2100-I & 3100-I FIREPLACE INSERT
Page 7
March 1999
MANUFACTURED BY:
Approved for installation and use in factory built zero-
clearance fireplaces conforming to minimum fire
chamber specifications.
Components required for installation: positive or direct
flue connection assembly or listed vent liner. Inspect
and clean vent system frequently in accordance with
manufacturers instructions.
In Canada a full length S635 flue liner is required.
For use with solid wood fuel only. Do not use grate or
elevate fire. Build wood fire directly on hearth.
Route power cord away from unit. Do not route cord
over or under appliance.
DANGER: Risk of electrical shock. Disconnect power
supply before servicing.
Optional component:
Blower Assembly: Part #831-1101
Electrical Rating:
115 VAC, .6 Amps, 60 Hz.
123456789012345678901234567890121234567890123456789012345678901
123456789012345678901234567890121234567890123456789012345678901
123456789012345678901234567890121234567890123456789012345678901
123456789012345678901234567890121234567890123456789012345678901
123456789012345678901234567890121234567890123456789012345678901
123456789012345678901234567890121234567890123456789012345678901
123456789012345678901234567890121234567890123456789012345678901
123456789012345678901234567890121234567890123456789012345678901
123456789012345678901234567890121234567890123456789012345678901
123456789012345678901234567890121234567890123456789012345678901
123456789012345678901234567890121234567890123456789012345678901
123456789012345678901234567890121234567890123456789012345678901
123456789012345678901234567890121234567890123456789012345678901
123456789012345678901234567890121234567890123456789012345678901
123456789012345678901234567890121234567890123456789012345678901
123456789012345678901234567890121234567890123456789012345678901
123456789012345678901234567890121234567890123456789012345678901
U.S. ENVIRONMENTAL PROTECTION AGENCY
Certified to comply with July 1990 particulate emissions standards.
Date of Manufacture
1999 2000 Jan. Feb. Mar. Apr. May June July Aug. Sept. Oct. Nov. Dec.
SAFETY LABELS
Listed solid fuel heater for installation in masonry or fac-
tory bult fireplaces.
LISTED TO: UL 1482, ULC S628
TYPE OF FUEL: SOLID WOOD ONLY
PREVENT HOUSE FIRES
Install and use only in accordance with manufacturers
installation, venting and operating instructions. Do not
remove bricks or mortar from masonry fireplace. Install
only on a non-combustible hearth. Contact local build-
ing or fire officials about restrictions and installation in-
spections in your area.
Do not connect this unit to a chimney serving another
appliance.
When used as a masonry insert stove, install only in a
masonry fireplace built to UBC Chapter 37. Do not re-
move brick or mortar to accommodate insert. Installa-
tion requires minimum of a starter pipe into existing chim-
ney with airtight face seal.
CONTACT YOUR LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND
INSTALLATION INSPECTION IN YOUR AREA
HEARTH EXTENSION
E
B
C
D
MANTEL
INSERT
A
F
INSTALLATION
A
B
C
D
E
F
UNITED STATES
32
22
14
10
16
8
CANADA
32
27
14
12
16
8
815mm 685mm 355mm 305mm 405mm 200mm
Minimum Clearances to Combus-
tible Materials (in inches)
Install insert with a mimimum of
32 clearance to combustible
sidewall, 10 to side and 14 to top
trim, 22 from top of insert to man-
tel. Floor protector must be 3/8
mimimum non-combustible mate-
rial or equivalent, extending 16 in
front and 8 to both sides.
Model:
Serial No.
QUADRA-FIRE
3100-I
Operate only with doors closed. Replace glass only with
5mm ceramic available from your dealer.