Range

Min 

Max 

   Fact. Set 

Sr.No. 

Parameter 

(LCD Message)

Description of parameters and functions.

Parameter setting

 method. 

AFT PROBE STATUS

Disable= It disables the Anti. Freeze Trip 
function of the controller
 Enable = It enables the Anti. Freeze 
Trip function of the controller

Use UP/DOWN keys to set desired 
range. 

To change the parameter,
press the set key.

08

Range

Min 

Max 

   Fact. Set 

Function: To enable or disable Antifreeze  
probe function.

EXAMPLE: 

Setting this parameter at 

0

6.0 C  will not allow the set point to go 

0

below 6.0 C Also, if the temperature 

0

reaches or goes below 6.0 C  the display 

 

will show Low Temp. Alarm and at this 
point the alarm will activate.

AFT Set 

Point 

+1.0ºC

- 0.5ºC

Set Point

6.0ºC

Disable

Enable

Disable

07

AFT SET TEMP

Use UP/DOWN keys to set desired 
range. 

EXAMPLE:

 If this parameter is set to  

5.0ºC controller will trip the compressor 
on Antifreeze fault if the AFT sensor 
goes below 5.0ºC.

press the set key.

To change the parameter,

09

Range

Min 

Max 

   Fact. Set 

Function: To set Antifreeze tripping point.

-30.0ºC

Lt-1.0ºC

5.0ºC

LOW TEMP. ALARM

07

Function: To set minimum allowable low 
temperature limit and alarm.

To change the parameter,
press the set key.

Use UP/DOWN keys to set desired range. 
Once set at a particular range, this will not 
allow the set point to go below this range 
and above Low Temp Alarm setting.

NC-110A

Sr.No. 

Parameter 

(LCD Message)

Description of parameters and functions.

Parameter setting

 method. 

08

LIQ. PROBE CAL

Use UP/DOWN keys to set desired range. 
During the course of time there may be a 
slight offset in the actual temperature and 
the temperature displayed.

EXAMPLE:

 If the actual temperature is 

20.0ºC and the temperature on the 
controller shows 22.0ºC set this 

O

parameter to -2.0 C and once out of  this 
mode, the temperature will display 
20.0ºC. (22.0ºC-2.0ºC).

press the set key.

To change the parameter,

11

Range

Min 

Max 

   Fact. Set 

Function: To set Main(Liquid) probe 
calibration.

AFT DIFFERENTIAL

To change the parameter,
press the set key.

10

Function: To set fault resetting 
differential once it tripped of Aft set point.

Use UP/DOWN keys to set desired 
range.

EXAMPLE:

 If the AFT set point is set at 

5.0ºC and differential is set to 2.0ºC then 
after tripping on AFT fault controller will 
clear the AFT fault  only when the AFT 
Temperature goes above 
7.0ºC(5.0ºC+2.0ºC).

1.0ºC

10.0ºC

2.0ºC

Range

Min 

Max 

   Fact. Set 

-10.0ºC

10.0ºC

0.0ºC

AFT PROBE CAL

Setting Procedure same as Liq. Probe 
Cal.

Use UP/DOWN keys to set desired 
range.

To change the parameter,
press the set key.

12

Function: To set Antifreeze probe 
calibration.

Range

Min 

Max 

   Fact. Set 

-10.0ºC

10.0ºC

0.0ºC

NC-110A

Содержание sub-zero NANOCHILL NC-110A

Страница 1: ...User Manual NANOCHILL NC 110A www pvrcontrols com RST 2 SET NANOCHILL...

Страница 2: ...Relay3 Alarm or Water Sv The Subzero NANO CHILL NC110A is a controller that integrates all the basic control functions required by a chiller A user friendly Lcd screen displays all parameters control...

Страница 3: ...ters CHILLER SET TEMP COMP TIME DELAY DIFFERENTIAL HI TEMP ALARM LOW TEMP ALARM AFTPROBE STATUS AFT SET TEMP AFT DIFFERENTIAL LIQ PROBE CAL AFT PROBE CAL FAULT SENS LOGIC LP SENSING DLY Pg No PROGRAM...

Страница 4: ...TIAL Function To set temperature differential for compressor restart Sr No Parameter LCD Message Description of parameters and functions Parameter setting method 06 HIGH TEMP ALARM EXAMPLE Setting thi...

Страница 5: ...ired range Once set at a particular range this will not allow the set point to go below this range and above LowTempAlarm setting NC 110A Sr No Parameter LCD Message Description of parameters and func...

Страница 6: ...isables Liquid level sensing in the controller Range Min Max Fact Set Disable Enable Disable PUMP RUN LOGIC RELAY3 LOGIC Use UP DOWN keys to set desired range Always On it sets the pump to always on m...

Страница 7: ...all parameters are programmed to factory settings Used to debug setting related problems Once the SET key is pressed the control goes into the normal mode and displays the temperature 21 22 Function R...

Страница 8: ...iew Max 15 mm 59 50 45 Wiring Diagram RELAY3 11 14 18 12 15 19 13 16 20 17 PHASE NEUTRAL COMP PUMP NO NO C C NC 1 4 8 2 5 3 6 7 NO C NC 9 10 POWER 230V LIQUID AFT To SZ N75 To SZ N75 HP LP LOW MED HIG...

Страница 9: ...liable for direct indirect special incidental or consequential damage arising out of the use or inability to use the product or documentation even if advised of the possibility of such damages No part...

Страница 10: ...s Globe Valves Hand Valves Flow Switches Solenoid Valves OUR OTHER PRODUCTS Cold Room Controller Chiller Controller Two Compressors Controller Heating Controller Humidity Controller Pressure Controlle...

Отзывы: