LEGAL
UL/cUL RESIDENTIAL FIRE & BURGLARY INSTALLATIONS
Note:
For ULC Residential Fire and Burglary (ULC-S304 Level I) installations set for daily test transmission, Wireless
Supervision window shall be set to 4 hours for UL/ULC Residential Fire Installations. Wireless Supervision window shall be
set to 24 hours for Residential Burglary Installations only. RF Jam detection shall be enabled.
For UL 985 6th Ed. Compliant installations using also the Wi-Fi connection, ensure Power for network equipment such as
hubs, switches, routers, servers, modems, etc., is backed up or powered by an uninterruptible power supply (UPS), standby
battery or the control unit, capable of facilitating 24 h standby
Note
: For UL residential fire and burglary applications, it is required to use UL listed compatible siren models PG9901 or
PG9911 to provide mandatory local notifications for fire and burglary alarms. A maximum of two daughter radio cards
(PowerG, SRF319, SRF345, SRF433 [DSC or AT&T], and Zigbee) shall be used in the available slots.
Note
: SRF345, SRF433 and SRF433 AT&T cards along with the compatible devices are UL/cUL listed only for use in
residential fire and burglary applications (ULC-S304 Security Level I).
QOLSYS CONFIDENTIAL AND PROPRIETARY
PAGE
OF
165
197
Содержание IQ4 Hub
Страница 8: ...INSTALLING THE PANEL...
Страница 13: ...USER INTERFACE...
Страница 17: ...PROGRAMMING...
Страница 54: ...SECURITY SENSORS...
Страница 86: ...WI FI DEVICES...
Страница 95: ...Z WAVE DEVICES...
Страница 106: ...BLUETOOTH DEVICES...
Страница 113: ...SYSTEM TESTS...
Страница 136: ...CUSTOMIZATION...
Страница 146: ...MAINTENANCE...
Страница 153: ...TROUBLESHOOTING...
Страница 162: ...LEGAL...
Страница 179: ...SPECIFICATIONS...