1.2 Block diagram. (fig.1). 

 

Fig.1. Block diagram of the PSU. 

 

 

1.3 Description of PSU components and connectors. 

 

Table 1.  Elements of the PSU (see fig. 2). 

Element no. 

Description 

[1] 

LED indicating presence of AC power  

[2] 

LED indicating presence of DC power 

[3] 

LED indicating correct battery voltage 

[4] 

FAC- AC absence technical output – relay type 

[5] 

FPS- output indicating DC absence/PSU failure – relay type 

[6] 

FLB- output indicating battery low voltage – relay type 

[7] 

FAC- AC absence technical output – OC  type 

[8] 

FPS- output indicating DC absence/PSU failure - OC  type 

[9] 

FLB- output indicating battery low voltage - OC  type 

[10] 

V

ADJ

 - potentiometer, DC voltage adjustment 

[11] 

+V ,-V- DC supply output 

[12] 

L-N  230V/AC power connector, 

 PE protection connector 

[13] 

Battery connectors: +BAT =red, - BAT = black 

[14] 

LED indication on the front panel 

[15] 

Battery charging current selection 

 

  Ibat = 0,5A 

 

  Ibat =1 A 

Legend: 

 dip switch installed 

 dip switch removed    

 

Содержание PSBOC1002435

Страница 1: ...PSBOC1002435 v 1 1 PSBOC 27 6V 3 5A OC Enclosed buffer switch mode power supply unit with automatic operation control EN Edition 5 from 10 02 2014 Supercedes edition 4 from 30 10 2013...

Страница 2: ...ription 1 1 General description 1 2 Block diagram 1 3 Description of PSU components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indi...

Страница 3: ...output indicating DC absence PSU failure relay type 6 FLB output indicating battery low voltage relay type 7 FAC AC absence technical output OC type 8 FPS output indicating DC absence PSU failure OC...

Страница 4: ...systems 50 mA Battery charging current 0 5A 1A jumper selectable Short circuit protection SCP electronic automatic recovery Overload protection OLP 105 150 of power supply automatic recovery Battery...

Страница 5: ...orage temperature 20 C 60 C Relative humidity 20 90 without condensation Vibrations during operation unacceptable Impulse waves during operation unacceptable Direct insolation unacceptable Vibrations...

Страница 6: ...le as V 5 Connect the technical outputs to the central or other device 6 Connect the battery in accordance with the signs colours 7 Once the tests and operation control have been completed the enclosu...

Страница 7: ...ttery voltage OC type output Under normal status UBAT 23V the output is connected to ground L level 0V In case of decrease of battery voltage UBAT 23V the output is switched into high impedance state...

Страница 8: ...at within 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs...

Отзывы: