MOBILE HOME INSTALLATION
You must use a Quadra-Fire 3100 outside air kit (see page 16 for part numbers) for installation in a mobile
home. Use of alternative material will void warranty.
1.
An outside air inlet must be provided for combustion and be unrestricted while unit is in use.
2.
Unit must be secured to the mobile home structure by bolting pedestal through hearth pad and into floor.
For leg models, use attachment brackets to attach stove through pad and into floor.
3.
Do not install unit in a sleeping room.
4.
The structural integrity of the mobile home floor, walls, and ceiling/roof must be maintained (i.e., do not
cut through floor joist, wall stud, ceiling truss, etc.).
5.
Unit must be grounded with #8 copper grounding wire or equivalent and terminated at each end with
N.E.C. approved grounding device.
6.
Refer to clearance to combustibles section (page 6) for listing to combustibles.
7.
Seal all wall/floor inlets to prevent air or moisture penetration. Check periodically to insure the inlet is free
of obstructions (e.g., snow or ice).
8.
Burn wood only. Other types of fuels may generate poisonous gases (e.g., carbon monoxide).
9.
If unit burns poorly while exhaust blower is on in home, increase combustion air.
NOTE: Offsets from the vertical, not exceeding 45
°
, are allowed per Section 905(a) of the Uniform
Mechanical Code (UMC). Offsets greater than 45
°
are considered horizontal and are also allowed,
providing the horizontal run does not exceed 75% of the vertical height of the vent. Construction,
clearance and termination must be in compliance with the UMC Table 9C. This installation also
complies with NFPA 211.
Page 15
FIGURE 13
E
XTERIOR
CHIMNEY
RUNNING
UP
THE
OUTSIDE
OF
THE
RESIDENCE
*Note: Unit has not been tested with
a horizontal connector. Refer
to local building codes.