Table 2. Components of the PSU (See Fig. 3). 

Component no. 

Description 

 

Isolation transformer 

 

Printed Circuit Board (see Table 1, Fig. 2) 

 

TAMPER;  

micro switch of tamper protection

 

(NC)

 

 

F

MAINS

 

fuse in the power supply circuit 230V, T3,15A / 250V 

 

 L-N  

power supply connector, 230V AC, 

 PE protective connector

 

 

Battery connectors: positive: +BAT = red, negative: - BAT = black 

 

 

Fig.3. The view of the PSU. 

 

 

1.4 Technical parameters:  

- Electrical parameters (Table 3)  
- Mechanical parameters (Table 4) 
- Safety of use (Table 5) 
- Operation parameters (Table 6) 

 

Table 3. Electrical parameters

 

PSU type: 

A (EPS - External Power Source) 

Mains supply 

230V AC / 50Hz (-15%/+10%) 

Current consumption 

0,57A @230V AC 

PSU’s power 

76W  

Efficiency 

76% 

Output voltage 

11V÷ 13,8V DC – buffer operation 
10V÷ 13,8V DC – battery operation 

Output current  

5A + 0,5A battery charging 
4,5A + 1A battery charging 
3,5A + 2A battery charging 
2,5A + 3A battery charging 

Output voltage adjustment range 

12÷14,5V DC 

Содержание PSBS5012C

Страница 1: ...PSBS 5012C v 1 1 PSBS 13 8V 5A 17Ah OC Buffer switch mode power supply unit with automatic operation control EN Edition 4 from 05 05 2014 Supercedes edition 3 from 16 09 2013...

Страница 2: ...iption 1 1 General description 1 2 Block diagram 1 3 Description of components and connectors 1 4 Technical parameters 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Power supply operati...

Страница 3: ...SBS 17Ah PSBS 5012C LB8 8x0 5A AWZ578 or AWZ580 MPSBS 17Ah 4 Buffer power supply PSBS 13 8V 12V 5A MPSBS 17Ah PSBS 5012C RN500 13 8V 12V MPSBS 17Ah 5 Buffer power supply PSBS 13 8V 12V 8x0 5A MPSBS 17...

Страница 4: ...the battery circuit F6 3A 250V Terminals AC AC power input EPS technical output of AC power failure indication hi Z state AC power failure 0V state AC power O K PSU technical output of PSU failure in...

Страница 5: ...BAT black Fig 3 The view of the PSU 1 4 Technical parameters Electrical parameters Table 3 Mechanical parameters Table 4 Safety of use Table 5 Operation parameters Table 6 Table 3 Electrical parameter...

Страница 6: ...uts EPS output indicating AC power failure PSU output indicating no DC power PSU failure LoB output indicating low battery voltage OC type 50mA max Normal operation L state 0V failure hi Z state delay...

Страница 7: ...Output current 3 5A 2A battery charging 4 Output current 2 5A 3A battery charging Total current battery is max 5 5A The power supply is designed for a continuous operation and is not equipped with a p...

Страница 8: ...BAT jumper is OFF 8 Mount the battery in the battery compartment of the enclosure Fig 3 Connect the batteries with the PSU paying special attention to the correct polarity 9 Switch on the 230V AC supp...

Страница 9: ...i Z high impedance state PSU failure can be caused by the following events Short circuit at the output Output overload DC DC voltage converter failure Under voltage protection activation LoB output in...

Страница 10: ...e power supply is equipped with the button on the PCB allowing to run the PSU from the battery when needed To do that press and hold the START button on the unit board for 1 second 4 3 Deep discharge...

Страница 11: ...elivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been...

Страница 12: ...ulsar pl PSBS5012C BLUE POWER 12 Pulsar K Bogusz Sp j Siedlec 150 32 744 apczyca Poland Phone 48 14 610 19 40 Fax 48 14 610 19 50 E mail biuro pulsar pl sales pulsar pl http www pulsar pl www zasilacz...

Отзывы: