Technical and Operations Manual - Installation Guidance
17
Electrostatic Precipitator (ESP)
Filter Unit
4.4 Installing Single Units
When installing a single Unit, please note the following:
●
The Unit should be positioned as close to the cooking source as possible, but please
ensure that the fume temperature will never exceed the maximum operational
temperature of the Unit, i.e. 60
o
C.
●
Ensure that there is adequate service space around the Unit to enable the removal
of the Unit’s components.
●
Ensure that there is adequate and safe access for servicing and maintaining the
Unit.
●
Check that the supporting structure is adequate for the weight of the Unit prior to
installation. See Technical Specifications for Unit weights.
●
The Unit should be mounted in the ducting system.
●
The Unit can either be supported by a suspension bracket or suspended by screw
rods attached to the top of the Unit. Suspension by screw rods will necessitate
drilling holes in the top of the Unit’s housing for this purpose.
●
The Unit can also be placed on the ground, providing a suitable frame is placed in
between the Unit and the floor to allow the system to be drained properly.
We suggest that this frame has a minimum height of 150mm and that you use
suitable rubber or neoprene insulation between the Unit and the frame.
●
The ducting should be fabricated to ensure as straight and even an airflow as
possible, prior to entry into the Unit.
Turbulent air or air directed to one side of the Unit will make the Unit less efficient.
Figure 12 - Preferred Mounting of Filter Unit
Please consult the Wiring Diagram, mounted on the inside of the Door Assembly and
shown on page 33 of this manual, when connecting the Unit to the mains. Beware of
possible differences in the mains power supply.
INFORMATION
The ESP filter must be interfaced with the extraction fan so that they run in
conjunction.