RUPS848T
RACK POWER
6
- Mount M6 cage nuts
- Secure the enclosure with 4xM6 screws
3. Connect the
receivers’ cables to the terminals AUX1...AUX8.
4. If needed, the following technical connections can be made:
- ALARM
– technical output of collective failure
5. Connect the battery to the +BAT- terminals:
- battery output (V+): terminal BAT+
- battery output (V-): terminal BAT-
6. Connect the ~230V AC power cord with the IEC C13 plug (included) to the 230V AC power supply and turn on the
power (~230V).
7. Check the PSU operation indicator.
3. Operating status indication.
3.1. LED indication.
The PSU has 13 LED lights at the front panel:
GREEN LED:
on
– the PSU is supplied with 230V AC
off
– no 230V AC supply
GREEN LED:
on
– DC voltage at the output of the switch mode PSU
off
– no DC voltage at the output of the switch mode PSU
RED LED:
on
– failure
off
– no failure
RED LED:
ON
– too high temperature of the switch mode power supply
(>70°C)
OFF
– standard temperature of the switch mode power supply
RED LED
:
on
– battery voltage <46V
off
– battery voltage >46V
GREEN LED
:
on
– DC voltage in the
AUX1…AUX8 output
off
– no DC voltage in the
AUX1…AUX8 output