Pulse Instruments
System 4 Manual
Version 1.6
Visit us Online at
www.pulseinstrument.com
11
HH
H
LL
High alarm
pH
Acid Pump
Normal
Operation
Low alarm
High alarm
1000
ORP
Normal
Operation
Oxid. Pump
Low alarm
HH
L
LL
0 0
14
4. Function
4.1 Operation
The system 4 provides complete automation of the water disinfection process and chemical
treatment with unique capabilities for a “Hands Free” operation, allowing for true automation 24
hours a day. It works with any oxidizer such as Chlorine, Chlorine Dioxide, Bromine, Ozone,
Peroxide, or Peroxyacetic Acid. It also controls the pH with any process compatible acid such as
Citric, Phosphoric, Muratic or Sulfuric Acid.
Fig. 8 pH and ORP Control Concept
pH has three set points: low alarm, acid chemical injection control, and high alarm. ORP also has
three set points: low alarm, oxidizer injection control, and high alarm.
pH
High alarm: turns on above HH
Acid pump: turns on above H
Low alarm: turns on below LL
ORP
High alarm: turns on above HH
Oxidation pump: turns on below L
Low alarm: turns on below LL