Fig. 1
INSTALLATION
1. Steam supply piping should be pitched two inches (2”) per foot,
back to the humidifier.
2. Install tube with orifices injecting steam up.
3. All drain piping is done by others.
Form No: IFPC 4/15
Secure to AHU/duct
casing with 3/8-16
UNC bolts
"H"
water
seal
"H"
water
seal
AHU/duct width
AHU/duct height
Typical PURE
Humidifier Co.
humidifier
Flexible steam
supply line
(or hard piped
by others in field)
Open sanitary
drain
Duct plate
"SX"/ "GX" Water Seal Height
The water seal height may have to be increased
"ES"/ "EC" Water Seal Height
if excessive duct static pressure exists.
11" (28 cm)
8" (20 cm)
17" (43 cm)
19" (48 cm)
58.5 thru 102
Total KW
22 thru 33
3 thru 19.5
39 thru 49.5
151 and above
100 to 150 (68.0)
Total lbs./hr (kg/hr)
Up to 60 (27.2)
61 to 99 (44.9)
"H"
19" (48 cm)
11" (28 cm)
17" (43 cm)
8" (20 cm)
"H"
3/4" SW drain piping
(by others)
Open sanitary
drain
Secure to
AHU/duct
casing with
3/8-16
UNC bolts
Flex connectors
(by PURE)
Stainless steel
tube header
(by PURE)
Typ. centers
Injection tube
AHU/duct casing
READ AND SAVE THESE INSTRUCTIONS
CUFFED FAST-PAC
INTERNAL MOUNT
MULTIPLE TUBE ASSEMBLY
INSTALLATION
AND
ASSEMBLY INSTRUCTIONS
TM
PURE HUMIDIFIER
®
is a registered trademark of PURE Humidifier Co.