/SIDEWALL

MUR ARRIÈRE/MUR DE CÔTÉ 

CORNER INSTALLATION
INSTALLATION DU COIN 

ALCOVE TOP VIEW /

VUE DU HAUT DE L'ALCÔVE 

ALCOVE SIDE VIEW / 

VUE DE CÔTÉ DE L'ALCÔVE

DO NOT REMOVE THIS LABEL / NE PAS ENLEVER L'ÉTIQUETTE

CONDUIT DU MUR SIMPLE

CONDUIT DU MUR DOUBLE

CONDUIT DU MUR DOUBLE

Manufactured by:
Fabriqué par:

 

C

D

A

B

C

D

90

o

 OFF TOP 

UP & OUT CEILING CLEARANCE
ESPACE LIBRE DU DESSUS DE 
L'APPAREIL AU PLAFOND AVEC 90  
DE COURBURE 

STOVE TO CEILING CLEARANCE

ESPACE LIBRE DU POÊLE AU 
PLAFOND 

G

G

H*

 

E

F

E

F

CONDUIT DU MUR DOUBLE

Modèle au dessus en appartement
Modèle au dessus en escalier

Modèle au dessus en escalier 

G

H*

Modèle au dessus en appartement
Modèle au dessus en escalier

Modèle au dessus en appartement
Modèle au dessus en escalier

Modèle au dessus en appartement

CONDUIT DU MUR SIMPLE

Modèle au dessus en appartement
Modèle au dessus en escalier

www.quadrafire.com

SERIAL NO. 

NUMÉRO DE SÉRIE

007196

G

A

B

G

A

B

3100 ACC Series

O-T L

Tested and 

Listed by

Portland

Oregon USA

OMNI-Test Laboratories, Inc.

C

US

16" from glass

8"

USA

Fuel loading door

Millennium & Step Top 31-5/8" Min

Millennium
& Step Top
39-5/8”
minimum

CANADA

203mm (8")

203mm

(8")

203mm

(8")

457mm (18")

Millennium
1280mm 
(50-3/8")
minimum

1040mm (41") minimum

Step Top
1321mm 
(52")
minimum

Made in U.S.A. 

of US and 

imported parts.

Fabriqué aux 

États-Unis-d’Amérique par des 

pièces d’origine américaine et 

pièces importées.

SAMPLE OF SERIAL NUMBER / SAFETY LABEL

LOCATION:  BACK OF APPLIANCE

Serial No.

Model 

Name

Test Lab & 
Report No.

Mfg. Date

S

A

M

P

L

E

NOTE:  Clearances may only be reduced 
by means approved by the regulatory 
authority having jurisdiction

Содержание 31ST-ACC

Страница 1: ...to touch glass Keep children away CAREFULLY SUPERVISE children in same room as fireplace Alert children and adults to hazards of high temperatures High temperatures may ignite clothing or other flamm...

Страница 2: ...ual 2015 2016 2017 Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec PREVENT HOUSE FIRES FLOOR PROTECTION Floor protector for Millennium and Pedestal Step Top Models must be a 3 8 inch min thickness...

Страница 3: ...tallation 24 25 Section 8 Operating Instructions A Over Firing Your Appliance 26 B Wood Selection Storage 26 C Burning Process 26 27 D Automatic Combustion Control ACC 27 E Air Controls 27 28 F Burn R...

Страница 4: ...ologies Operating appliance without fully assembling all components Operating appliance without legs attached if supplied with unit Do NOT Overfire If appliance or chimney connector glows you are over...

Страница 5: ...ping areas Follow the smoke detector manufacturer s placement and installation instructions and be sure to maintain regularly 2 A conveniently located Class A fire extinguisher to contend with small f...

Страница 6: ...ents to furnace or air condi tioning Imbalances of HVAC air handling system Upper level air leaks Recessed lighting Attic hatch opening Duct leaks To minimize the affects of negative air pressure the...

Страница 7: ...ce after one hour of operation at each burn setting NOTE These are guidelines only and may vary somewhat for individual installations F Tools And Supplies Needed Before beginning the installation be s...

Страница 8: ...n Cap Storm Collar Flashing Figure 8 3 Interior Prefabricated Chimney Figure 8 2 Exterior Prefabricated Chimney Figure 8 1 Masonry Chimney H Typical Stove Systems Stove system with masonry chimney con...

Страница 9: ...ID 14 15 16 in 373mm 25 1 4 in 641mm 9 15 16 in 237mm 12 1 2 in 318mm 30 in 762mm 15 1 16 in 383mm 10 15 16 in 271mm 19 1 16 in 484mm C L 31M ACC MBK Millennium Model Figure 9 3 Figure 9 4 31M ACC LE...

Страница 10: ...Pedestal 31ST ACC Step Top Model with Queen Ann Legs 23 7 8 in 606mm 33 1 8 in 841mm 15 1 16 in 383mm 19 1 16 in 484mm 10 15 16 in 278mm 14 15 16 in 379mm 21 1 8 in 537mm 6 11 16 in 170mm C L 34 1 4...

Страница 11: ...15 381 8 1 2 216 25 635 12 1 2 318 5 1 2 140 17 1 2 445 48 1219 12 305 DOUBLE WALL PIPE A B C and D dimensions are based off of certification clearances Stove pipe manufacture clearances MUSt be adhe...

Страница 12: ...5 8 in minimum 1041mm 41 in minimum Must extend 2 in 51mm beyond each side of pipe shaded area In Canada similar floor protection must be provided 18 inches 457mm in front and 8 inches 203mm from the...

Страница 13: ...ing in the face of the appliance See page 12 for Canadian clearances and horizontal venting exception For the Step Top Leg Model In US installations it is nec essary to install a floor protector of a...

Страница 14: ...ue is smaller than 0 84 and therefore is acceptable C Outside Air Kit Installation 31M ACC MBK 31ST ACC A source of air oxygen is necessary in order for combus tion to take place Whatever combustion a...

Страница 15: ...he fire must be replaced Air is replaced via air leakage around windows and under doors In homes that have tightly sealed doors and windows an outside air source is needed An optional Outside Air Kit...

Страница 16: ...f appliance CAUTION Figure 16 1 MANUAL Over rides the Snap Disc AUTO Fan will turn ON OFF Automatically by the Snap Disc Controls the Fan Speed Snap Disc Bracket with Magnet MANUAL FAN AUTO LOW HIGH O...

Страница 17: ...teel black or 26 gauge blued steel or an approved air insulated double wall venting pipe Thimble A manufactured or site constructed device installed in combustible walls through which the chimney conn...

Страница 18: ...ing lumber to fit into wall opening Inside opening of frame should be no less than 14 inch x 14 inch 356mm x 356mm Figure 18 1 4 Attach the wall spacer to the chimney side of the frame 5 Nail the fram...

Страница 19: ...ors must conform to each other to ensure a proper fit and seal Flue Gas Direction Crimped End Toward Stove Secure pipe sections with a minimum of 3 screws Figure 19 2 Chimney Connector Stove Pipe WARN...

Страница 20: ...roof within 10 feet 305cm Must be located away from trees or other struc tures These are safety requirements and are not meant to assure proper flue draft Figure 20 1 E 2 10 3 Rule Figure 20 2 NOTE Ch...

Страница 21: ...onnector UL103 HT chimney and terminal cap with spark arrestor Never use a single wall connector stove pipe in a mobile home installation Use only double wall connector pipe Dura Vent DVL Selkirk meta...

Страница 22: ...included If not needed discard Tools Required Phillips head screwdriver 7 16 socket wrench 3 32 and 5 36 Allen wrench Begin installing the ARS System 1 Remove 2 front bricks as shown in Figure 22 1 2...

Страница 23: ...emovel Drawer Adapters Oak Pedestal Trim Figure 23 1 B Leg Kit and Ash Removal Installation ARS for Step Top Uni Body Begin installing the ARS System 1 Follow steps 1 through 6 on page 22 See also Fig...

Страница 24: ...ndle through door 3 Install second washer s as shown 4 Install key in groove 5 Align groove in latch cam with key slide latch cam over shaft 6 Install locknut but do not overtighten as the door handle...

Страница 25: ...100 Wood Stove Series ACC R Figure 25 1 Figure 25 2 The 31LE units are now being shipped with a tile panel securing clip on both sides of the units Please remove and discard pins prior to use Fig 25 3...

Страница 26: ...out of wet unseasoned wood resulting in wasted heat Do not over fire Over firing may ignite creosote or will damage the stove and chimney To prevent over firing your stove DO NOT Use flammable liquids...

Страница 27: ...is function is performed by sliding the con trol all the way back until it stops at the HI indicator on the label and then pulling forward to the front of the stove until it stops This activates the A...

Страница 28: ...Low setting Figure 28 1 NOTE These are approximate settings and will vary with type of wood or chimney draft Due to altitude and other environmental circumstances this operational information is a gui...

Страница 29: ...e 29 2 Figure 29 1 CORRECT POSITION Firebox damage due to improper baffle place ment is not covered by warranty Operate the wood burning appliance with the baffle in the correct position only Not doin...

Страница 30: ...2mm in diameter Be careful not to smother the fire Stack the pieces of wood carefully near enough to keep each other hot but far enough away from each other to allow adequate air flow between them 7 S...

Страница 31: ...page 31 I Blower Operating Instructions WARNING Fire Risk DO NOT BURN GARBAGE OR FLAMMABLE FLUIDS SUCH AS GASOLINE NAPTHA OR ENGINE OIL Do NOT burn treated wood or wood with salt driftwood May genera...

Страница 32: ...the door is closing properly The chimney and chimney cap must be inspected for soot and creosote during the burn season This will prevent pipe blockage poor draft and chimney fires Always burn dry woo...

Страница 33: ...that before each heating season the entire system be professionally inspected cleaned and repaired if necessary a The stove and ashes must be completely cooled down before using the Ash Removal System...

Страница 34: ...air will be flowing over the glass and the smoky relatively cool condition of a low fire will cause the glass to become coated Operating the appliance with the Burn Rate Air Control and Start UpAir Co...

Страница 35: ...appliance without firebrick 1 After the coals have completely cooled remove all old brick and ash from unit and vacuum firebox 2 Remove new brick set from box and lay out to diagram shown 3 Lay bottom...

Страница 36: ...top of baffle board open up and flatten and smooth out the blanket Re check the baffle board for correct positioning Figure 36 2 Figure 36 1 Baffle Figure 36 2 Ceramic Blanket F Snap Disc Replacement...

Страница 37: ...ube channel assembly into side of firebox and insert each tube into the corresponding hole in the tube channel rack starting with the back hole first 3 Make sure tube channel assembly is flush against...

Страница 38: ...appliance towards the wind Wood condition is too wet too large Use dry seasoned wood refer to wood fuel sec tion Bed of coals not established before adding wood Start with paper kindling to establish...

Страница 39: ...eginning Manufacturing Date July 2006 Ending Manufacturing Date Active Millennium Wood Stove Advanced Combustion Control ACC Part number list on following page 31M ACC MBK 7 06 Active 31M ACC GT 7 06...

Страница 40: ...ort Rack 7033 148 7 Brick Retainer 7033 149 8 Ceramic Fiber Blanket 1 2 Thick 19 W x 13 3 4 H 832 3390 Y 9 Baf e Board 9 1 2 in W x 13 3 4 in H Pkg of 2 SRV7033 209 Y 10 Brick Assembly Complete Set Pk...

Страница 41: ...2 Y 14 4 Timer Air Control Assembly SRV7033 052 Y Rear Air Door Assembly 7033 024 Y 14 5 Rear Air Control Arm Assembly 7033 035 Y 14 6 Start Up Control Knob 7000 343 14 7 Air Control Rod Guide 7033 21...

Страница 42: ...Key Cam Latch 430 1151 Nut Locking Door Handle Pkg of 24 226 0100 24 Y Screw Flat Head Philips 8 32 X 1 2 Pkg of 10 832 0860 Y Washer Sae 3 8 Pkg of 3 832 0990 Y 17 4 Spring Handle Door 1 2 Gold 832...

Страница 43: ...142 SRV7000 614 Y Component Pack Includes Touch Up Paint Spring Handles 1 1 2 and 2 1 4 Trimount Plug Owners Manual and Warranty Card Black Gold Trim 7033 027 Nickel Trim 7033 029 Paint Touch Up 812 0...

Страница 44: ...R 31ST ACC Beginning Manufacturing Date Sept 2006 Ending Manufacturing Date Active Step Top Wood Stove 31ST ACC Advanced Combustion Control Part number list on following page 1 2 3 4 5 6 7 8 9 10 11 1...

Страница 45: ...ick 6 x 4 1 2 x 1 1 4 Qty 4 Req 4 3 Brick 9 x 4 1 2 x 1 1 4 w angles see diagram Qty 1 Req 4 4 Brick 4 1 2 x 4 1 2 x 1 1 4 Qty 2 Req 4 5 Brick 9 x 3 x 1 1 4 w angle see diagram Qty 1 Req Brick Uncut P...

Страница 46: ...033 035 Y 14 6 Start Up Control Knob 7000 343 14 7 Air Control Rod Guide 7033 210 14 8 Latch Magnet For Air Control 229 0631 14 9 Timer Arm Assembly 7033 034 Y 14 10 Timer Only Replacement Assembly SR...

Страница 47: ...FH 17 1 Hinge Pins 1 2 Black Pkg of 2 7000 606 2 Gold Pkg of 2 832 0250 Nickel Qty 2 req 430 5320 17 2 Rope Door 3 4 X 84 Field Cut to Size 7 Ft 832 1680 Y 17 3 Door Glass Assembly 15 1 2 in W x 13 3...

Страница 48: ...r Assembly 7033 043 Component Pack Includes Touch Up Paint Spring Handles 1 1 2 and 2 1 4 Trimount Plug Owners Manual and Warranty Card Black Gold Trim 7033 027 Nickel Trim 7033 029 Paint Touch Up 812...

Страница 49: ...od Stove Series ACC R C Exploded Drawing Service Parts Service Parts 31M ACC LE Beginning Manufacturing Date Sept 2014 Ending Manufacturing Date Active R Part number list on following page 04 15 14 1...

Страница 50: ...bly Side Left SRV7033 082 Y 5 Ceramic Fiber Blanket 1 2 Thick 832 3390 6 Baf e Protection Channel SRV7033 298 7 Tube Support Rack 7033 148 8 Brick Retainer 7033 149 9 Baf e Board Pkg of 2 SRV7033 209...

Страница 51: ...ibutor Stocked at Depot ITEM DESCRIPTION COMMENTS PART NUMBER 14 2 Spring Handle 1 4 250 8340 Y 14 3 Door Gasket 7033 282 Y 14 4 Timer Air Control Assembly SRV7033 052 Y 14 5 Control Arm Assembly Rear...

Страница 52: ...or Assembly DR 31 43BK FH 18 1 Hinge Pin 1 2 430 5320 18 2 Rope Door 3 4 x 84 7 Ft 832 1680 Y 18 3 Door Glass Assembly 7000 012 Y Gasket Glass Tape 3 4 x 1 8 5 Ft 832 0460 Y 18 4 Glass Frame Set 4 pcs...

Страница 53: ...rovide model number and serial number when requesting service parts from your dealer or distributor Stocked at Depot ITEM DESCRIPTION COMMENTS PART NUMBER ACCESSORIES Blower Assembly BK ACC Blower Con...

Страница 54: ...al purchase In the case of new home construction warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independent authorized HHT de...

Страница 55: ...33 277N Page 55 3100 Wood Stove Series ACC R WARRANTY CONDITIONS This warranty is void if LIMITATIONS OF LIABILITY 8 K N N OQ U Z 8 88 Z 8 Z Q 8 N N Q U N Z Q 8 U N N 88 N Z Q 8 N O K WARRANTY EXCLUSI...

Страница 56: ...e Dealership purchased from Dealer phone Notes We recommend that you record the following pertinent information for your 3100 WOOD STOVE ACC DO NOT DISCARD THIS MANUAL CAUTION Important operating and...

Отзывы: