Hold-up Time
The hold-up time is the time during which a power supply’s output voltage remains within specification following the loss
of input power. The hold-up time is output load dependent. At no load, the hold-up time can be up to several seconds. The
status LED is also on during this time.
AC 100 V
AC 120 V
AC 230 V
Hold-up Time
typ.
75 ms
75 ms
75 ms
At 150 W output load, see Fig. 7-1
min.
56 ms
56 ms
56 ms
At 150 W output load, see
Fig. 7-1
typ.
44 ms
44 ms
44 ms
At 300 W output load, see
Fig. 7-1
min.
29 ms
29 ms
29 ms
At 300 W output load, see
Fig. 7-1
Fig. 7-1: Hold-up time vs. input voltage