Pulsar HPSB 10A24C Скачать руководство пользователя страница 2

www.pulsar.pl

                                                               

HPSB10A24C                                                    

GREEN POWER

 

 

 

2

 

Features: 

 

 

DC 27,6V/10A uninterruptible power supply*  

 

fitting battery: 2x17Ah/12V  

 

wide range 

of mains supply: 176÷264V  

 

built-in power factor correction system (PFC)   

 

high efficiency 85% 

 

battery charging and maintenance control 

 

excessive discharging (UVP) protection 

 

jumper selectable battery charge current  

      1A/2A/4A 

 

 

battery output full protection against short-circuit 
and reverse polarity connection  

 

LED indication  

 

protections: 

 

SCP short-circuit protection 

 

OVP overvoltage protection 

 

overvoltage protection (AC input)  

 

against sabotage 

 

overload protection (OLP) 

 

overheat protection OHP 

 

 forced cooling - built-in fan 

   warranty 

– 2 year from the production date   

 

CONTENTS: 
1. Technical description. 

1.1 General description 
1.2 Block diagram 
1.3 Description of PSU components and connectors. 
1.4 Specifications 

2. Installation. 

2.1 Requirements 
2.2 Installation procedure 

3. Operating status indication. 
4. Operation and use. 

4.1 Overload or short circuit of the PSU output (SCP on) 
4.2 Disconnection of discharged battery 
4.3 Maintenance

 

 

 
1. Technical description. 
 

1.1 General description. 

A buffer PSU is intended for an uninterrupted supply to devices requiring stabilised voltage of 

24V DC (+/-15%).

 

The PSU provides voltage of 

U=27,6V DC.

 Current efficiency: 

 

                                     1. Output current 9A + 1A battery charge

*

 

                                     2. Output current 8A + 2A battery charge

                                     3. Output current 6A + 4A battery charge

*

   

                                                 Total device c battery: 10A max

*

 

In case of power decay 230V, a battery back-up is activated immediately. The PSU is constructed based on the 

switch mode PSU, with high energy efficiency. The PSU is housed in a metal enclosure (colour RAL 9003) which can 
accommodate a 2x17Ah/12V battery. A micro switch indicates door opening (front cover). 

 

The power supply housing has space for additional modules (fuse blocks, voltage regulators and DC/DC 
converters). Optional power supply configurations are available at the website

www.pulsar.pl

 

 

 
 
 
 
 
 
 
 
 
 
 

                                                 

*

 

Refer to chart 1

 

Содержание HPSB 10A24C

Страница 1: ...HPSB 10A24C v 1 0 HPSB 27 6V 10A 2x17Ah Buffer switch power supply unit EN Edition 1 from 18 03 2016 Supercedes the edition ...

Страница 2: ... 2 Installation procedure 3 Operating status indication 4 Operation and use 4 1 Overload or short circuit of the PSU output SCP on 4 2 Disconnection of discharged battery 4 3 Maintenance 1 Technical description 1 1 General description A buffer PSU is intended for an uninterrupted supply to devices requiring stabilised voltage of 24V DC 15 The PSU provides voltage of U 27 6V DC Current efficiency 1...

Страница 3: ...ule 2 Connectors PSU L N power supply connector 230V AC Protection connector PE V V DC power output B B battery output 3 green LED indicates AC power 4 P1 potentiometer output voltage adjustment 5 Battery outputs red black 6 TAMPER contact of sabotage protection NC 7 Additional connector for LED indication 8 Selection jumper for charging current Ibat 1A Ibat 2A Ibat 4A Description jumper installed...

Страница 4: ...chart 1 Output current tAMB 40 C 6A 1A battery charge refer to chart 1 5A 2A battery charge refer to chart 1 3A 4A battery charge refer to chart 1 Voltage adjustment range 24 28VDC Ripple 150mV p p max Current consumption by PSU systems 150mA Battery charge current 1A 2A or 4A jumper selectable Short circuit protection SCP electronic automatic return Overload protection OLP 105 150 of the PSU powe...

Страница 5: ...hat cables can be led Forced cooling built in fan Table 4 Operation safety Protection class PN EN 60950 1 2007 I first Protection grade PN EN 60529 2002 U IP20 Electrical strength of insulation between input and output circuits of the PSU I P O P between input circuit and PE protection circuit I P FG between output circuit and PE protection circuit O P FG 3000 V AC min 1500 V AC min 500 V AC min I...

Страница 6: ...The electrical system shall follow valid standards and regulations 2 2 Installation procedure 1 Before installation cut off the voltage in the 230V power supply circuit 2 Mount the PSU in a selected location and connect the wires 3 Connect the power cables 230Vac to L N clips of the PSU Connect the ground wire to the clip marked by the earth symbol PE PSU module connector Use a three core cable wi...

Страница 7: ...ped with the discharged battery disconnection system During the battery assisted operation reducing voltage below 19V at the battery terminals will cause battery disconnection 4 3 Maintenance Any and all maintenance operations may be performed following the disconnection of the PSU from the power supply network The PSU does not require performing any specific maintenance measures however in case o...

Страница 8: ...in 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carried out at the service centre of the manufa...