Range
Min
Max
Fact. Set
Sr.No.
Parameter
(LCD Message)
Description of parameters and functions.
Parameter setting
method.
AFT PROBE STATUS
Disable= It disables the Anti. Freeze Trip
function of the controller
Enable = It enables the Anti. Freeze
Trip function of the controller
Use UP/DOWN keys to set desired
range.
To change the parameter,
press the set key.
08
Range
Min
Max
Fact. Set
Function: To enable or disable Antifreeze
probe function.
EXAMPLE:
Setting this parameter at
0
6.0 C will not allow the set point to go
0
below 6.0 C Also, if the temperature
0
reaches or goes below 6.0 C the display
will show Low Temp. Alarm and at this
point the alarm will activate.
AFT Set
Point
+1.0ºC
- 0.5ºC
Set Point
6.0ºC
Disable
Enable
Disable
07
AFT SET TEMP
Use UP/DOWN keys to set desired
range.
EXAMPLE:
If this parameter is set to
5.0ºC controller will trip the compressor
on Antifreeze fault if the AFT sensor
goes below 5.0ºC.
press the set key.
To change the parameter,
09
Range
Min
Max
Fact. Set
Function: To set Antifreeze tripping point.
-30.0ºC
Lt-1.0ºC
5.0ºC
LOW TEMP. ALARM
07
Function: To set minimum allowable low
temperature limit and alarm.
To change the parameter,
press the set key.
Use UP/DOWN keys to set desired range.
Once set at a particular range, this will not
allow the set point to go below this range
and above Low Temp Alarm setting.
NC-110A
Sr.No.
Parameter
(LCD Message)
Description of parameters and functions.
Parameter setting
method.
08
LIQ. PROBE CAL
Use UP/DOWN keys to set desired range.
During the course of time there may be a
slight offset in the actual temperature and
the temperature displayed.
EXAMPLE:
If the actual temperature is
20.0ºC and the temperature on the
controller shows 22.0ºC set this
O
parameter to -2.0 C and once out of this
mode, the temperature will display
20.0ºC. (22.0ºC-2.0ºC).
press the set key.
To change the parameter,
11
Range
Min
Max
Fact. Set
Function: To set Main(Liquid) probe
calibration.
AFT DIFFERENTIAL
To change the parameter,
press the set key.
10
Function: To set fault resetting
differential once it tripped of Aft set point.
Use UP/DOWN keys to set desired
range.
EXAMPLE:
If the AFT set point is set at
5.0ºC and differential is set to 2.0ºC then
after tripping on AFT fault controller will
clear the AFT fault only when the AFT
Temperature goes above
7.0ºC(5.0ºC+2.0ºC).
1.0ºC
10.0ºC
2.0ºC
Range
Min
Max
Fact. Set
-10.0ºC
10.0ºC
0.0ºC
AFT PROBE CAL
Setting Procedure same as Liq. Probe
Cal.
Use UP/DOWN keys to set desired
range.
To change the parameter,
press the set key.
12
Function: To set Antifreeze probe
calibration.
Range
Min
Max
Fact. Set
-10.0ºC
10.0ºC
0.0ºC
NC-110A