INSTALLATION AND OPERATION MANUAL SOLAR MODULES DUO-G5.X – HANWHA Q CELLS – EN
INSTALLATION AND OPERATION MANUAL SOLAR MODULES DUO-G5.X – HANWHA Q CELLS – EN
15
14
DANGER!
Risk of fatal injury due to electric shock!
When disconnecting an electric circuit carrying direct
current, electric arcs can occur that may result in
life-threatening injuries.
Ä
Do NOT unplug the cable when under load.
Ä
Do NOT connect any exposed cable ends.
A solar module generates electrical current and voltage
even at a low intensity of illumination. Sparks and electric
arcs may result from the separation of a closed circuit.
These can result in life-threatening injuries. The danger
increases when several modules are connected in series.
Ä
Please be aware of that the entire open circuit voltage
is active even at low levels of solar irradiation.
Ä
Please follow the valid national regulations and safety
guidelines for the installation of electrical devices and
systems.
Ä
Please make sure to take all necessary safety precautions.
With module or phase voltages of more than 120 V, the
extra-low voltage range is exceeded.
Ä
Carry out work on the inverter and the wiring with extreme
caution.
Ä
Ensure that the modules are disconnected at the inverter
prior to separation.
Ä
Be sure to observe the time intervals specified by the
inverter manufacturer after switching off the inverter.
DANGER
! Risk of fatal injury due to electric
shock!
Ä
Never open the junction box.
Ä
Do not remove bypass diodes.
DANGER
! Risk of fatal injury due to electric
shock!
Ä
Never touch live contacts with bare
hands.
Ä
Cover connectors by suitable protective
caps until installation.
DANGER
! Risk of fatal injury due to electric
shock!
Ä
Insulate any exposed cable ends.
Ä
Only connect cables with plugs.
DANGER
! Risk of fatal injury due to electric
shock!
Ä
Only use dry, insulated tools for electrical
work.
4.1 Safety
4
ELECTRICAL CONNECTION
DANGER
! Risk of fatal injury due to electric
shock!
Ä
Ensure correct polarity.
DANGER
! Risk of fatal injury due to electric
shock!
Ä
Be sure to maintain the time intervals as
specified by the inverter manufacturer
between switching off the inverter and
beginning any further work.
DANGER
! Risk of fatal injury due to electric
shock!
Ä
Never plug or unplug the cable when
under load. Modules must not carry any
current.
1.
Switch off the inverter.
OFF
EN
3.
Switch off the DC circuit breaker.
Ä
Disconnect plugs by the use of
appropriate and qualified tools of the
manufacturer.
2.
Cover the modules to be connected or
disconnected.
4.2 Electrical installation safety
4
ELECTRICAL CONNECTION
Ä
Maximum allowed bend of the cable is
with a radius of 8 times the width of
the cable. Q CELLS standard cable is
< 7.5 mm, resulting in a maximum bend
with a radius of 60 mm.
EN
(60mm)