background image

 

 

UC10.241, UC10.242

 

 

UC-Series 

24V,

 

15A,

 

CAPACITOR-BASED

 

DC-UPS 

 

 

17.

 

P

ROTECTION 

F

EATURES

 

 

Output protection 

Electronically protected against overload, no-load and short-circuits 

*)

 

Output over-voltage protection 
in buffer mode 

typ. 32Vdc 
max. 35Vdc 

In case of an internal DC-UPS defect, a redundant 
circuit limits the maximum output voltage. The output 
shuts down and automatically attempts to restart. 

Degree of protection 

IP 20 

EN/IEC 60529 
For use in a controlled environment according to CSA 
22.2 No 107.1-01. 

Penetration protection 

> 3.5mm 

e.g. screws, small parts 

Over-temperature protection included 

Output 

shuts 

down with automatic restart 

Input over-voltage protection 

Max. 35Vdc, no harm or defect of the unit 

Internal input fuse 

included 

Non user replaceable 
The tripping of this fuse is caused by an internal defect. 
In such cases, send unit to the factory for inspection. 

Internal capacitor fuse 

included 

Non user replaceable 
The tripping of this fuse is caused by an internal defect. 
In such cases, send unit to the factory for inspection. 

Overcharging of capacitors 

included 

The capacitors are permanently monitored. In case of a 
too high charging voltage, the charger will be switched 
off with redundant protection measures. 

Balancing of capacitors 

included 

An active balancing circuit ensures uniform capacitor 
voltages. If necessary, the charging current will be 
reduced to a safe value. 

Failing of one or more 
capacitor in the capacitor-string 

included 

Ready contact open, moving light pattern on the three 
LEDs 

Temperature of capacitors 

included 

Indicated by the diagnosis LED, ready contact open 

Internal errors (broken wires, 
…) 

included 

Charging is stopped, ready contact open, moving light 
pattern on the three LEDs 

*)   In case of a protection event, audible noise may occur. 

 

 

18.

 

S

AFETY 

F

EATURES

 

 

Output voltage 

SELV 

IEC/EN 60950-1, 
The input must be powered from a SELV power source. 

 

PELV 

IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41, 
The input must be powered from a PELV power source. 

Class of protection 

III 

PE (Protective Earth) connection not required 

Isolation resistance 

> 5MOhm 
> 800kOhm 
> 5MOhm 

Power port to signal port 
Power port to housing 
Signal port to housing 

Dielectric strength 

500Vac 
500Vac 

Power port to signal port 
Power port / signal port to housing 

Touch current (leakage current) 

The leakage current which is produced by the DC-UPS itself depends on the input 
voltage ripple and need to be investigated in the final application. For a smooth DC 
input voltage, the produced leakage current is less than 100μA. 

May 2016 / Rev. 2.2 DS-UC10.241-EN 
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 

www.pulspower.com   Phone +49 89 9278 0    Germany 

18/27

Содержание DIMENSION UC Series

Страница 1: ...t this energy is released to the DC bus in a regulated process The DC UPSs are maintenance free and have a similar lifetime expectancy as power supplies No regular replacement of the capacitors is nec...

Страница 2: ...he publisher TERMINOLOGY AND ABREVIATIONS Normal mode Describes a condition where the capacitor is charged the input voltage is in range and the output is loaded within the allowed limits Buffer mode...

Страница 3: ...permanently with more than 50 of the rated power Increase this clearance to 15mm in case the adjacent device is a heat source e g a power supply Fig 2 1 Typical wiring diagram buffered branches non b...

Страница 4: ...A buffer current The transfer threshold voltage describes the input voltage where the unit switches into buffer mode and delivers output voltage from the capacitors if the input was above the turn on...

Страница 5: ...15A see Fig 4 2 Short circuit current min 17 9A load impedance 100mOhm see Fig 4 2 max 21 0A load impedance 100mOhm see Fig 4 2 Output capacitance typ 1 500 F included inside the DC UPS Capacitive an...

Страница 6: ...8 12 14 200mv 300mv Voltage drop Fig 4 3 Transition from buffer mode to normal mode and vice versa definitions Fig 4 4 Transfer behavior typ 500ms DIV 0V Output Voltage Input Voltage 24V 22 25V at 10...

Страница 7: ...after discharging with 1A until buffering stops Allowed number of charging discharging cycles no limitation no limitation Initial charging means that no input voltage was applied for several hours or...

Страница 8: ...680s at 0 5A buffer current typ 200s 400s at 1A buffer current typ 68s 136s at 3A buffer current typ 39s 78s at 5A buffer current typ 26s 53s at 7A buffer current typ 16 5s 33s at 10A buffer current...

Страница 9: ...ad min 1mA at 5Vdc min permissible load Isolation voltage 500Vac signal port to power port 8 INHIBIT INPUT The inhibit input disables buffering In normal mode a static signal is required In buffer mod...

Страница 10: ...Power Supply Output DC UPS Output full empty Capacitor Ready Contact closed open Buffering Contact closed open 5s 70s Example A The buffer event is longer than 1s and ends before the buffer capacitors...

Страница 11: ...pacitor fully charged typ 5 0W During charging 0A output current Fig 10 1 Efficiency vs output current in normal mode typ Fig 10 2 Power losses vs output current in normal mode typ Power losses versus...

Страница 12: ...10A 55 C 19 000h 34 000h 19 000h 34 000h at 24V 15A 55 C MTBF UC10 241 UC10 242 MTBF SN 29500 IEC 61709 1 519 000h 1 515 000h at 24V 10A 25 C 1 443 000h 1 439 000h at 24V 15A 25 C 899 000h 895 000h a...

Страница 13: ...9 50 A Remaining capacity A 85 B 75 B 15A Output Current 12 FUNCTIONAL DIAGRAM Fig 12 1 Functional diagram 24V Power Supply Boost Converter Step up Converter Charger Balancing Safety Circuits Input E...

Страница 14: ...onnecting a wire Instructions a Use appropriate copper cables that are designed for minimum operating temperatures of 60 C for ambient up to 45 C and 75 C for ambient up to 60 C and 90 C for ambient u...

Страница 15: ...Flashing pattern for the red warning LED Check input voltage 1 0 1 0 PC Mode activated AUU Input Terminals quick connect spring clamp terminal UUBUU Output Terminals quick connect spring clamp termina...

Страница 16: ...coupling clamp Criterions A DC UPS shows normal operation behavior within the defined limits EMC Emission According generic standards EN 61000 6 3 and EN 61000 6 4 Conducted emission IEC CISPR 16 1 2...

Страница 17: ...2103 EN 50178 not conductive LABS compatibility The unit does not release any silicone or other LABS critical substances and is suitable for use in paint shops Operational temperature is the same as t...

Страница 18: ...ve balancing circuit ensures uniform capacitor voltages If necessary the charging current will be reduced to a safe value Failing of one or more capacitor in the capacitor string included Ready contac...

Страница 19: ...TEX certificate EPS 15 ATEX 1 025 X The power supply must be built in in an IP54 enclosure EN 60079 0 EN 60079 15 ATEX II 3G Ex nA nC II T4 Gc Suitable for use in Class 1 Zone 2 Groups IIa IIb and IIc...

Страница 20: ...The DIN rail height must be added to the unit depth 127mm to calculate the total required installation depth Installation Clearances See chapter XX2XX Fig 21 1 Front view UC10 241 Fig 21 2 Front view...

Страница 21: ...s bracket is used to mount the DC UPS onto a flat surface without utilizing a DIN Rail UC10 241 UC10 242 May 2016 Rev 2 2 DS UC10 241 EN All parameters are specified at 24V 10A output current 25 C amb...

Страница 22: ...the wire size that is used the wiring is considered as thermally safe regardless of whether the MCB opens or not To avoid voltage dips and under voltage situations in adjacent 24V branches which are s...

Страница 23: ...2 Wiring example for a fully redundant system redundant power supplies and redundant DC UPSs Power Supply 24V Output Power Supply 24V Output Load Failure Monitor YRM2 DIODE OUT IN 1 IN 2 IN 1 IN 2 23...

Страница 24: ...tic signal is required In buffer mode a pulse with a minimum length of 250ms is required to stop buffering The inhibit signal is stored and can be reset by cycling the input voltage For service purpos...

Страница 25: ...ontact closed External signal to start the delayed shut down Load open closed Buffering Contact open 1s full empty Capacitor Pin 7 8 open Ready Threshold 250ms Activation of the external control mode...

Страница 26: ...depends on the load current the lower the load current the lower the cut off voltage Considering this voltage range the energy can be calculated with the following formula full charge voltage U1 2 5V...

Страница 27: ...ee notes in section 2 first Symptom Action Check input voltage LED is on Check input voltage must be between 22 8V and 30V DC UPS did not buffer Inhibit input was set Capacitor did not have enough tim...

Отзывы: