Pulsar PWB Series Скачать руководство пользователя страница 5

 

Table 3. Parameters of power supplies. 

 
Table 4. Operation safety. 

 
Table 5. Operating parameters. 

Model 

PWB-52V1A 

PWB-52V2A 

Supply voltage 

~ 200 - 240 V 

Current consumption 

0,7 A 

1,2 A 

Power frequency 

50/60 Hz 

Inrush current 

40 A 

50 A 

PSU power 

67 W 

134 W 

Output current max. 

1,15 A 

2,3 A 

Efficiency 

83% 

87% 

Output voltage 

52 V 

– AUX output 

11 - 13,8 V 

– BAT output 

52 V 

– AUX output 

22 - 27,6 V 

– BAT output 

Ripple voltage (max.) 

100 mV p-p 

Current consumption by PSU systems 
during battery-assisted operation. 

approx.40 mA 

approx. 30 mA 

Recommended battery capacity 

– 20 Ah 

– 20 Ah 

(2x)

 

Charging current 

0,5 A 

0,5 A 

Net/gross weight 

0,6/0,65 kg 

0,9/0,95 kg 

Battery circuit protection SCP and 
reverse polarity connection 

-  glass fuse 

Overload protection OLP   

110-150%  PSU power, automatically recovered 

Deep discharge battery protection UVP 

U<9,5 V (± 5%) –  disconnection of 

battery circuit 

U<19 V (± 5%) –  disconnection of 

battery circuit 

Optical indication 

-  LEDs on PCB of power supply unit   

-  LED indicators on power suppl

y’s cover ( optional, see section 3.1) 

Fuses: - F

BAT

 

F5A/250V 

F5A/250V 

Enclosure dimensions                     
(LxWxH

) [±2mm]

 

200x120x48 

204x141x52 

Fixing 
(L

1

xW

1

xL

2

xW

2

155x64x18x41  

186x80x26x48  

Terminals:  
Mains supply: 
Outputs: 
Battery outputs: 

 

0,5 

– 2,5 mm

2

 (AWG 26 

– 12) 

 

Battery wires 6,3F 

– 45cm, angle muffs ML062 

Optional equipment 

set of external LED indicators PKAZ168, mounting plate DIN4 

Notes 

Convectional cooling 

Protection class EN 62368-1 

I (first) 

Protection grade EN 60529 

IP20 

Electrical strength of insulation: 
- between input and output circuits of the PSU   
- between input circuit and protection circuit   
- between output circuit and protection circuit 

 
2500 V AC min. 
1500 V AC min. 
  500 V AC min. 

Insulation resistance: 

 

between input circuit and output or protection circuit 

 
100 MΩ, 500 V DC  

Operating temperature 

-

10ºC...+40ºC  

Storage temperature 

-

20ºC...+60ºC 

Relative humidity 

20%...90%, 

 without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insolation 

unacceptable 

Vibrations and impulse waves during transport 

According to PN-83/T-42106 

Содержание PWB Series

Страница 1: ...USER MANUAL EN Edition 1 from 19 03 2021 Supersedes edition Power supply units PWB series Enclosed buffer switch mode POE power supply units...

Страница 2: ...tallation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication 3 1 Optical indication 4 Maintenance 1 Technical description 1 1 General description Switch mode buffer power supply...

Страница 3: ...of PSU see Fig 2a 2b Element no Description 1 L N power supply connector 230 V AC connector for protective conductor 2 START button running PSU on battery backup 3 Battery fuse 4 Battery terminals BAT...

Страница 4: ...www pulsar pl PWB series 4 Fig 2b View of power supply module PWB 52V2A 1 4 Specification electrical parameters tab 3 operation safety tab 4 operating parameters tab 5...

Страница 5: ...LEDs on PCB of power supply unit LED indicators on power supply s cover optional see section 3 1 Fuses FBAT F5A 250V F5A 250V Enclosure dimensions LxWxH 2mm 200x120x48 204x141x52 Fixing L1xW1xL2xW2 1...

Страница 6: ...allation switch with a nominal current of 6 A in power supply circuits outside power supply unit 1 Mount module of power supply in a selected location and connect wires 2 Connect power cables 230 V to...

Страница 7: ...pply network The PSU does not require performing any specific maintenance measures however in the case of significant dust rate its interior is recommended to be cleaned with compressed air In the cas...

Отзывы: