background image

 

SCP short-circuit protection in the battery 
circuit and reverse polarity protection 

3,15A- current limitation, fuse F3,15A (failure requires 
replacement of the fuse-element) 

Excessive discharge protection UVP 

U<10,0 V (± 5%) – disconnection of (-BAT) battery 

Technical outputs: 
-Cx, Nx, Nx output indicating the fault to 
the AC supply 
x={1,2} 
 

- R-relay type, 1A@ 30Vdc/50Vac max. 
Time lag about 5s (+/-1%) 
Normal status: activated Cx-NOx,  
Failure status: activated Cx-NCx  

Optical indication: 
 
- AC diode indicating the AC supply status 
- AUX diode indicating DC supply status at 
the power-supply output  
- LB diode indicating the battery charging 
process 
 
- Fbat diode indication the battery fuse  

 
 
- red, normal status, permanently illuminated,  
- green, normal status, permanently illuminated,  
 
- yellow, illuminated with light with intensity depending on 
battery charging current  
- blue, normal status no illumination,  
  fuse failure permanently illuminated 

F fuse 

F 3,15A 

Operation conditions 

II environmental class, -10°C ÷40°C, convectional air flow 
around the power supply for the convectional cooling shall be 
provided 

Table 4. 

Casing dimensions 

70 x 69 x 89 (WxHxD) 

Fixation 

on the DIN rail TH35 

Connectors 

Ф0,41÷1,63 (AWG 26-14) 

BAT battery outputs 

Connectors 6,3F-2,5, 30cm 

Net/gross weight 

0,19kg/0,25kg 

 
2. Installation. 
 

2.1 Requirements. 

The  buffer  PSU  module    is  dedicated  for  installation  by  the  qualified  electrician,  holding  relevant  permits 

and licenses (applicable and required for the specific country) for connecting (interference with) the 230V/AC and 
low-voltage  systems.  The  unit  should  be  mounted  in  the  non-open  premises,  in  accordance  with  the  II-nd 
environmental class, with the normal relative humidity (RH=90% maximum, without condensing) and temperature 
within  the  range  -10°C  to  +40°C.  The  PSU  module  should  be  operated  in  the  position  ensuring  that  the  air  may 
freely flow through  ventilation openings in a convectional way.  

Prior  to  entering  for  the  installation,  the  balance  of    load  should  be  drawn  up.  Pending  the  normal 

operation,  the  sum  of  currents  consumed  by  the  consumers  may  not  exceed

  I=2,5A 

with  the  inclusion  of  the 

battery charging current 

Ibat.  

As the PSU module  is designed for constant operation, it is not equipped with supply isolator, the proper 

overload  protection  in  the  supply  circuit  should  be  ensured.  Also  the  user  should  be  advised  of  the  methods  of 
disconnecting the PSU module  from the supply voltage (most frequently through the separation and indication of 
the  relevant  fuse  in  the  fuse  box).  The  wiring  system  should  be  completed  in  accordance  with  the  applicable 
standards and regulations.  

The unit should be installed in the metallic enclosure (cabinet, equipment) equipped with the DIN TH35 rail 

(width  35  mm)  and,  in  order  to  meet  the  requirements  of  EU,  the  following  rules  should  be  observed:  supply, 
development, shielding - accordingly to the application.  

 

The module requires for proper operation Voltage in range 16-22V AC with galvanic separation (transformer). 
It is needed to compare power of the transformer with the Diagram.1. (S=f(I). 

Содержание MSRD-13,8V/2,5A

Страница 1: ...2 0 Buffer switching power supply module with the AC absence indication output UVP battery protection in the casing for the DIN rail EN Edition 2 from the 07th April 2009 Supercedes edition 1 from the 25th September 2008 30092009 ...

Страница 2: ...ge decay prompt switching to battery supply occurs The power supply module has the following protections short circuit SCP overload OLP overheat OHP It is adapted for cooperation with the sealed lead acid battery SLA The power supply module controls automatically the charging and maintenance process of the battery what is more it is equipped with the BAT output protections short circuit and revers...

Страница 3: ... P potentiometer voltage adjustment 5 INPUTS OUTPUTS connector Tab 2 6 START pushbutton power activation with battery 7 STOP pushbutton power deactivation with battery 8 F switch in the battery circuit Version v 2 0 or higher Table 2 2 5 Description of power supply module outputs AC AC supply input 16V 22V AC BAT BAT DC supply output of the battery BAT red BAT black AUX AUX DC supply output AUX U ...

Страница 4: ...ge setting range 11 5 V 14 0 V Voltage adjustment range 1 Ripple voltage 25mV p p max Output current 2 0 A max Current consumption by PSU module systems 25 mA max Battery charging current 500 mA max 7Ah U bat 10 0V or 200 mA max 1 2Ah U bat 10 0V 5 J dip switch function version v 2 0 or higher SCP short circuit protection 200 250 of supply power limitation of current and or fuse failure in the bat...

Страница 5: ...plicable and required for the specific country for connecting interference with the 230V AC and low voltage systems The unit should be mounted in the non open premises in accordance with the II nd environmental class with the normal relative humidity RH 90 maximum without condensing and temperature within the range 10 C to 40 C The PSU module should be operated in the position ensuring that the ai...

Страница 6: ...otentiometer P monitoring the voltage at the AUX output of the PSU module 8 Connect the battery in accordance with the indications BAT red to plus BAT black to minus the LB diode should go on and the lighting intensity should reduce with the charging time elapsed increasing 9 Once the tests and control operation have been completed lock the enclosure cabinet etc Fig 3 Installation procedure on the...

Страница 7: ...f the PSU module power or incorrect connection of the battery the fuse F in the battery circuit becomes permanently damaged and the restoration of the voltage at the BAT output requires the replacement of the fuse 4 2 Battery assisted operation In the case of power failure in the unit will instantly switch to the battery assisted operation In order to activate the operation of the PSU from the bat...

Страница 8: ...le cooperates with the sealed lead acid battery SLA After the operating period ends the power supply shall not be discarded but recycled according to valid regulations WARRANTY 24 months since the sale date 36 months since the production date THE WARRANTY IS VALID ONLY after presenting the invoice of the sale to which the claim refers Pulsar K Bogusz Sp j Siedlec 150 32 744 Łapczyca Poland Tel 48 ...

Отзывы: