background image

www.pulsar.pl   

 

 

 

AWZ502 

 

 

 

 

 

 

 
 

11 

 

 

AW – technical output indicating PSU status 

the  OC  type  output  indicates  the  PSU  failure.  In  normal 
state  (during  correct  operation)  the  output  is  in  high 
impendence  state  –  hi-Z.  In  case  of  incorrect  operating 
parameters (voltage, current, temperature), the output is 
ground fault (L state – 0V) 

 

 

    Fig.5. Electrical diagram of the OC outputs. 

 

 

TAMPER  -  output  indicating  tampering  with  the  PSU.  The  output’s  volt-free  (potential-free)  contacts 
indicate PSU door status and mounting to the surface:  

- unit closed and mounted: NC,  
- unit opened or mounted incorrectly/detached from the mounting surface: NO 

 

4. Operation and use. 
 

4.1 Overload or short circuit of the PSU output  
 
The AUX output is equipped with a protection due to a PTC polymer fuse. If the load of the PSU exceeds 

I

max

 (load 110% ÷ 150% 

@25ºC 

of the PSU power) the output voltage is automatically cut off and indicated by the 

green diode going out. To restore the output power and to protect the PTC, cut off the output load for approximately 
1 minute.  

In the case of a short-circuit to the AUX, BAT output (load 200% ÷ 250% of the PSU power) or a reverse 

polarity connection, the F1 fuse in the battery circuit becomes permanently damaged and the restoration of the 
voltage at the BAT output requires replacement of the fuse. 

 

 

 

4.2 DC output over voltage protection (OVP) 
 
In case of voltage exceeding 16.5V±0.2V at the regulator’s output, the system cuts off the power at the 

outputs to protect the battery and the receivers from damage. The outputs will be battery-powered. The protection 

system is indicated by the red LED on the PSU panel. After pressing

, the SEr code will be displayed. 

 

4.3 Battery-assisted operation.  

 

Immediate battery reverting in case of main power outage. 
In order to run the PSU from the battery only, connect the BAT connectors in accordance with the signs:  
+ BAT red to ‘plus’ and, - BAT black to 'minus’ then press the START button on the main board and hold 
it for 5 seconds. 

 

In order to turn off the PSU while battery-assisted operation, press the STOP button on the main board and 

hold for 2 seconds. The OFF sign will appear on the display, the PSU will disconnect the output after 10 seconds.  
 
        The PSU is equipped with a discharged battery disconnection system (UVP), set by AKU: Z3, Z4 
jumpers. The battery protection is active when both jumpers are on.  
 

4.4 Battery-assisted operation – standby time 
To keep the standby time, the current drawn from the PSU during batter-assisted operation should be 

limited. 
Characteristics for 

17Ah/12V SLA 

- for step 1 (8h), current Id= 1,7A 
- for step 2 (15h), current Id=0,9A 
QAKU = 1.25*[(Id + Iz)*Td] – basic formula 
where:  
QAKU - battery capacity [Ah] 
1.25 - factor that allows for capacity loss due to its ageing  
Id -current drawn by the receivers during inspection [A] 
Iz -current drawn for PSU's own requirements  [A]  
Td - required inspection time [h]  

 

4.5 Dynamic battery test 
The PSU runs a battery test every 20 minutes. It is done by a momentary output voltage reduction and 

voltage measurement at the battery terminals. A failure is indicated when voltage drops below 

12V. Not to prolong 

the loading process, the test will not be held if the battery charging current does not drop below 0.6A. The battery test 
facility can be switched off if, for instance, the battery is not connected to the PSU. 

Содержание AWZ 502

Страница 1: ...AWZ 502 v 1 2 AWZ 13 8V 5A 17Ah LM Linear Buffer Power Supply Unit EN Edition III 14 th Feb 2012 Supercedes the II 3 rd Nov 2011 edition ...

Страница 2: ...components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication 3 1 Control panel operation 3 2 Acoustic indication 3 3 Technical outputs 4 Operation and use 4 1 Overload or short circuit of the PSU output 4 2 DC output over voltage protection OVP 4 3 Battery assisted operation 4 4 Battery assisted operation standby time 4 5 Dyn...

Страница 3: ... 1 2 Block diagram Fig 1 Block diagram of the PSU 1 3 Description of PSU components and connectors Table 1 Elements of the PSU pcb see Fig 2 Element nr Opis 1 ZB pin acoustic indication ZB acoustic indication on ZB acoustic indication off AKU pins Z3 Z4 adjustment of battery protection function UVP Z3 Z4 protection on battery disconnection time lag 20s Z3 Z4 protection on battery disconnection tim...

Страница 4: ...6 LED indicating over voltage protection UVP on 7 Connector of the temperature detector 8 J1 J2 pins battery charging current selection J1 J2 Ibat 0 6 A J1 J2 Ibat 1 2 A J1 J2 Ibat 1 8 A J1 J2 Ibat 2 4 A Caption jumper on jumper off 9 P1 output voltage adjustment 10 Acoustic indicator Fig 2 The view of the PSU pcb Table 2 Elements of the PSU see Fig 3 Element no Description 1 Isolation transformer...

Страница 5: ...www pulsar pl AWZ502 5 ...

Страница 6: ...P and reverse polarity connection 6 3A current limitation T 6 3A fuse fuse element replacement required Over discharge protection UVP U 10 0 V 5 disconnection BAT of the battery adjustment by the Z3 Z4 jumpers time lag adjustment 20s 15min 1h OFF TAMPER indicates enclosure opening or detaching from the mounting surface 2 micro switches NC contacts enclosure closed 0 5A 50V DC max Technical outputs...

Страница 7: ...flow through ventilating holes of the enclosure 1 Output current 5A 0 6A battery charge 2 Output current 4 4A 1 2A battery charge 3 Output current 3 8A 1 8A battery charge 4 Output current 3 2A 2 4A battery charge Total current of the receivers battery 5 6A max As the PSU is designed for a continuous operation and is not equipped with a power switch therefore an appropriate overload protection sha...

Страница 8: ...res adjustment it should be set by the VADJ potentiometer monitoring the voltage at the AUX output of the PSU 8 Connect the battery in accordance with the markings colours red black 9 With the STOP button initiate or finish a dynamic battery test Tab 1 Deactivating the test turns out the PSU failure indication at the AW output but it does not affect the protection system against complete battery d...

Страница 9: ...atstone bridge s output V Uo2 OUT2 output voltage measurement V Uo1 OUT1 output voltage measurement V Resolution for voltage measurement 0 1V for current measurement 0 1A Displayed voltage and current rate is only approximate For higher accuracy a multimeter shall be used Current failure overview In case of a failure a red LED is illuminated on the panel its code can be checked After pressing the ...

Страница 10: ...ure the enclosure ventilation SEr regulator error over voltage protection was activated a break in the regulator circuit unplug the PSU contact the service center AHE too high supply voltage AC 250V check the voltage of 230V mains supply nAc no voltage or too low network voltage Check the mains fuse of the transformer rSt PSU restart AC supply on launching the PSU with the START button 3 2 Acousti...

Страница 11: ...ion system is indicated by the red LED on the PSU panel After pressing the SEr code will be displayed 4 3 Battery assisted operation Immediate battery reverting in case of main power outage In order to run the PSU from the battery only connect the BAT connectors in accordance with the signs BAT red to plus and BAT black to minus then press the START button on the main board and hold it for 5 secon...

Страница 12: ... 1 and 2 4 The equipment subject to warranty is to be brought to the place where it was purchased or directly to the main office of the manufacturer 5 The warranty applies to complete equipment accompanied by a properly filled warranty claim with a description of the defect 6 Should the claim be accepted the manufacturer is obliged to provide warranty repairs at the earliest convenience however no...

Отзывы: