The CLX_offset is the offset into the data for the connection. You can select the offset
where the data is located or you can leave it out and AN-X will automatically assign the
offset. If the offset is omitted, the line must start with a comma.
The Modicon_location consists of an address in the form dxrysz where x is the drop
number, from 1 to 32, y is the rack number, from 1 to 5 for 800 series drops and 1 to 4 for
Quantum drops, and s is the slot number, from 1 to 16.
If the rack number is 1, the explicit rack number (ry) can be omitted.
Example:
To associate ControlLogix offset 27 with the Modicon module at address drop 4, rack 2,
slot 4 and assign it tagname tag1
27, d4r2s4, tag1
Example:
To map the Modicon module at address drop 14, rack 1, slot 3 to the next available
ControlLogix location and assign it tagname tag2
,d14r1s3, tag2
or, since the rack number is 1, you can also use
,d14s3, tag2
Example: Simple Configuration File
ClxName, AnxModMas
ClxPrefix,MOD_
ClxSlot, 0
DataOutput
,d4s4, Drop4Slot4Outputs
DataInput
,d4s7, Drop4Slot7Inputs
Swap Option
For some modules, the data is swapped when it should not be. You can add keyword
swap to the mapping to change the bit order.
Example:
1,d1s2,d01s2_Out,swap
If the module has both inputs and outputs, you can apply swap to the input mapping, the
output mapping, or both.