QTS-CLX-PVX Page
3
The module is shipped in monitor mode, with a blank configuration.
Watchdog and Jabber Inhibit
A watchdog timer is implemented in the module’s hardware. If the firmware does not
kick the watchdog within the timeout period the watchdog times out and generates a fatal
error (see page 31) with error code D1. In master mode, the module stops scanning and
stops communicating with the ControlLogix.
A jabber inhibit timer is implemented in the module’s hardware. If the bus transmitter is
on longer than 150% of the longest frame time, the jabber inhibit forces the transmitter
off and generates a fatal error (see page 31) with error code D0. In master mode, the
module stops scanning and stops communicating with the ControlLogix.
Power Requirements
The QTS-CLX-PVX module requires 675 mA @ 24VDC and 5 mA @ 5.1VDC from I/O
chassis backplane.
Other Requirements
To use the Windows utility programs, you must have RSLinx software, version 2.54 or
later, with an activation. Use RSLinx Gateway or RSLinx Professional software. Do not
use RSLinx Lite.
Package Contents
•
QTS-CLX-PVX module
•
CD containing software and documentation