2. Installation. 
 

2.1 Requirements. 

The buffer PSU shall be mounted by a qualified installer with appropriate permissions and qualifications  

for 230 V AC installations and low-voltage installations (required and necessary for a given country). The unit should be 
mounted  in  confined  spaces  with  normal  relative  humidity  (RH=90%  maximum,  without  condensing)  and  temperature 
from  -

10°C to +40°C.  The PSU shall work in a vertical position that guarantees sufficient convectional air-flow through 

ventilating holes of the enclosure.  

As power supply is designed for a continuous operation and is not equipped with a power-switch, therefore, an 

appropriate overload protection in power supply circuit should be provided. Moreover, the user shall be informed about 
the method of unplugging (most frequently through separating and assigning an appropriate fuse in the fuse-box).  
The electrical system shall follow valid standards and regulations.  

 

2.2 Installation procedure.

  

 

CAUTION

Before  installation,  cut  off  voltage  in  230V  power-supply  circuit.  To  switch  power  off,  use  an 
external switch, in which distance between contacts of all poles in disconnection state is not 
less than 3mm. 
 

         It  is  required  to  install  an  installation  switch  with  a  nominal  current  of  6  A  in  power  supply  circuits 
outside power supply unit. 

 

1.  Mount module of power supply in a selected location and connect wires.  
2.  Connect power cables (~230 V) to L-N clips of PSU 

3.  Connect  ground  wire  to  clip  marked  by  earth  symbol 

.  Use  a  three-core  cable  (with  a  yellow  and  green 

protection wire) to make connection 

). Lead the cables to the appropriate clips through the insulating bushing 

of the PSU. 

 

 
Shock protection circuit shall be done with a particular care: yellow and green wire coat 

of  power  cable  should  be  connected  to  terminal  marked  with  the  grounding  symbol  on  PSU 
enclosure. Operation of PSU without the properly made and fully operational shock protection 
circuit is UNACCEPTABLE! It can cause damage to equipment or an electric shock. 

  

 

1.  Connect equipment to appropriate output terminals of power supply (positive pole marked AUX+, negative pole 

marked AUX-). 

2.  Connect the batteries with the PSU paying special attention to the correct polarity and type of connections  

(Fig. 4): 
 

a) 

 

 

 

b) 

    .  

 

 

Fig. 4 Connecting batteries depending on version of power supply:                                                

   a) PWB-52V1A, b) PWB-52V2A,  

 
CAUTION: PWB-52V1A power supply operates with one 12V battery, while PWB-52V2A requires two 12V 
batteries connected in series! 

 

3.  Switch on 230 V supply. LEDs on the PCB of power supply should light 

 

4.  After installing and checking proper working, enclosure/cabinet etc. can be closed  

 
 
 
 
 
 
 
 
 

Содержание PWB Series

Страница 1: ...USER MANUAL EN Edition 1 from 19 03 2021 Supersedes edition Power supply units PWB series Enclosed buffer switch mode POE power supply units...

Страница 2: ...tallation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication 3 1 Optical indication 4 Maintenance 1 Technical description 1 1 General description Switch mode buffer power supply...

Страница 3: ...of PSU see Fig 2a 2b Element no Description 1 L N power supply connector 230 V AC connector for protective conductor 2 START button running PSU on battery backup 3 Battery fuse 4 Battery terminals BAT...

Страница 4: ...www pulsar pl PWB series 4 Fig 2b View of power supply module PWB 52V2A 1 4 Specification electrical parameters tab 3 operation safety tab 4 operating parameters tab 5...

Страница 5: ...LEDs on PCB of power supply unit LED indicators on power supply s cover optional see section 3 1 Fuses FBAT F5A 250V F5A 250V Enclosure dimensions LxWxH 2mm 200x120x48 204x141x52 Fixing L1xW1xL2xW2 1...

Страница 6: ...allation switch with a nominal current of 6 A in power supply circuits outside power supply unit 1 Mount module of power supply in a selected location and connect wires 2 Connect power cables 230 V to...

Страница 7: ...pply network The PSU does not require performing any specific maintenance measures however in the case of significant dust rate its interior is recommended to be cleaned with compressed air In the cas...

Отзывы: