10
Installation & Operation Manual
Copyright © Puretec Pty Ltd 2018
Mixer Tap Maintenance
Replacement of Ceramic Disc Cartridge(s)
1.
Hot/Cold Outlet
• Remove hot and cold water indicator then release screw in lever and lift lever off, now
you can unscrew dome cap and loosen the cartridge lock nut.
• Lift out old cartridge and clean inside making sure no old O-rings are still stuck inside
cartridge housing.
• Insert new cartridge making sure O-rings on bottom of new cartridge have not fallen
off and lugs in bottom of cartridge line up with holes in cartridge housing.
• Now you can tighten lock nut with a torque wrench to 14 newton meters, then reinstall
dome cap, lever screw and hot and cold water indicator.
2.
Filtered/Rain Ancillary Outlet
• Remove front button cover using fine-edged 1.2mm screwdriver.
• Unscrew handle then remove cartridge by unscrewing it anti-clockwise, using 5/8”
socket. Install cartridge by following removal instructions as above, in reverse order.
• Ensure cartridge is firmly tightened, not over tightened.