 Installation instructions

 Note

• Install the 

line

 pressure regulator in such a way that it is protected against mechanical

 

damage. Also note

 

that electricity must be kept separate from gas pipelines according to current

 

standards, see SIS HB 370.

• The installer must have the required product knowledge and 

certificatin for shield gas brazing

 and

 

have

 

undergone 

brazing certification

 in accordance with EN 13585 and EN 13134. 

Brazing

 must take

 

place

 

with shielding gas,

 

without flux and with silver phosphor copper 

with a minimum of 5% silver content

article number QMT

 

7200812.

• The components of the 

line

 pressure regulator must not be exposed to temperatures

 

exceeding 100 ° C.

• The installer must ensure that the correct gas and function are achieved through safety testing and

 

that

 

the system complies with EN 7396-1 and national standard SIS HB 370.

• The system must be inspected for safety before commissioning in accordance with current

 

standards.

 Warning

The use of shielding gas in medical gas systems must be carefully planned and separated from the 

rest of the system. After 

brazing 

and testing is completed, the system is flushed with the medical gas 

(= drug) to be contained in the system, to prevent personal injury. See SIS HB 370 and the hospital's 

instructions.

The components of the 

brazing

 pressure regulator must not be exposed to temperatures exceeding 

100 ° C, either during installation or operation. Should this happen or suspect that this has 

happened, the 

components

 must be replaced and the system cleaned. In the event of fire, the 

affected section must be separated and decontaminated immediately before operation. Sealing 

plugs, packaging or protective packaging must not be removed until at the time of installation, as 

there may be a risk of damaging or contaminating the product.

Mounting: 

Fasten the bottom plate to the wall

with required screw

s

 (4 pcs).

For all gases except Air and

 AIR for

driving surgical tools

, the

 

outlet pipe

from the 

safety relief valves

 

must be

evacuated to the outside of

 

the

building according to EN 7396-1 and

SIS HB 370.

When brazing

 the inlet connection (1),

shielding gas can be connected

through connection (

1a) or (1b)

.

 

NOTE!

Remember that valves (4a)

 

and (4b)

must be open.

When brazing

 the outlet connection

(2),

 

shielding gas can be connected

through gas outlets (2a) or (2b).

 

NOTE!

Remember that valves (5a)

 

and (5b)

must be open.

When brazing

 the outlet pipe (6) from

the

 

safety valve (3), shielding gas can

be

 

connected through gas outlets (2a)

or

 

(2b). NOTE: Remember that valves

(5a) and (5b) must be open and that at

least one of the relief valves of the

safety valves must be kept open 

,for

example with a wedge.

2a

3

2

2b

1b

1

5b

5a

4b

4a

6

7

1

a

Содержание QMT 7MS028 Series

Страница 1: ...ine pressure regulator 210331 3 Art nr QMT 7MS028XXX QMT 7MS035XXX QMT 7MS042XXX QMT 7MS054XXX Phone 46 0 480 44 02 00 Telefax 46 0 480 44 00 10 Address Amerikav gen 6 393 56 KALMAR Sweden Website e p...

Страница 2: ...Contents 3 4 4 4 5 5 6 6 7 8 8 8 2 instructions...

Страница 3: ...ly accessible if necessary more copies can be ordered from Qmt tech If something is unclear you can also call us at 0480 440200 Ensure the following The medical gases must not come into contact with o...

Страница 4: ...outlet nominal distribution pressure is standard Pressure transducer for inlet nominal supply system pressure is option Optionally contact gauges can be fitted instead of pressure transducers The uni...

Страница 5: ...lockwise Check against the pilot regulator pressure gauge and the outlet pressure gauge Lower the operating pressure by carefully opening the adjusting screw C on the regulator outlet side until a low...

Страница 6: ...ators and safety valves can be serviced or replaced without interruption by isolating the circuit to be serviced with the shut off valves Note that during service during operation a circuit must alway...

Страница 7: ...70 and the hospital s instructions The components of the brazing pressure regulator must not be exposed to temperatures exceeding 100 C either during installation or operation Should this happen or su...

Страница 8: ...4 Black 2 Blue Connect to low alarm Connect to common conductor Connect to high alarm Spare parts QMT 78500XX QMT 7611XXX QMT 7200013 QMT QMT article number for Reulators Valves Pressure gauges Transm...

Отзывы: