Operating Manual: RWM MC - Diagnostic device for smoke alarm devices
EN
41
EN
(3)
Switch on the RWM MC again.
(See chapter 5.1 “Switch on the
RWM MC“ on page 33)
(4)
If necessary, send in the faulty
device to your retailer.
f
Observe chapter 6 “Packaging, trans-
port and storage“ on page 42.
The smoke alarm device is not
connected or faulty
If a smoke alarm device is not connected
with the RWM MC or is faulty, the message
“FEHLER - Verbindung fehlgeschlagen - Kabel
prüfen sonst Melder defekt / Batt. leer”
(ERROR - connection failed - check cable
otherwise detector defect / battery empty)
will appear.
Proceed as follows:
(1)
Check the connection between the
RWM MC and the smoke alarm device.
f
If applicable, connect the RWM MC
to the smoke alarm device. (See chap-
ter 5.2 “Connect the RWM MC to the
smoke alarm device“ on page 33)
(2)
Check whether the smoke alarm
device to be tested is switched on
and operates.
f
Switch on the smoke alarm device.
(See operating manual for the
smoke alarm device)
f
Press the Testing / stop button on the
smoke alarm device. (See operating
manual for the smoke alarm device)
If the smoke alarm device does not emit a
test tone, the smoke alarm device is faulty
and must be replaced.
f
Replace the smoke alarm device.
(See operating manual for the
smoke alarm device)
f
Repeat the readout procedure.
(See chapter 5.3 “Reading out the
smoke alarm device“ on page 34)