Pulsar HPSB 10A24C Скачать руководство пользователя страница 5

www.pulsar.pl

                                                               

HPSB10A24C                                                    

GREEN POWER

 

 

 

5

 

W

H

D

0,5A@50V DC (max.) 

LED indication:  
- AC diode indicating AC power status 
- DC diode indicating DC power status at 
the PSU output 

 
- red, normal status 

– on, failure: off 

- green, normal status 

– on, failure: off 

 
      Table 3. Mechanical parameters  

Enclosure dimensions 

400 x 350 x 90+8  [mm] (WxHxD) 

Fixation 

see figure 2 

Fitting battery 

2x17Ah/12V (SLA) max. 
370x170x80mm (WxHxD) max  

Net/gross weight 

4kg/ 4,20 kg 

Enclosure  

Steel plate DC01, thickness: 1,0mm, colour: RAL 9003 

Closing 

Cheese head screw x 2 (at the front), lock assembly possible 

Connectors 

Power supply: 

Φ0,63-2,50 (AWG 22-10) 

Outputs: Φ0,63-2,50 (AWG 22-10),  
Battery output BAT: 

Ф6/1,5mm

2

 

TAMPER output: wires  

Notes 

The enclosure does not touch the assembly surface so that cables can be led. 
Forced cooling - built-in fan. 

       

       Table 4. Operation safety  

Protection class PN-EN 60950-1:2007 

I (first) 

Protection grade PN-EN 60529: 2002 (U) 

IP20 

Electrical strength of insulation: 
- between input and output circuits of the PSU (I/P-O/P) 
- between input circuit and PE protection circuit (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
3000 V/AC min. 
1500 V/AC min. 
  500 V/AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 MΩ, 500V/DC  

 

Table 5. Operating parameters 

Operating temperature 

-

10ºC...+40ºC (see: chart 1) 

Storage temperature 

-

20ºC...+60ºC 

Environmental class 

II 

Relative humidity 

20%...90%, without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insulation 

unacceptable 

Vibrations and impulse waves during transport 

According to PN-83/T-42106 

 

 

Chart 1. Acceptable output current from the PSU depending on ambient temperature. 

 
 
 
 
 

 

Содержание HPSB 10A24C

Страница 1: ...HPSB 10A24C v 1 0 HPSB 27 6V 10A 2x17Ah Buffer switch power supply unit EN Edition 1 from 18 03 2016 Supercedes the edition ...

Страница 2: ... 2 Installation procedure 3 Operating status indication 4 Operation and use 4 1 Overload or short circuit of the PSU output SCP on 4 2 Disconnection of discharged battery 4 3 Maintenance 1 Technical description 1 1 General description A buffer PSU is intended for an uninterrupted supply to devices requiring stabilised voltage of 24V DC 15 The PSU provides voltage of U 27 6V DC Current efficiency 1...

Страница 3: ...ule 2 Connectors PSU L N power supply connector 230V AC Protection connector PE V V DC power output B B battery output 3 green LED indicates AC power 4 P1 potentiometer output voltage adjustment 5 Battery outputs red black 6 TAMPER contact of sabotage protection NC 7 Additional connector for LED indication 8 Selection jumper for charging current Ibat 1A Ibat 2A Ibat 4A Description jumper installed...

Страница 4: ...chart 1 Output current tAMB 40 C 6A 1A battery charge refer to chart 1 5A 2A battery charge refer to chart 1 3A 4A battery charge refer to chart 1 Voltage adjustment range 24 28VDC Ripple 150mV p p max Current consumption by PSU systems 150mA Battery charge current 1A 2A or 4A jumper selectable Short circuit protection SCP electronic automatic return Overload protection OLP 105 150 of the PSU powe...

Страница 5: ...hat cables can be led Forced cooling built in fan Table 4 Operation safety Protection class PN EN 60950 1 2007 I first Protection grade PN EN 60529 2002 U IP20 Electrical strength of insulation between input and output circuits of the PSU I P O P between input circuit and PE protection circuit I P FG between output circuit and PE protection circuit O P FG 3000 V AC min 1500 V AC min 500 V AC min I...

Страница 6: ...The electrical system shall follow valid standards and regulations 2 2 Installation procedure 1 Before installation cut off the voltage in the 230V power supply circuit 2 Mount the PSU in a selected location and connect the wires 3 Connect the power cables 230Vac to L N clips of the PSU Connect the ground wire to the clip marked by the earth symbol PE PSU module connector Use a three core cable wi...

Страница 7: ...ped with the discharged battery disconnection system During the battery assisted operation reducing voltage below 19V at the battery terminals will cause battery disconnection 4 3 Maintenance Any and all maintenance operations may be performed following the disconnection of the PSU from the power supply network The PSU does not require performing any specific maintenance measures however in case o...

Страница 8: ...in 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carried out at the service centre of the manufa...

Отзывы: