background image

 

3.2 Technical output. 

The PSU module is equipped with indication outputs allowing transmitting the information of the absence of AC 

supply. 

 

Cx-NCx-NOx: AC supply absence output

: -relay output indicates the absence of AC supply. 

Under normal status, with  the AC supply on, the C1-NO1 and C2-NO2 contacts  are closed and in the case of AC 
supply loss, the PSU module will switch over C1-NC1 and C2-NC2 contacts. 

 
 
 

4. Handling and operation. 

4.1 Overload or short-circuits to the PSU module output. 

The AUX output of the PSU module is equipped with the PTC polymer fuse assisted protection. If the load 

of the PSU module  exceeds 2,5A (load 110% ÷ 150% @25ºC of the PSU module  power), the output voltage is 
automatically  disconnected  and  this  is  indicated  by  the  green  diode  going  off.  The  voltage  at  the  output  may  be 
restored by disconnecting the output load for the period of about one minute. 
 

In the case of the short-circuit to the AUX, BAT output, (load 200% ÷ 250% of the PSU module  power) or 

incorrect  connection  of  the  battery,  the  fuse  F  in  the  battery  circuit  becomes  permanently  damaged  and  the 
restoration of the voltage at the BAT output requires the replacement of the fuse. 

 

4.2 Battery assisted operation. 

In the case of power failure, in the unit will instantly switch to the battery assisted operation. In order to 

activate  the  operation  of  the  PSU      from  the  battery  itself,  connect  the  BAT  connectors  in  accordance  with  the 
indications:  +BAT  red  to  ‘plus’  and,  -BAT  black  to  'minus’  of  the  battery  and  press  START  button  during  [5s]. 
Turning off the power supply module – pressing STOP button on the module panel  

The PSU is equipped with the discharged battery disconnection system (UVP). 

 

4.3 Maintenance. 

Any and all maintenance operations may be performed following the disconnection of the PSU module from 

the  power  supply  network.  The  PSU  module  does  not  require  performing  any  specific  maintenance  measures, 
however, in the case of significant dust rate, its interior is recommended to be cleaned with compressed air. In the 
case of fuse replacement, only the substitutes in conformity to the original ones are allowed. 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание MSRD-13,8V/2,5A

Страница 1: ...2 0 Buffer switching power supply module with the AC absence indication output UVP battery protection in the casing for the DIN rail EN Edition 2 from the 07th April 2009 Supercedes edition 1 from the 25th September 2008 30092009 ...

Страница 2: ...ge decay prompt switching to battery supply occurs The power supply module has the following protections short circuit SCP overload OLP overheat OHP It is adapted for cooperation with the sealed lead acid battery SLA The power supply module controls automatically the charging and maintenance process of the battery what is more it is equipped with the BAT output protections short circuit and revers...

Страница 3: ... P potentiometer voltage adjustment 5 INPUTS OUTPUTS connector Tab 2 6 START pushbutton power activation with battery 7 STOP pushbutton power deactivation with battery 8 F switch in the battery circuit Version v 2 0 or higher Table 2 2 5 Description of power supply module outputs AC AC supply input 16V 22V AC BAT BAT DC supply output of the battery BAT red BAT black AUX AUX DC supply output AUX U ...

Страница 4: ...ge setting range 11 5 V 14 0 V Voltage adjustment range 1 Ripple voltage 25mV p p max Output current 2 0 A max Current consumption by PSU module systems 25 mA max Battery charging current 500 mA max 7Ah U bat 10 0V or 200 mA max 1 2Ah U bat 10 0V 5 J dip switch function version v 2 0 or higher SCP short circuit protection 200 250 of supply power limitation of current and or fuse failure in the bat...

Страница 5: ...plicable and required for the specific country for connecting interference with the 230V AC and low voltage systems The unit should be mounted in the non open premises in accordance with the II nd environmental class with the normal relative humidity RH 90 maximum without condensing and temperature within the range 10 C to 40 C The PSU module should be operated in the position ensuring that the ai...

Страница 6: ...otentiometer P monitoring the voltage at the AUX output of the PSU module 8 Connect the battery in accordance with the indications BAT red to plus BAT black to minus the LB diode should go on and the lighting intensity should reduce with the charging time elapsed increasing 9 Once the tests and control operation have been completed lock the enclosure cabinet etc Fig 3 Installation procedure on the...

Страница 7: ...f the PSU module power or incorrect connection of the battery the fuse F in the battery circuit becomes permanently damaged and the restoration of the voltage at the BAT output requires the replacement of the fuse 4 2 Battery assisted operation In the case of power failure in the unit will instantly switch to the battery assisted operation In order to activate the operation of the PSU from the bat...

Страница 8: ...le cooperates with the sealed lead acid battery SLA After the operating period ends the power supply shall not be discarded but recycled according to valid regulations WARRANTY 24 months since the sale date 36 months since the production date THE WARRANTY IS VALID ONLY after presenting the invoice of the sale to which the claim refers Pulsar K Bogusz Sp j Siedlec 150 32 744 Łapczyca Poland Tel 48 ...

Отзывы: