IS535 ECN 3673
Page 3 of 9
SAFETY INSTRUCTIONS
Installation, commissioning and servicing must only be
carried out by qualified personnel in compliance with
national and local regulations in force in the country of
installation.
Warning
The manufacturer assumes no liability resulting from failure
to follow the instructions in this booklet.
INSTALLATION
Location of installation
Technical data, dimensions, and connections are
provided in the Appendix.
The appliance must be installed in a well
ventilated place. For this reason, rooms must be
ventilated in compliance with existing technical
regulations. The airflow must not be less than 2
cubic metres per hour per kW of installed capacity.
The appliance must be installed at least 300mm
from any potential side walls, 1,000mm from
ceilings and 100mm from any potential back walls.
Ensure all vents are unobstructed.
If the appliance must be fitted near walls,
partitions, kitchen furniture, decorative elements
etc, we recommend they are made from non-
inflammable material; otherwise they should be
covered with a suitable heat resistant material.
We recommend full attention is paid to fire
regulations.
Install this appliance beneath an extraction
canopy.
Assembly
Before connecting the appliance, all protective
covers must be removed. Clean the work area
and external parts carefully with a solvent to
remove any traces of glue.
Check with a spirit level. Levelling can be
achieved by adjusting the legs.
Connecting appliances (Fig 1)
Place the appliances together and adjust them to
the same level using the adjustable feet.
Connect the appliances using the holes situated
on the side at the front and back of the hob.
Connecting to an electricity supply
Before connecting the appliance, check that the
mains voltage corresponds to the value shown on
the data plate.
The appliance must be powered by a separate
electric cable which is properly specified (see
Table T1)
The cable type should be at least H 07 RN-F.
Fixed wiring insulation must be protected by
insulated sleeving having a temperature rating of
at least 60 Deg C.
Connect the cable to the terminal board following
the instructions on the electrical diagrams on the
appliance.
Ensure the earth cable is longer than the other
cables, so that in the event that the cable clamp
breaks, it is the last lead to disconnect.
For a direct connection to a power supply, a
device which guarantees disconnection from the
power supply is required, with a minimum contact
separation of 3mm to ensure complete
disconnection in case of overvoltage in category
III, in compliance with installation instructions.
Earth and equipotential connection
The appliance must be connected to an
equipotential system
– the terminal is situated
near the entry point of the electrical supply cable
and is marked by the symbol
The appliance must be earthed. Connect the
earth cable to the terminal near the
terminal block marked by the symbol
ADJUSTMENT FOR DIFFERENT VOLTAGES
To convert the appliance to a different type of voltage:
Changing the electrical connections
Remove the control panel.
Work on the terminal block, and then replace the
data plate on the side of the appliance with the
correct label indicating the new voltage and
electrical details.
PREPARING FOR OPERATION
Inspection of the electrical supply
Start the appliance following the operating
instructions and ensure that it is working correctly.
Operate the oven following the operating
instructions. Check the condition of control
devices and elements, trying all modes of heating
i.e.grill only, floor only etc.
In the event of a failure, the appliance is equipped
with a safety thermostat that interrupts the supply.
In the event of this operating, identify and rectify
the cause of the fault and restart the appliance by
resetting the thermostat manually by pushing the
red button situated under the thermostat.
Inspection of the rated thermal output
When the installation, conversion and adjustment
operations are complete or after maintenance,
please verify the condition of the appliance and
check the rated thermal output and supply voltage
as indicated in table T1.
Attention: If the electrical supply values are not
within the limits indicated in table T1, switch off the
appliance and contact your electrical supply
company.
Fig 1
ENG