background image

PIM90.241

Feb. 2022 / Rev. 2.0 DS-PIM90.241-EN

www.pulspower.com

6 / 17

All parameters are specified at 24V, 3.8A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.

6.

Output

The output provides a SELV/PELV/ES1 rated voltage, which is galvanically isolated from the input voltage. The output is
electronically protected against no-load, overload and short circuit. In case of a protection event, audible noise may occur.

The output is designed to supply any kind of loads, including inductive and capacitive loads. Capacitive loads should not
be larger than 4 000μF with 3.8A or 5 000μF with 1.9A additional resistive load.

At heavy overloads (when output voltage falls below 14V), the device delivers continuous output current for 20ms. After
this,  the  output  is  switched  off  for  approx.  160ms  before  a  new  start  attempt  is  automatically  performed.  This  cycle  is
repeated as long as the overload exists.

If the overload has been cleared, the device will operate normally.

Output voltage

nom.

DC 24V

Adjustment range

24-28V

Guaranteed value

max.

29.5V

This is the maximum output voltage which can occur at
the clockwise end position of the potentiometer due
to tolerances. It is not a guaranteed value which can be
achieved.

Factory settings

typ.

24.1V

±0,2%, at full load, cold unit

Line regulation

max.

10mV

Between 90 and 300Vac

Load regulation

max.

100mV

Between 0 and 3.8A, static value, see Fig. 6-1

Ripple and noise voltage

max.

100mVpp

Bandwidth 20Hz to 20MHz, 50Ohm

Output current

nom.

3.8A

At 24V and an ambient temperature below 60°C

nom.

2.8A

At 24V and 70°C ambient temperature

nom.

3.2A

At 28V and an ambient temperature below 60°C

nom.

2.4A

At 28V and 70°C ambient temperature

Overload protection

Included

Electronically protected against no-load, overload and
short circuit. In case of a protection event, audible noise
may occur.

Overload behaviour

Continuous current

For output voltage above 14Vdc, see Fig. 6-1

Intermittent current

For output voltage below 14Vdc, see Fig. 6-2

max.

6.7A

Continuous current, see Fig. 6-1

Overload/
short-circuit current

typ.

8.6A

Intermitted current peak value for typ. 20ms
Load impedance 150mOhm, see Fig. 6-2
Discharge current of output capacitors is not included.

max.

3.2A

Intermitted current average value (R.M.S.)
Load impedance 150mOhm, see Fig. 6-2

Output capacitance

typ.

1 600

μ

F

Included inside the device

Back-feeding loads

max.

35V

The unit is resistant and does not show malfunctioning
when a load feeds back voltage to the device. It does not
matter whether the device is on or off. The absorbing
energy can be calculated according to the built-in large
sized output capacitor.

Fig. 6-1: Output voltage vs. output current, typ.

Fig. 6-2: Intermittend current at short circuit, typ.

*)

*) with cold devices the times are about 15% longer.

Содержание PIM90.241

Страница 1: ...Class of Protection II unit and fulfills the safety and EMC requirements without an input PE connection This saves wiring costs The PIANO family is a compact industrial grade DIN rail power supply se...

Страница 2: ...ntly changing the information in this data sheet is subject to revision We therefore kindly ask you to always use the latest issue of this document available under www pulspower com No part of this do...

Страница 3: ...ith the input terminals on the bottom of the device Make sure that the wiring is correct by following all local and national codes Use appropriate copper cables that are designed for a minimum operati...

Страница 4: ...g 3 1 Shut down voltage typ 54Vac Steady state value see Fig 3 1 External input protection See recommendations in chapter 2 AC 100V AC 120V AC 230V Input current typ 1 69A 1 45A 0 95A At 24V 3 8A see...

Страница 5: ...mpact on the inrush current value The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch on AC 100V AC 120V AC 230V typ 14A 18A 40A At 40 C ambient...

Страница 6: ...unit Line regulation max 10mV Between 90 and 300Vac Load regulation max 100mV Between 0 and 3 8A static value see Fig 6 1 Ripple and noise voltage max 100mVpp Bandwidth 20Hz to 20MHz 50Ohm Output curr...

Страница 7: ...oltage remains within specification following the loss of input power The hold up time is output load dependent At no load the hold up time can be up to several seconds The green DC OK LED is also on...

Страница 8: ...3W 0 3W 0 4W At no load typ 5W 4 3W 3 8W At 24V 1 9A half load typ 9 5W 7 9W 6W At 24V 3 8A full load The average efficiency is an assumption for a typical application where the device is loaded with...

Страница 9: ...1 9A and 25 C 10 MTBF MTBF stands for Mean Time Between Failure which is calculated according to statistical device failures and indicates reliability of a device It is the statistical representation...

Страница 10: ...11 1 Functional diagram 12 Terminals And Wiring The terminals are IP20 Finger safe constructed and suitable for field and factory wiring All Terminals Type Push in terminals Solid wire max 2 5mm2 Stra...

Страница 11: ...se noted 13 Front Side And User Elements A Input Terminals N Neutral conductor input L Phase Line input B OutputTerminals Dual terminals for the negative and positive pole Both poles are internally co...

Страница 12: ...iterion A Conducted disturbance EN 61000 4 6 0 15 80MHz 10V Criterion A Voltage dips EN 61000 4 11 0 of 100Vac 0Vac 20ms Criterion A C 40 of 100Vac 40Vac 200ms Criterion C 70 of 100Vac 70Vac 500ms Cri...

Страница 13: ...the derated current limits in order not to overload the unit Humidity 5 to 95 r h According to IEC 60068 2 30 No condensation allowed Atmospheric pressure 110 54kPa See Fig 15 2 for details Altitude...

Страница 14: ...ins IT mains typ 130 A 270 A At 230Vac 50Hz TN TT mains IT mains max 80 A 190 A At 110Vac 50Hz TN TT mains IT mains max 120 A 270 A At 132Vac 60Hz TN TT mains IT mains Touch current leakage current ma...

Страница 15: ...witch mode power supply units ISA 71 04 1985 Manufacturer s Declaration Online Document Airborne Contaminants Corrosion Test Severity Level G3 Harsh H2S 100ppb NOx 1250ppb Cl2 20ppb SO2 300ppb Test Du...

Страница 16: ...rail height must be added to the unit depth to calculate the total required installation depth Weight 270g 0 6lb DIN rail Use 35mm DIN rails according to EN 60715 or EN 50022 with a height of 7 5 or 1...

Страница 17: ...ANCY Do not use this device to build redundant systems since there is no monitoring DC OK signal included 21 5 TWO PHASE OPERATION The power supply can also be operated on two phases of a three phase...

Отзывы: