Pulsar PSBOC1002435 Скачать руководство пользователя страница 5

www.pulsar.pl 

 

 

 

 

PSBOC1002435 

 

 

 

 

 
 

5

Temperature characteristics. 

 

 

 
 
 
 
 

Chart 1.  
Acceptable output current from the PSU 
depending on ambient temperature. 

 

 

Mechanical specifications (tab. 3). 

Enclosure dimensions 

199 x 97 x 42 +23 [mm] (LxWxH)  (+/- 2) 

Net/gross weight 

0,77kg / 0,81kg 

Connectors 

power supply, technical outputs: 

Φ

0,63÷2,5   I/O PCB : 

Φ

0,41÷1,63   

BAT battery outputs: 6,3F-2,5/40cm, 
Led indication output: 3-pin 5 mm connector 

Operation safety (tab.4). 

Protection class PN-EN 60950-1:2007 

I (first) 

Degree of Protection PN-EN 60529: 2002 (U) 

IP20 

Electrical strength of insulation: 
- between PSU input circuit and output circuits (I/P-O/P) 
- between input circuit and PE protection circuit (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
3000 V/AC min. 
1500 V/AC min. 
  500 V/AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 M

, 500V/DC  

Operating specifications (tab.5). 

Operating temperature 

-10ºC...+40ºC  

Storage temperature 

-20ºC...+60ºC 

Relative humidity 

20%...90%, without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insolation 

unacceptable 

Vibrations and impulse waves during transport 

PN-83/T-42106 

 
 

2. Installation. 
 

2.1 Requirements 
The buffer PSU is to be mounted  by a qualified installer, holding relevant permits and licenses (applicable 

and  required  for  a  given  country)  for  230V/AC  interference  and  low-voltage  installations.  The  unit  should  be 
mounted  in  confined  spaces,  in  accordance  with  the  2nd  environmental  class,  with  normal  relative  humidity 
(RH=90% maximum, without condensation) and temperature from -10°C to +40°C. 

 
The  device  shall  be  mounted  in  a  metallic  enclosure  (a cabinet,  an  intended  case).  In  order  to fulfil  LVD 

and  EMC  requirements,  the  rules  for:  power-supply,  encasing  and  screening  shall  be  followed,  according  to 
application. The PSU provides voltage of U=27,6 V DC current efficiency: 

  
                               1. Output current 3A + 0,5A battery charging

*

 

                               2. Output current 2,5A + 1A battery charging

*

 

 

                 Total device c battery: 3,5A max

.

*

 

 
 
2.2. Installation procedure. 

                                                   

*

 

See chart 1

 

Содержание PSBOC1002435

Страница 1: ...PSBOC1002435 v 1 1 PSBOC 27 6V 3 5A OC Enclosed buffer switch mode power supply unit with automatic operation control EN Edition 5 from 10 02 2014 Supercedes edition 4 from 30 10 2013...

Страница 2: ...ription 1 1 General description 1 2 Block diagram 1 3 Description of PSU components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indi...

Страница 3: ...output indicating DC absence PSU failure relay type 6 FLB output indicating battery low voltage relay type 7 FAC AC absence technical output OC type 8 FPS output indicating DC absence PSU failure OC...

Страница 4: ...systems 50 mA Battery charging current 0 5A 1A jumper selectable Short circuit protection SCP electronic automatic recovery Overload protection OLP 105 150 of power supply automatic recovery Battery...

Страница 5: ...orage temperature 20 C 60 C Relative humidity 20 90 without condensation Vibrations during operation unacceptable Impulse waves during operation unacceptable Direct insolation unacceptable Vibrations...

Страница 6: ...le as V 5 Connect the technical outputs to the central or other device 6 Connect the battery in accordance with the signs colours 7 Once the tests and operation control have been completed the enclosu...

Страница 7: ...ttery voltage OC type output Under normal status UBAT 23V the output is connected to ground L level 0V In case of decrease of battery voltage UBAT 23V the output is switched into high impedance state...

Страница 8: ...at within 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs...

Отзывы: