Caution:
It shall be installed an AC breaker outside for AC short-circuit protection. The
specifications of the breaker shall meet the system's parameters. System parameters
refer to the system parameters table (chapter 2.2.1)
Dry Contact Terminal
Dry Contact Terminal: provided 2 input and 4 output dry contact signal.
Reset
Reset Button: Long press this button to restart the battery system.
ADD
ADD: 6 bit dial switches to manually distribute the communication address of the battery
system. Nether position is OFF, means “0”. Upper position is ON, means “1”. 1
st
bit to 5
th
bit is for
address, and the 6
th
bit dial switch support a 120
Ω
resistance.
Power Output Switch
To control the mains DC circuit open/close after the Control Module Power Switch ON.
Caution:
When the breaker is tripped off because of over current or short circuit, must
wait after 30min to turn on it again, otherwise may cause the breaker damage.
Isolating switch
To control the high voltage DC power output ON/OFF during the Control Module Power
Switch ON.
Start Button
Start Button: press more than
5sec until the buzzer rings, to
start the battery module,
power output ready.
CAN / RS485
CAN Communication Terminal: (RJ45 port) follow CAN protocol, for communication between
battery system and inverter.