updating firmware), the configuration is unaffected.
Click Apply to download the firmware.
When the firmware download is successful, the module displays the following message
and shows the version of firmware downloaded.
Click OK to clear the message, then click Done.
If you change the module mode from master to monitor or from monitor to master:
the configuration in the configuration program is converted to the new mode
data mappings change
The ControlLogix controller with the connection to the module must be in program mode
when you change mode. If the processor is in run mode, the following message appears.
The QTS-CLX-PVX displays the module and firmware and version on the 4-character
display.
Configuring from a PROVOX Control I/O Bus
The QTS-CLX-PVX must be configured by capturing configuration information sent by
a PROVOX master to a running PROVOX system.
WARNING!
Connecting the module to the Control I/O disrupts bus traffic!
Connect the module only at a time when it is safe to do so.
Use the following steps to configure the QTS-CLX-PVX.
1.
Connect the module, in monitor mode, to a running PROVOX bus.
Содержание QTS-CLX-PVX