background image

Mounting the Heater - General

The heater may be mounted to discharge the heated air either
horizontally or vertically. when the heater is mounted for vertical
discharge, it is recommended that the heater be positioned so
that the access door will open away from the wall to provide
greater access to the wiring and control compartment. if the
heater is to be mounted with the access door facing a wall, the
heater must be mounted far enough from that wall to allow full
opening of the access door (a distance approximately equal to
the width of the heater, check clearance before installing).  Refer
to Table 1 for wall and ceiling clearances before mounting heater. 

The heater may be mounted for either vertical or horizontal dis-
charge by the use of threaded rods. (Refer to Table 2 for thread-
ed rod sizes required.) observe the detailed procedures in the
following installation instructions.

The heater may also be suspended from the wall or ceiling by
means of an optional mounting bracket (type MMB or MCMB)
which permits horizontal pivoting of the heater.

After the heater is installed, the louvers may be positioned to
direct the heated air in the desired direction. when the heater is
installed for horizontal discharge, the louvers should direct the
air either straight ahead or downward. Directing the air upward
may cause the heated air to remain in the ceiling area and waste
energy.

Horizontal Discharge (rod-mount from Ceiling)

1. install four threaded mounting rods in the threaded holes and

secure in place using lock nuts.  (see Table 2).

2. securely attach the four mounting rods to the ceiling.  (Refer

to Table 1 for wall and ceiling clearances, and Table 2 for
mounting rod spacing).

Vertical Discharge (rod-Mount from Ceiling)

1. Remove bolts  from the threaded holes in the back of the

heater.

2. install four threaded mounting rods in the threaded holes and

and secure in place using lock nuts.

3. securely attach the four mounting rods to the ceiling.  (Refer

to Table 1 for wall and ceiling clearances, and Table 3 for
mounting rod spacing dimensions.)

Wiring Branch Circuit (Power)

1. Connect heater only to the voltage, amperage and frequency

specified on the nameplate.

2. field wiring must be properly sized to carry the amperage in

accordance with the NEC.

3. The access door is hinged.  There are either one or two screws

accessible from the side that must be loosened to gain access.
These screws are the captive type; do not try to remove them.

4. A knockout is provided in the back of the heater close to the

power terminal block and the control terminal board. The con-
trol terminal board knockout is 1/2 inch (12.7 mm) conduit size.
The power terminal block knockout is multiple diameter.  Use
the diameter that fits the required conduit size.

5. A ground terminal is provided near the power terminal board.

The ground wire should be connected before other connections
are made.

6. The power terminal block is equipped with box terminals sized

to accept the correct size power supply wire.  Branch circuit
wire rated min 600V, 60° C is acceptable for heaters rated up to
80 amps. for heaters rated more than 80 amps, branch circuit
wire must be rated at least 75°C. Either aluminum or copper
wire is satisfactory for connection to the heater power terminal
block box terminal.  Copper wire is recommended and must be
used with built-in disconnect switch.

3

A

B

C

D

Figure 1. Horizontal Discharge Mounting and Spacing.

CEIlING

BaCK Wall

B
a
C
K

W
a
l
l

S
I
D
E

W
a
l
l

MOUNtING
rOD

lOCK NUt

UNIt HEatEr

THREADED

MoUNTiNg

HoLEs

B

a

D

C

(tOP VIEW)

table 2. rod thread and Spacing Dimensions, inches (mm) 

for Horizontal Discharge

rod thread

Unit

type

a

B

C

D

3 - 5 kw

6

4

1

/

16

3

/

4

6

1

/

16

(152.4)

(103.1)

(19.0)

7.5 - 10 kw

5

/

16

- 18

(153.9)

15 - 20 kw

11

3

/

8

8

7

/

8

5

1

/

8

3

/

4

(289.0)

(225.6)

(130.3)

(19.0)

25 - 30 kw

10

9

/

16

14 - 12

6

3

/

16

5

/

8

(268.2)

(368.3)

(157.2)

(16.0)

40 - 50 kw

3

/

8

- 16

15

15

/

16

14 - 12

6

3

/

16

5

/

8

(404.9)

(368.3)

(157.2)

(16.0)

table 1. Wall and Ceiling Clearance, inches (mm)

Unit

Discharge

Ceiling

Side Wall

Back Wall

3 & 5 kw

Horiz.

2 (50.8)

6 (152.4)

9 (228.6)

Vert.

6 (152.4)

18 (457.2)

18 (457.2)

7.5 to 10 kw

Horiz.

6 (152.4)

6 (152.4)

13 (330.2)

Vert.

6 (152.4)

24 (609.6)

24 (609.6)

15 to 10 kw

Horiz.

6 (152.4)

9 (228.6)

12

1

/

2

(317.5)

Vert

6 (152.4)

24 (609.6)

24 (609.6)

25 to 50 kw

Horiz.

16 (406.4)

12 (304.8)

18

1

/

2

(470.0)

Vert.

12 (304.8)

39 (914.4)

39 (914.4)

Figure 2. Vertical Discharge Mounting and rod Spacing

CEIlING

B
a
C
K

W
a
l
l

S
I
D
E

W
a
l
l

ACCEss
DooR

MoUNTiNg
RoD (4)

THREADED
MoUNTiNg
HoLEs

CLEARANCE EQUAL To wiDTH of
HEATER  To  pERMiT  fULL  opEN-
iNg of THE ACCEss DooR

LoCK NUT

BaCK Wall

E

H

f

g

(tOP VIEW)

Table 3. Rod Thread and Spacing Dimensions, inches (mm) 

for Vertical Discharge

rod thread

Unit

type

E

F

G

H

3 - 5 kw

6

9

3

/

4

2

4

1

/

16

5

/

16

- 18

(152.4)

247.7)

(50.8)

(103.1)

7.5 - 20 kw

8

7

/

8

14

5

/

8

2

5

1

/

8

(225.6)

(371.6)

(50.8)

(130.3)

25 - 30 kw

3

/

8

- 16

14

1

/

2

21

1

/

4

2

3

/

16

6

3

/

16

(368.3)

(539.8)

(56.0)

(157.2)

Содержание MUH Series

Страница 1: ...71 2 38 17 2 100 in3 MUH102 552 5 482 6 190 5 38 17 2 1639 cm3 MUH107 38 17 2 MUH104 38 17 2 MUH073 38 17 2 MUH076 38 17 2 MUH103 38 17 2 MUH106 38 17 2 Mounting Wiring Basic Model Height Width Depth...

Страница 2: ...nect panel 9 Do not insert or allow foreign objects to enter any ventilation or exhaust opening as this may cause an electric shock fire or damage to the heater 10 To prevent a possible fire do not bl...

Страница 3: ...ne or two screws accessible from the side that must be loosened to gain access These screws are the captive type do not try to remove them 4 A knockout is provided in the back of the heater close to t...

Страница 4: ...3b and following the directions shown below on models MUH0521 MUH0581 MUH072 MUH078 MUH102 and MUH108 figure 3a move only the two wires marked A1 and marked B1 do not move or change any other wiring...

Страница 5: ...e heater example MUH0581 is rated 24 amps 4 on units provided with internal contactor units rated 7 Kw and higher refer to figure 5 for wiring diagram Control wiring must be rated minimum 18 Awg OPEra...

Страница 6: ...ded minimum torque of 35 in lbs 3 9 N m After completing the cleaning and servicing the heater should be fully reassembled and checked for proper operation MaINtENaNCE INStrUCtIONS it is important to...

Страница 7: ...0010 000 14 speed Nut 4100 7036 026 15 Bracket Captive screw used on MUH 03 thru MUH 20 only 1215 0291 000 Bracket Captive screw used on MUH 25 thru MUH 50 only 1215 0289 000 17 protector Linear Limi...

Страница 8: ...8...

Страница 9: ...5814 0003 002 3900 0363 000 1210 0098 000 1402 0340 002 1425 0012 003 1802 0087 019 2504 0014 001 1432 0002 003 MUH 30 8 1425 0011 003 5814 0003 000 3900 0364 000 1210 0098 000 1402 0340 002 1425 000...

Страница 10: ...Marley Engineered products service Center and we will repair or replace at our option at no charge to you with return freight paid by Marley it is agreed that such repair or replacement is the exclus...

Страница 11: ...4 19 71 2 38 17 2 100 pulg 3 MUH102 552 5 482 6 190 5 38 17 2 1639 cm3 MUH107 38 17 2 MUH104 38 17 2 MUH073 38 17 2 MUH076 38 17 2 MUH103 38 17 2 MUH106 38 17 2 altura ancho Prof Peso de Volumen del...

Страница 12: ...n del circuito del cale factor en el tablero de desconexi n principal 9 No inserte ni permita que entren objetos extra os en ninguna aber tura de ventilaci n o de descarga porque esto puede ser causa...

Страница 13: ...ceso est abisagrada Existen uno o dos tornillos accesibles desde el costado que deben aflojarse para tener acceso Estos tornillos son del tipo prisionero no intente quitarlos 4 se ha provisto un prepu...

Страница 14: ...zos en el dia grama de conexionado del calefactor 10 CalEFaCtOr DE 208 240 VOltS los calefactores est n cablead os de f brica para 240 V Cuando conecte el calefactor a una fuente de alimentaci n de 20...

Страница 15: ...ALEfACToR ANTEs DE HACER CoNEXioNEs A LA pLACA DE CoNTRoL A fiN DE EViTAR UN RiEsgo DE CHoQUE EL CTRiCo 15 MT 1 MT 2 ROJO ROJO NEGRO NEGRO P2 H2 F1 F2 S P1 H1 TERMOSTATO INTERNO DE 2 ETAPAS INTERRUPTO...

Страница 16: ...para asegurar un funcionamiento eficiente observe las instrucciones simples que se indican a continuaci n Instrucciones de limpieza para el usuario 1 Despu s de que el calefactor se haya enfriado pue...

Страница 17: ...MUH25 hasta MUH 50 solamente 2900 0031 000 6 Extensi n del soporte utilizado en MUH 15 MUH 20 MUH 40 y MUH 50 solamente 1215 0282 000 7 soporte de interruptor 1215 0256 000 8 Retardo del ventilador 4...

Страница 18: ...TA MUH 20 soLAMENTE VisTA D D MUH 03 HAsTA MUH 05 soLAMENTE EsTAs piEzAs sE UsAN EN EL MoDELo MUH05 21T soLAMENTE VisTA B B VisTA C C VER VisTA VER VisTA VER VisTA VER VisTA 23 No sE UsA CUANDo sE UsA...

Страница 19: ...8 000 1402 0340 002 1425 0009 009 1802 0087 028 2504 0014 001 1432 0002 001 MUH 40 2 1425 0011 001 5814 0003 000 3900 0350 000 1210 0097 000 1402 0340 003 1425 0012 002 1802 0087 020 2504 0015 001 143...

Страница 20: ...las limitaciones de esta garant a las unidades que no funcionan deben regresarse al centro de servicio autorizado Marley m s cercano o al Centro de servicio de Marley Engineered products y nosotros l...

Страница 21: ...4 19 71 2 38 17 2 100 po 3 MUH102 552 5 482 6 190 5 38 17 2 1639 cm3 MUH107 38 17 2 MUH104 38 17 2 MUH073 38 17 2 MUH076 38 17 2 MUH103 38 17 2 MUH106 38 17 2 N de Hauteur largeur Profondeur Poids de...

Страница 22: ...bjets trangers et ne permettez pas qu il en entre dans toute ouverture d admission ou d vacuation car cela peut causer une commotion lectrique ou un d part d incendie ou endommager le radiateur 10 pou...

Страница 23: ...is accessibles depuis le dessous qu il faut desserrer pour obtenir l acc s Ce sont des vis de type imperdable donc n essayez pas de les enlever 4 Une pastille enfoncer est fournie au dos du radiateur...

Страница 24: ...ne ont leur connexion indiqu e en lignes pointill es sur le sch ma de c blage du radiateur 10 Radiateur en 208 240 volts Les radiateurs sont c bl s en usine pour du secteur 240 V Quand un tel radiateu...

Страница 25: ...onnement efficace suivez les instructions simples ci dessous LA TENsioN sECTEUR EsT pR sENTE sUR CERTAiNEs BoRNEs DE LA CARTE DE TERMiNAisoN DEs CoNTR LEs CoUpEz ToUJoURs L ALiMENTATioN sECTEUR EN AMo...

Страница 26: ...vec son accessoire brosse pour liminer la poussi re et les peluches des surfaces ext rieures du radiateur y compris les ouver tures de la grille 2 Avec un chiffon humide enlevez toute poussi re et pel...

Страница 27: ...072 000 3 l ment de retenue ressort 5208 0074 000 4 Commutateur sur MUH 25 MUH 50 seulement 5216 7076 001 5 isolateur sur MUH 25 MUH 50 seulement 2900 0031 000 6 support prolong sur MUH 15 MUH 20 MUH...

Страница 28: ...05 sEULEMENT CEs pi CEs soNT UTiLis Es sUR MoD LEs MUH05 21T sEULEMENT VUE B B VUE C C VoiR VUE VoiR VUE VoiR VUE VoiR VUE 23 NoN UTiLis QUAND 2 pi CEs 17 soNT UTiLis Es AgRAfE DE T MoiN No 1403 0041...

Страница 29: ...009 1802 0087 028 2504 0014 001 1432 0002 001 MUH 40 2 1425 0011 001 5814 0003 000 3900 0350 000 1210 0097 000 1402 0340 003 1425 0012 002 1802 0087 020 2504 0015 001 1432 0002 004 MUH 40 4 1425 0011...

Страница 30: ...RANTiE EXpREssE oU iMpLiCiTE ET ToUTE gARANTiE iMpLiCiTE DE CoMMER CiALisATioN oU DE CoNVENANCE UN UsAgE QUELCoNQUE ALLANT AU DEL DE LA gARANTiE EXpREssE Ci DEssUs EsT pAR LEs pR sENTEs R fUT E ET EXC...

Отзывы: