- EXT IN; input of collective failure.
5. With the
I
BAT
jumper determine the maximum battery charging current, in accordance with the battery
parameters.
6. With the
P
BAT
jumper determine if the discharged battery disconnection system U<10V (+/-5%) shall be on or off.
The battery protection is on when the P
BAT
jumper is off.
7. Switch on the ~230V AC supply (red AC diode and green AUX diode should be on).
8.
Check the output voltage (the PSU voltage without load and without battery should amount to 13.7V ÷ 13.9V,
with
a battery or during battery charging process: 11.0V÷13.8V). If the value of the voltage requires adjustment, it
should be set with use of the V
ADJ
potentiometer, monitoring the voltage at the AUX output of the PSU.
9. Connect the batteries in accordance with the markings: +BAT red to 'plus', -
BAT black to 'minus’. The LB diode
should be on during battery charging process.
10. Press the STOP button to activate or deactivate a dynamic battery test. Deactivating the test turns out the PSU
failure indication at the APS FLT output, but it does not affect the protection system against complete battery
discharge.
11. Check the current consumption of the receivers, taking into account the battery charging current, so as not to
exceed the total current efficiency of the PSU.
12. Once the tests are completed, close the PSU cover.
Table 3. Operation parameters.
Environmental class
II
Operating temperature
-
10ºC...+40ºC
Storing temperature
-
20ºC...+60ºC
Relative humidity
20%...90%, no condensation
Sinusoidal vibrations during operation
EN 50130-5
Surges during operation
EN 50130-5
Direct insolation
unacceptable
Vibrations and surges during transport
PN-83/T-42106
Table 4. Factory settings of the PSU.
Indication time of EPS network loss
5s
section 5.6
Battery charging current
1A
section 7.5
Battery presence
YES (battery present)
section 7.6
Battery test
ON
section 6.2.2
section 7.3
Deep discharge battery protection UVP
ON
section 7.2
Acoustic indication
ON
section 5.5
Communication address
1
section 6.2.5
Transmission
115.2k 8E1
section 6.2.6
Highlighting
Constant
– 50%
section 6.3.4
Blinking light indicating failure
ON
section 6.3.6
Passwords:
-
user’s
-
installer’s
- keyboard lock
1111
1234
NO
section 6.1