5. Trouble Shooting Steps 

5.1 Problem determination based on: 

1) Whether the battery can be turned on or not; 
2) If battery is turned on, check the red light is off, flashing or lighting; 
3) If the red light is off, check whether the battery can be charged/discharged or not. 

5.2 Preliminary determination steps: 

1) Battery cannot turn on, switch on the lights are all no lighting or flashing. 
If the battery external switch is ON, the RUN light is flashing, and the external power supply 
voltage is 48V or more, the battery still unable to turn on, please contact distributor. 
 
2) The battery can be turned on, but red light is lighting, and cannot charge or discharge. If the 

red light is lighting, that means system is abnormal, please check values as following: 

a) Temperature: Above 50

 or under -10

, the battery could not work. 

Solution: to move battery to the normal operating temperature range between -10

 and 50

 

 
b) Current: If current is greater than 100A, battery protection will turn on. 
Solution: Check whether current is too large or not, if it is, to change the settings on power supply 
side. 
 
c) High Voltage: If charging voltage above 54V, battery protection will turn on. 
Solution: Check whether voltage is too high or not, if it is, to change the settings on power supply 
side.  
 
d) Low Voltage: When the battery discharges to 44.5V or less, battery protection will turn on. 
Solution: Charge the battery for some time, the red light turn off   
 

Excluding the four points above, if the faulty is still cannot be located, turn off battery and repair. 

 
5.3 The battery cannot be charged or discharged   

1) Cannot be charged:   
Disconnect the power cables, measure voltage on power side, if the voltage is 53~54V, restart 
the battery, connect the power cable and try again, if still not work, turn off battery and contact 
distributor . 
2) Unable to discharge:   
Disconnect the power cables and measure voltage on battery side, if it is under 44.5V, please 
charge the battery; if voltage is above 48V and still cannot discharge, turn off battery and 
contact distributor. 

21

 / 

23

 18BQSV0801 

Содержание US3000 Plus

Страница 1: ...Information Version 1 1 Lithium Iron Phosphate Battery US3000 Product Manual...

Страница 2: ...6 Definition of RJ11 Port Pin 7 LED Indicators Instructions 8 3 SAFE HANDLING OF LITHIUM BATTERIES GUIDE 9 3 1 Schematic Diagram of Solution 9 3 2 Explanation of Symbol 9 3 3 Tools 10 3 4 Safety Gear...

Страница 3: ...s 10 Do not connect battery with PV solar wiring directly 11 The warranty claims are excluded for direct or indirect damage due to items above 12 Any foreign object is prohibited to insert into any pa...

Страница 4: ...y QC tab removed or damaged 5 In case of fire only dry powder fire extinguisher can be used liquid fire extinguishers are prohibited 6 Please do not open repair or disassemble the battery except staff...

Страница 5: ...e module is non toxic non polluting and environmentally friendly Cathode material is made from LiFePO4 with safety performance and long cycle life Battery management system BMS has protection function...

Страница 6: ...V e g a t l o V e g r a h C Recommend Charge Discharge Current A 37 4 7 A t n e r r u C e g r a h c s i D e g r a h C x a M Peak Charge Discharge c e s 5 1 A 0 0 1 A t n e r r u C N A C 5 8 4 S R 2 3...

Страница 7: ...S3000B does not have this LED light Alarm Alarm light red LED flashing to show the battery has alarm and lighting to show the battery is under protection SOC SOC light 6 green LEDs to show the battery...

Страница 8: ...s 1 0 1 5th 5th battery group s master battery should setup as this 0 1 1 6th 6th battery group s master battery should setup as this 1 1 1 7th 7th battery group s master battery should setup as this...

Страница 9: ...or power cables uses water proofed connectors It must keep pressing this Lock Button during pulling out the power plug Dry Contact Terminal Dry Contact Terminal provided 1 way input and 3 ways output...

Страница 10: ...ON flash on 0 3s off 3 7s flash on 0 5s off 1 5s BMS function Protection and Alarm Management and Monitor Charge Discharge End Cells Balance Charge Over Voltage Intelligent Charge Model Discharge Unde...

Страница 11: ...3 Safe handling of lithium batteries Guide 3 1 Schematic Diagram of Solution 3 2 Explanation of Symbol PV ARRAY Public Grid Local Load INVERTER BATTERY MODULE 1 2 9 23 18BQSV0801...

Страница 12: ...prevent accidental electric shock or short circuits If insulated tools are not available cover the entire exposed metal surfaces of the available tools except their tips with electrical tape 3 4 Safet...

Страница 13: ...Grounding cable 2 For Battery system connects to inverter Two long power cables current capacity 120A and one communication cable for each energy storage system NOTE These three long cables are belong...

Страница 14: ...ature and humidity is maintained at a constant level There is minimal dust and dirt in the area CAUTION If the ambient temperature is outside the operating range the battery pack stops operating to pr...

Страница 15: ...Put the battery into the cabinet Drive the 4 pcs screws Connect the cables between battery modules Connect the cables to inverter 13 23 18BQSV0801...

Страница 16: ...cable and communication cable 1 Switch power on Switch on all the battery modules 2 The one with empty Link Port 0 is the Master Battery Module others are slaves 1 master battery configure with maxim...

Страница 17: ...battery to power on all the battery LED light will be on one by one from the Master battery If all the battery LED lights on and then off which means the battery system is good and working C Installat...

Страница 18: ...16 23 18BQSV0801...

Страница 19: ...Aim at the 4 pare of Location Pin and Location Hole stack the batteries together And hasp the 4 agraffes together 17 23 18BQSV0801...

Страница 20: ...Maximum 4 batteries can be athwart stacked One or two batteries can be sidelong stacked Cables connection and batteries system start are same as cabinet installation 18 23 18BQSV0801...

Страница 21: ...id power it should turn on the inverter at first to avoid current pulse of the inverter add on the battery bank z Between battery bank and inverter should install breaker to protect system safety z Al...

Страница 22: ...20 23 18BQSV0801...

Страница 23: ...is greater than 100A battery protection will turn on Solution Check whether current is too large or not if it is to change the settings on power supply side c High Voltage If charging voltage above 5...

Страница 24: ...ATER Only dry powder fire extinguisher can be used if possible move the battery pack to a safe area before it catches fire 3 Wet Batteries If the battery pack is wet or submerged in water do not let p...

Страница 25: ...Pylon Technologies Co Ltd No 73 Lane 887 ZuChongzhi Road Zhangjiang Hi Tech Park Pudong Shanghai 201203 China T 86 21 51317697 F 86 21 51317698 Eservice pylontech com cn Wwww pylontech com cn...

Отзывы: