2.  Installation. 
 

2.1. Requirements. 

The  buffer  PSU  should  be  mounted  by  a  qualified  installer,  holding  relevant  permits  and  licenses 

(applicable and  required  for  a  given  country)  for  230V/AC  and  low-voltage  installations. The  unit  should  be 
mounted  in  confined  spaces,  in  accordance  with  the  2nd environmental  class,  with  normal  relative  humidity 
(RH=90% maximum, no condensation) and temperature range from -

10°C up to +40°C. The  power  supply  should  

operate  in  a  vertical position in order to provide free and  convectional  air  flow  through ventilating holes of the 
enclosure.  

 

 

      
During normal operation, the total current drawn by the device should not exceed I=5,6A.  

 
 

The    power    supply    is    designed    for    a    continuous    operation    and    is    not    equipped    with    a    power-

switch. Therefore, an appropriate overload protection in the power supply circuit should be provided. Moreover, the 
user should be informed how to disconnect the power supply unit from the mains supply (usually by assigning an 
appropriate  fuse  in  the  fuse  box).      The  electrical  system shall  be  made  in  accordance  with applicable  standards 
and regulations.  

The PSU is designed for 10Mbit/s and 100Mbit/s  Ethernet network (so-called Fast Ethernet)

. However, it 

can  not  be  used  for  a  1000  Mbit/s  network  (so-called  Gigabit  Ethernet).

  Connections  between  the  power 

supply and the camera can be done using UTP-3 cable (networks with data-rates up to 10 Mbit/s) or UTP-5 cable. 
Due to the lower resistance wiring, it is recommended (especially at large distances between the power supply and 
receivers) to use UTP-5 cable also for networks with data-rates up to 10 Mbit/s.  

 

2.2. Installation procedure. 
 

1. Before installation, cut off the voltage in the 230V power-supply circuit. 

2. Mount the PSU in a selected location and lead the connecting cables. 
3.  Connect  the  power  cables  (230V  AC)  to  L-N  terminals  of  the  PSU.  Connect  the  ground  wire  to  the  terminal 

marked  with grounding  symbol:

.  Use  a  three-core  cable  (with a  yellow  and  green  PE  protection  wire)  to make 

the  connection.  The  power  cables  should  be  connected  to  the  appropriate  terminals  on  the  connection  board 
through the bushing.  

 

 

The shock protection circuit shall be done with a particular care: the yellow and green wire 

coat of  the  power  cable  should be connected to  the  terminal  marked  with  the  

  symbol  

in  the  PSU enclosure. Operation of the PSU without the properly made and fully operational 
shock  protection  circuit  is  UNACCEPTABLE!  It  can  cause  damage  to  the  equipment  or  an 
electric shock

 

 
4. Connect the network cables (Ethernet) to the PoE module:supply voltage is present only at the PoE sockets and 
the cameras should be connected to them. Connection diagram is shown in Figure 4:  
 

 

 

Fig. 4. Connection of cameras and network devices to the LAN and PoE terminals. 

 
 

 

Содержание POE1648

Страница 1: ...POE1648 v 1 0 PoE 48V 6A PoE power supply for up to 16 IP cameras EN Edition 1 from 09 02 2016 Supersedes the edition ...

Страница 2: ...ection OLP overload protection warranty 2 year from the production date Example of power supply of up 16 IP cameras range 41V 56V DC 16 x 0 35A TABLE OF CONTENTS 1 Technical description 1 1 General description 1 2 Block diagram 1 3 Description of components and connectors of the PSU 1 4 Technical parameters 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Power supply operation indicat...

Страница 3: ...dicating door opening front cover The PSU can not be used in Gigabit Ethernet networks where all twisted pairs are involved in the transmission of data 1 2 Block diagram Fig 1 Block diagram of the PSU 1 3 The description of components and connectors of the PSU Table 1 Component No Fig 2 Description 1 IN screw connection input power supply of the module factory setting 2 red LED indicates power 48V...

Страница 4: ...e switch mode PSU 2 L N power supply connector 230V AC PE protection connector 3 LED light indicating correct operation of the switch mode PSU 4 VADJ potentiometer regulation of the power supply output voltage 41 56V DC 5 PoE module 6 TAMPER microswitch contacts of antisabotage protection NC Tab 2 Components of the PSU see Fig 3 ...

Страница 5: ... 0mm RAL 9003 Closing Cylindrical screw x 2 at the front lock assembly possible Terminals Switch mode power supply Φ0 63 2 05 AWG 22 12 PoE module Φ0 5 2 05 AWG 24 12 LAN1 LAN4 inputs RJ45 8P8C shielded PoE1 PoE4 outputs RJ45 8P8C shielded TAMPER output wires 35cm Notes The enclosure has a 15mm distance from the mounting surface so the cables can be led PSU cooling fan cooling Safety of use Table ...

Страница 6: ...hernet Connections between the power supply and the camera can be done using UTP 3 cable networks with data rates up to 10 Mbit s or UTP 5 cable Due to the lower resistance wiring it is recommended especially at large distances between the power supply and receivers to use UTP 5 cable also for networks with data rates up to 10 Mbit s 2 2 Installation procedure 1 Before installation cut off the vol...

Страница 7: ... In case of power supply overload the output voltage is automatically disconnected which is indicated by turning off the corresponding LED The voltage is restored automatically restored once the fault overload is cleared 4 2 Activation of the overload protection of the power supply unit When the OVP system is activated the output voltage is automatically cut off Restart is possible after disconnec...

Страница 8: ...technical possibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services are carried out at the service centre of the manufacturer exclusively 8 The warranty does not cover the defects of the equipment resulting from reasons beyond the manufacturer s control mechanical damage improper storage and tran...