4. Connect the receivers’ cables to the +OUT1- i +OUT2 connectors of the terminal block on the PSU board. If the 
output current exceeds I>2,5A, a Wheatstone bridge should be implemented at the +OUT1 i +OUT2 outputs. 
If necessary, connect the device (alarm panel, controller, indicator, etc.) conductors to the technical outputs: 
    - BS output - indicates 230V power failure 
During normal PSU operation, the BS technical output is disconnected from ground (‘-‘) and in the case of 230V AC 
power loss it is connected to ground (‘-‘) after the time determined by Z1, Z2 jumpers (Tab 3). 
    - AW output - indicates failure 
During normal PSU operation, the AW technical output is ground fault (‘-‘). If any of failures mentioned above 
occurs, the output is cut off. 
5. During battery-assisted operation, it is possible to determine time necessary for battery disconnection by the Z3, 
Z4 
pins (Tab.1) when the voltage at its terminals drops below 10.5V. 
6. Determine the maximum charging current using the J1, J2 pins (Tab. 1). 
7. Activate the ~230V/AC supply (the AC diode and the AUX diode should be permanently illuminated) 
Check the output voltage (the PSU voltage without load should amount to 13,6 V÷ 13,9 V, during battery charge: 
11,0 V÷13,8 V). If the value of the voltage requires adjustment, it should be set by the V

ADJ

 potentiometer, 

monitoring the voltage at the AUX output of the PSU. 
8. Connect the battery in accordance with the markings (colours: “+” red, „-„ black) 
9. With the STOP button, initiate or finish a dynamic battery test (Tab.1) 
Deactivating the test turns out the PSU failure indication at the AW output, but it does not affect the protection 
system against complete battery discharge. 
10. Run a PSU test: LED indication, acoustic indication, AW technical output; through: 

cutting off the 230V AC current: LED and acoustic indications – immediately; the BS technical output – 

after some time, determined by Z1, Z2 pins. 

disconnecting the battery: LED indication, acoustic indication and the AW technical output – after a 

battery test have been completed (approx. 20 min.) 
11. With the ZB pin, decide whether the acoustic indication stall be on. (Tab.2) 
12. Check the current consumption of the receivers without exceeding the total current capacity of the PSU. 
13. Erase the failure memo of the PSU. 
14. Once the tests and operation control have been completed, the enclosure can be locked. 
 
 
 
3. Operating status indication. 
     3.1 Control panel operation 
 
         The PSU is equipped with a panel with buttons and a 3-digit LED display. It enables reading the main voltage 
and  current  parameters  of  the  PSU  as  long  as  browsing  failures.  The  panel  buttons  are  to  be  used  for  choosing 
and approving a parameter that is to be displayed. 

 
 
 

 

 

Fig. 4. A control panel. 

 
 
 
 
 
 

Содержание AWZ 502

Страница 1: ...AWZ 502 v 1 2 AWZ 13 8V 5A 17Ah LM Linear Buffer Power Supply Unit EN Edition III 14 th Feb 2012 Supercedes the II 3 rd Nov 2011 edition ...

Страница 2: ...components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication 3 1 Control panel operation 3 2 Acoustic indication 3 3 Technical outputs 4 Operation and use 4 1 Overload or short circuit of the PSU output 4 2 DC output over voltage protection OVP 4 3 Battery assisted operation 4 4 Battery assisted operation standby time 4 5 Dyn...

Страница 3: ... 1 2 Block diagram Fig 1 Block diagram of the PSU 1 3 Description of PSU components and connectors Table 1 Elements of the PSU pcb see Fig 2 Element nr Opis 1 ZB pin acoustic indication ZB acoustic indication on ZB acoustic indication off AKU pins Z3 Z4 adjustment of battery protection function UVP Z3 Z4 protection on battery disconnection time lag 20s Z3 Z4 protection on battery disconnection tim...

Страница 4: ...6 LED indicating over voltage protection UVP on 7 Connector of the temperature detector 8 J1 J2 pins battery charging current selection J1 J2 Ibat 0 6 A J1 J2 Ibat 1 2 A J1 J2 Ibat 1 8 A J1 J2 Ibat 2 4 A Caption jumper on jumper off 9 P1 output voltage adjustment 10 Acoustic indicator Fig 2 The view of the PSU pcb Table 2 Elements of the PSU see Fig 3 Element no Description 1 Isolation transformer...

Страница 5: ...www pulsar pl AWZ502 5 ...

Страница 6: ...P and reverse polarity connection 6 3A current limitation T 6 3A fuse fuse element replacement required Over discharge protection UVP U 10 0 V 5 disconnection BAT of the battery adjustment by the Z3 Z4 jumpers time lag adjustment 20s 15min 1h OFF TAMPER indicates enclosure opening or detaching from the mounting surface 2 micro switches NC contacts enclosure closed 0 5A 50V DC max Technical outputs...

Страница 7: ...flow through ventilating holes of the enclosure 1 Output current 5A 0 6A battery charge 2 Output current 4 4A 1 2A battery charge 3 Output current 3 8A 1 8A battery charge 4 Output current 3 2A 2 4A battery charge Total current of the receivers battery 5 6A max As the PSU is designed for a continuous operation and is not equipped with a power switch therefore an appropriate overload protection sha...

Страница 8: ...res adjustment it should be set by the VADJ potentiometer monitoring the voltage at the AUX output of the PSU 8 Connect the battery in accordance with the markings colours red black 9 With the STOP button initiate or finish a dynamic battery test Tab 1 Deactivating the test turns out the PSU failure indication at the AW output but it does not affect the protection system against complete battery d...

Страница 9: ...atstone bridge s output V Uo2 OUT2 output voltage measurement V Uo1 OUT1 output voltage measurement V Resolution for voltage measurement 0 1V for current measurement 0 1A Displayed voltage and current rate is only approximate For higher accuracy a multimeter shall be used Current failure overview In case of a failure a red LED is illuminated on the panel its code can be checked After pressing the ...

Страница 10: ...ure the enclosure ventilation SEr regulator error over voltage protection was activated a break in the regulator circuit unplug the PSU contact the service center AHE too high supply voltage AC 250V check the voltage of 230V mains supply nAc no voltage or too low network voltage Check the mains fuse of the transformer rSt PSU restart AC supply on launching the PSU with the START button 3 2 Acousti...

Страница 11: ...ion system is indicated by the red LED on the PSU panel After pressing the SEr code will be displayed 4 3 Battery assisted operation Immediate battery reverting in case of main power outage In order to run the PSU from the battery only connect the BAT connectors in accordance with the signs BAT red to plus and BAT black to minus then press the START button on the main board and hold it for 5 secon...

Страница 12: ... 1 and 2 4 The equipment subject to warranty is to be brought to the place where it was purchased or directly to the main office of the manufacturer 5 The warranty applies to complete equipment accompanied by a properly filled warranty claim with a description of the defect 6 Should the claim be accepted the manufacturer is obliged to provide warranty repairs at the earliest convenience however no...

Отзывы: