FPS300.245-049-102
All parameters are specified at 24 V, 12.5 A, 230 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted.
Apr. 2022 / Rev. 0.2 FPS300-EN
18 / 28
EMC
The EMC behavior of the device is designed for applications in industrial environment as well as in residential, commercial
and light industry environments.
The device is investigated according to EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 61000-3-2 and
EN 61000-3-3.
EMC immunity
Electrostatic discharge
EN 61000-4-2
Contact discharge
8kV
Criterion A
Air discharge
Air discharge
15kV
Criterion A
Electromagnetic RF field
EN 61000-4-3
80MHz - 2.7GHz
20V/m
Criterion A
2.7GHz - 6GHz
10V/m
Criterion A
Magnetic field
EN 61000-4-8
50Hz/60Hz
30A/m
Criterion A
Fast transients (Burst)
EN 61000-4-4
AC Input lines
4kV
Criterion A
DC Output lines
4kV
Criterion A
IO-Link
4kV
Criterion A
Surge voltage on AC input
EN 61000-4-5
L to N
2kV
Criterion A
L to PE, N to PE
4kV
Criterion A
Surge voltage on DC output
EN 61000-4-5
+ to -
1kV
Criterion A
+/- to PE
2kV
Criterion A
Surge voltage on OUT-OK
EN 61000-4-5
OUT-OK to PE
1kV
Criterion A
Conducted immunity
EN 61000-4-6
0.15 - 80MHz
20V
Criterion A
Voltage dips
EN 61000-4-11
0% of 100Vac
0Vac, 20ms
Criterion A
40% of 100Vac
40Vac, 200ms
Criterion C
70% of 100Vac
70Vac, 500ms
Criterion C
0% of 200Vac
0Vac, 20ms
Criterion A
40% of 200Vac
80Vac, 200ms
Criterion A
70% of 200Vac
140Vac, 500ms
Criterion A
Voltage interruptions
EN 61000-4-11
0 V
5000 ms
Criterion C
Voltage sags
SEMI F47
Dips on the input voltage according to SEMI F47 standard
80% of 120Vac (96Vac)
1000ms
Criterion A
70% of 120Vac (84Vac)
500ms
Criterion A
50% of 120Vac (60Vac)
200ms
Criterion A
Powerful transients
VDE 0160
Over entire load range
750V, 0.3ms
Criterion A
Performance criterions:
A: The device shows normal operation behavior within the defined limits.
C: Temporary loss of function is possible. The device may shut-down and restarts by itself. No damage or hazards
for the device will occur.