4. Service and operation. 

 
4.1  Overload or short-circuit of the power supply output (SCP activation). 

            The AUX output of the PSU is protected against short-circuit by

 

PTC polymer fuse. If the power supply load 

current exceeds Imax. (110% ÷ 150% @ 25°C of the PSU power), automatic disconnection of the output voltage, 
indicated  by  switching  off  the  green  LED,  takes  place.  To  restore  the  voltage  at  the  output,  disconnect  the  load 
from the power supply output for approximately 1 minute. 
 

In case of a short-circuit at the AUX, BAT output or reverse battery connection, the F

BAT

 fuse in the battery 

circuit becomes permanently damaged. The voltage restoration at the BAT output requires fuse replacement. 

 

4.2  Running the PSU from the battery. 

 

The power supply is equipped with the button on the PCB allowing to run the PSU from the battery, when 

needed. To do that, press and hold the 

START

 button on the unit board for 1 second. 

 

4.3  Deep discharge battery protection UVP. 

The  power  supply  is  equipped  with  deep  discharge  battery  protection  (UVP).  If  the  voltage  at  the  battery 

terminals drops below 1

0V±0.5V during battery-assisted operation, the batteries will be disconnected. 

The battery 

protection is on when the P

BAT 

jumper is off.

 

 

Caution.  

It is not recommended to disable  UVP since deep  discharge of the batteries reduces their ability to 
store energy, their capacity and lifetime. 

 
 

4.4  Maintenance. 

All  maintenance  procedures  can  be  performed  after  disconnecting  the  power  supply  from  the  power 

network.  The  PSU  does  not  require  any  specific  maintenance;  however,  its  interior  should  be  cleaned  with 
compressed air if used in dusty conditions. In case of fuse replacement, use only compatible replacement parts. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание PSBS5012C

Страница 1: ...PSBS 5012C v 1 1 PSBS 13 8V 5A 17Ah OC Buffer switch mode power supply unit with automatic operation control EN Edition 4 from 05 05 2014 Supercedes edition 3 from 16 09 2013...

Страница 2: ...iption 1 1 General description 1 2 Block diagram 1 3 Description of components and connectors 1 4 Technical parameters 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Power supply operati...

Страница 3: ...SBS 17Ah PSBS 5012C LB8 8x0 5A AWZ578 or AWZ580 MPSBS 17Ah 4 Buffer power supply PSBS 13 8V 12V 5A MPSBS 17Ah PSBS 5012C RN500 13 8V 12V MPSBS 17Ah 5 Buffer power supply PSBS 13 8V 12V 8x0 5A MPSBS 17...

Страница 4: ...the battery circuit F6 3A 250V Terminals AC AC power input EPS technical output of AC power failure indication hi Z state AC power failure 0V state AC power O K PSU technical output of PSU failure in...

Страница 5: ...BAT black Fig 3 The view of the PSU 1 4 Technical parameters Electrical parameters Table 3 Mechanical parameters Table 4 Safety of use Table 5 Operation parameters Table 6 Table 3 Electrical parameter...

Страница 6: ...uts EPS output indicating AC power failure PSU output indicating no DC power PSU failure LoB output indicating low battery voltage OC type 50mA max Normal operation L state 0V failure hi Z state delay...

Страница 7: ...Output current 3 5A 2A battery charging 4 Output current 2 5A 3A battery charging Total current battery is max 5 5A The power supply is designed for a continuous operation and is not equipped with a p...

Страница 8: ...BAT jumper is OFF 8 Mount the battery in the battery compartment of the enclosure Fig 3 Connect the batteries with the PSU paying special attention to the correct polarity 9 Switch on the 230V AC supp...

Страница 9: ...i Z high impedance state PSU failure can be caused by the following events Short circuit at the output Output overload DC DC voltage converter failure Under voltage protection activation LoB output in...

Страница 10: ...e power supply is equipped with the button on the PCB allowing to run the PSU from the battery when needed To do that press and hold the START button on the unit board for 1 second 4 3 Deep discharge...

Страница 11: ...elivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been...

Страница 12: ...ulsar pl PSBS5012C BLUE POWER 12 Pulsar K Bogusz Sp j Siedlec 150 32 744 apczyca Poland Phone 48 14 610 19 40 Fax 48 14 610 19 50 E mail biuro pulsar pl sales pulsar pl http www pulsar pl www zasilacz...

Отзывы: