2. Five-position ON/OFF potentiometer
Set the dip switches in the correct position, depending on the features used. Pay attention to activate
the LED switch (walk test) - this will enable the proper configuration of the sensor (e.g. microwave
sensitivity). After configuring of the sensor, the LED can be turned off.
The designation and the switch
number
Function
L – H
Microwave range
DIP1
The microwave detector range
ON – range of 7–15m
OFF – range of 3– 7m
OR
DIP2
Unused switch
AUTO
OR AUTO function
DIP3
ON –OR AUTO ON
OFF –OR AUTO OFF
MEM
Alarm memory
DIP4
ON – Alarm memory ON
OFF – Alarm memory OFF
LED
Walk test
DIP5
ON –LED ON
OFF –LED OFF
L-H (DIP1) – Adjusting the operating range of the MW detector
DIP1 – OFF low microwave range (3-7m)
DIP1– ON high microwave range (7-15m)
„AUTO” (DIP3) –AUTO-OR function:
DIP3 – OFF The alarm is generated by both PIR and WM detectors or after six detections of the
microwave detector within less than 30 seconds.
DIP3 – ON – The alarm is generated by both PIR and WM detectors or after three detections of the
microwave detector within less than 30 seconds.
„MEM” (DIP4) – Alarm memory.
DIP4 – ON This feature enables determining which detector triggered the alarm, which is indicated by
flashing LEDs (green LED – alarm by microwave detector, Orange LED – alarm by PIR detector, Red LED - –
alarm generated by both PIR and WM detectors).
This function is implemented by the „B/S” control input, which should be connected to the control panel,
while one of the control panel outputs should be programmed to supply the B/S terminal with the +13,8VDC
when the system is armed. When the system is disarmed, the B/S terminal shall be shorted to ground or
disconnected. In case of alarm, the LED will be signaling which detector triggered the alarm. The alarm memory is
reset each time the control panel is armed.
DIP4-OFF – turning off the alarm memory.
„LED” (DIP5)- Walk test
DIP5 – ON – Walk test LED ON
DIP5 – OFF – Walk test LED OFF