Fig.2. The view of the power-supply module. 

 

1.4. Technical parameters:  
- electrical parameters (tab.3) 
- mechanical parameters (tab.4)

 

Table 3. 

Supply voltage 

16V÷22V/AC (min. 50VA) 

Supply frequency 

50Hz (47÷53HZ) 

PSU module power P 

35W max. 

Current consumption 

3.3 A max.  

Output voltage 

11,0V÷13,8Vdc – buffer operation 
10,0V÷13,8Vdc – battery assisted operation 

Output voltage setting, escalation and keeping 
time 

20ms/40ms/12ms @ Inom., Uac=min. 

Voltage setting range 

11,5 V÷14,0 V  

Voltage adjustment range 

± 1% 

Ripple voltage  

25mV p-p max. 

Output current  

2,0 A max.  

Current consumption by PSU module  systems  

25 mA max. 

Battery charging current 

500 mA max (@7Ah, U bat.=10,0V) or  
* 200 mA max (@1,2Ah, U bat.=10,0V) (± 5%) 

(* J dip switch function, version v.2.0 or higher)

 

SCP short-circuit protection 

200% ÷ 250% of supply power – limitation of current and/or 
fuse failure in the battery circuit (fuse-element replacement 
required) 

OLP overload protection 

110% ÷ 150% (@25ºC÷55ºC) of power supply – current 
limitation with the PTC  automatic fuse, manual restart (the 
fault requires the disconnection of the DC output circuit) 

Содержание MSRD-13,8V/2,5A

Страница 1: ...2 0 Buffer switching power supply module with the AC absence indication output UVP battery protection in the casing for the DIN rail EN Edition 2 from the 07th April 2009 Supercedes edition 1 from the 25th September 2008 30092009 ...

Страница 2: ...ge decay prompt switching to battery supply occurs The power supply module has the following protections short circuit SCP overload OLP overheat OHP It is adapted for cooperation with the sealed lead acid battery SLA The power supply module controls automatically the charging and maintenance process of the battery what is more it is equipped with the BAT output protections short circuit and revers...

Страница 3: ... P potentiometer voltage adjustment 5 INPUTS OUTPUTS connector Tab 2 6 START pushbutton power activation with battery 7 STOP pushbutton power deactivation with battery 8 F switch in the battery circuit Version v 2 0 or higher Table 2 2 5 Description of power supply module outputs AC AC supply input 16V 22V AC BAT BAT DC supply output of the battery BAT red BAT black AUX AUX DC supply output AUX U ...

Страница 4: ...ge setting range 11 5 V 14 0 V Voltage adjustment range 1 Ripple voltage 25mV p p max Output current 2 0 A max Current consumption by PSU module systems 25 mA max Battery charging current 500 mA max 7Ah U bat 10 0V or 200 mA max 1 2Ah U bat 10 0V 5 J dip switch function version v 2 0 or higher SCP short circuit protection 200 250 of supply power limitation of current and or fuse failure in the bat...

Страница 5: ...plicable and required for the specific country for connecting interference with the 230V AC and low voltage systems The unit should be mounted in the non open premises in accordance with the II nd environmental class with the normal relative humidity RH 90 maximum without condensing and temperature within the range 10 C to 40 C The PSU module should be operated in the position ensuring that the ai...

Страница 6: ...otentiometer P monitoring the voltage at the AUX output of the PSU module 8 Connect the battery in accordance with the indications BAT red to plus BAT black to minus the LB diode should go on and the lighting intensity should reduce with the charging time elapsed increasing 9 Once the tests and control operation have been completed lock the enclosure cabinet etc Fig 3 Installation procedure on the...

Страница 7: ...f the PSU module power or incorrect connection of the battery the fuse F in the battery circuit becomes permanently damaged and the restoration of the voltage at the BAT output requires the replacement of the fuse 4 2 Battery assisted operation In the case of power failure in the unit will instantly switch to the battery assisted operation In order to activate the operation of the PSU from the bat...

Страница 8: ...le cooperates with the sealed lead acid battery SLA After the operating period ends the power supply shall not be discarded but recycled according to valid regulations WARRANTY 24 months since the sale date 36 months since the production date THE WARRANTY IS VALID ONLY after presenting the invoice of the sale to which the claim refers Pulsar K Bogusz Sp j Siedlec 150 32 744 Łapczyca Poland Tel 48 ...

Отзывы: