Pulsar PSBS5012C Скачать руководство пользователя страница 2

www.pulsar.pl                                                       

PSBS5012C                                                                

BLUE POWER

     

 

PSU features: 

 

 

uninterruptible power supply DC 13,8V/5A  

 

battery housing: 17Ah/12V 

 

supply voltage AC 230V  

 

high efficiency 76% 

 

low voltage ripple 

 

battery charging and maintenance control 

 

deep discharge battery protection (UVP)  

 

battery charging current 0,5A/1A/2A/3A, jumper 
selectable  

 

START button to start the battery  

 

battery output protection against short-circuit and 
reverse connection  

 

LED indication  

 

EPS technical output of 230V power failure  
– OC type 

 

PSU technical output indicating PSU failure 

– OC type 

 

LoB technical output indicating low battery voltage 

 

– OC type  

 

Optional installation of the MPSBS relay module  
changing technical outputs of the OC type to relay 
type  

 

adjustable times of 230V AC failure indication 

 

Protection type: 

 

SCP short-circuit protection 

 

Overheat protection OHP 

 

surge protection  

 

Tamper protection: enclosure opening and 

detachment from the wall 

 

overload protection OLP 

 

warranty - 5 years from the production date 

 
TABLE OF CONTENTS: 
1. Technical description. 

1.1 General description 
1.2 Block diagram 
1.3 Description of components and connectors 
1.4 Technical parameters 

2. Installation. 

2.1 Requirements 
2.2 Installation procedure 

3. Power supply operation indication. 

3.1 Optical indication of operation 
3.2 Technical outputs 
3.3 Relay technical outputs 

4. Service and operation 

4.1 Overload or short-circuit the power supply output (SCP activation) 
4.2  Running the PSU from the battery. 
4.3  Deep discharge battery protection UVP. 
4.4  Maintenance 
 

 

1. Technical description. 
 

1.1 General description. 

A  buffer  PSU  is  designed  for  uninterrupted  supply  of  devices  requiring  stabilized  voltage  of 

12V  DC  (+/-

15%).

 The PSU supplies voltage of 

U=13,8V DC 

and total current capacity of

 

1. Output current 5A + 0,5A battery charging 

 

 

 

2. Output current 4,5A + 1A battery charging 

 

 

 

3. Output current 3,5A + 2A battery charging 

 

 

 

4. Output current 2,5A + 3A battery charging 

 

Total c battery is max. 5,5A 

 

In  case  of  mains  power  loss,  the  unit  will  instantly  switch  to  battery  operation.  The  PSU  is  enclosed  in  a 

metal  casing  (color  RAL  9003)  with  battery  housing  for  17Ah/12V  batteries.  The  enclosure  is  fitted  with  a  micro 
switch indicating door opening (front cover) and the detachment from the wall. 

 
 
 
 
 
 
 
 

Содержание PSBS5012C

Страница 1: ...PSBS 5012C v 1 1 PSBS 13 8V 5A 17Ah OC Buffer switch mode power supply unit with automatic operation control EN Edition 4 from 05 05 2014 Supercedes edition 3 from 16 09 2013...

Страница 2: ...iption 1 1 General description 1 2 Block diagram 1 3 Description of components and connectors 1 4 Technical parameters 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Power supply operati...

Страница 3: ...SBS 17Ah PSBS 5012C LB8 8x0 5A AWZ578 or AWZ580 MPSBS 17Ah 4 Buffer power supply PSBS 13 8V 12V 5A MPSBS 17Ah PSBS 5012C RN500 13 8V 12V MPSBS 17Ah 5 Buffer power supply PSBS 13 8V 12V 8x0 5A MPSBS 17...

Страница 4: ...the battery circuit F6 3A 250V Terminals AC AC power input EPS technical output of AC power failure indication hi Z state AC power failure 0V state AC power O K PSU technical output of PSU failure in...

Страница 5: ...BAT black Fig 3 The view of the PSU 1 4 Technical parameters Electrical parameters Table 3 Mechanical parameters Table 4 Safety of use Table 5 Operation parameters Table 6 Table 3 Electrical parameter...

Страница 6: ...uts EPS output indicating AC power failure PSU output indicating no DC power PSU failure LoB output indicating low battery voltage OC type 50mA max Normal operation L state 0V failure hi Z state delay...

Страница 7: ...Output current 3 5A 2A battery charging 4 Output current 2 5A 3A battery charging Total current battery is max 5 5A The power supply is designed for a continuous operation and is not equipped with a p...

Страница 8: ...BAT jumper is OFF 8 Mount the battery in the battery compartment of the enclosure Fig 3 Connect the batteries with the PSU paying special attention to the correct polarity 9 Switch on the 230V AC supp...

Страница 9: ...i Z high impedance state PSU failure can be caused by the following events Short circuit at the output Output overload DC DC voltage converter failure Under voltage protection activation LoB output in...

Страница 10: ...e power supply is equipped with the button on the PCB allowing to run the PSU from the battery when needed To do that press and hold the START button on the unit board for 1 second 4 3 Deep discharge...

Страница 11: ...elivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been...

Страница 12: ...ulsar pl PSBS5012C BLUE POWER 12 Pulsar K Bogusz Sp j Siedlec 150 32 744 apczyca Poland Phone 48 14 610 19 40 Fax 48 14 610 19 50 E mail biuro pulsar pl sales pulsar pl http www pulsar pl www zasilacz...