background image

 

 

UC10.241, UC10.242

 

 

UC-Series 

24V,

 

15A,

 

CAPACITOR-BASED

 

DC-UPS 

 

 

14.

 

F

RONT 

S

IDE AND 

U

SER 

E

LEMENTS

 

 

 

Fig. 14-1

   Front side 

(UC10.241)

 

 

E Diagnosis 

LED 

(yellow)

  

Helps troubleshooting and indicates the following:
- Current Overload: output voltage below 20Vdc 
   due to a too high output current,  
   ready contact is open 
- High Temperature: signal for too high capacitor 
   temperature (>65˚C), charging and buffering is 
   still possible, ready contact is open 
- Buffer Time Expired: 
   buffering stopped due to discharged capacitors 
- Inhibit Active: buffering is blocked by the inhibit 
   signal 

 

Flashing pattern for the yellow diagnosis LED: 

 

1
0

Current

Overload

1
0

High

Temperature

1
0

Buffer time

expired

1
0

Inhibit

active

 

 

F “Warning” 

LED 

(red)

  

- Check Input Voltage:

 

   Indicates a too low or too high input voltage. 
   The input voltage must be between 23Vdc and  
   30Vdc to turn-on the output and to start 
   charging of the capacitors. 
- PC-Mode Activated 
   Indicates, that the PC-Mode (see also section 9) is
   activated. 

 

Flashing pattern for the red warning LED: 

 

Check input

voltage

1
0
1
0

PC-Mode

activated

 

 

 

 

A

UU

 Input 

Terminals

 (quick-connect spring-clamp terminal) 

 

UU

B

UU

 Output Terminals

 (quick-connect spring-clamp terminal)

The minus-pole has the same reference as the minus-pole 
of the input terminals 

 

C

UU

 Signal 

Connector 

(plug connector)  

- Ready: contact is closed when status LED indicates ready 
- Buffering: contact is closed during buffering 
- Inhibit:  a voltage applied on this input signal disables 
                 buffering (e.g. during service) 
- PC-Mode: To activate the PC-mode connect the two pins of  
                    the signal connector together; see also section 9

 

D Status 

LED 

(green)

  

- Ready: capacitors are fully charged, no failures detected 
- Charging: capacitors are being charged  
- Buffering: capacitors are being discharged 

 

Flashing pattern for the green status LED: 

G Chassis 

Ground 

 (screw) 

Use a M4 ring-type terminal to connect the 
housing to ground, when required 

1
0

Ready

1
0

Charging

1
0

Buffering

 

 

May 2016 / Rev. 2.2 DS-UC10.241-EN 
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 

www.pulspower.com   Phone +49 89 9278 0    Germany 

15/27

Содержание DIMENSION UC Series

Страница 1: ...t this energy is released to the DC bus in a regulated process The DC UPSs are maintenance free and have a similar lifetime expectancy as power supplies No regular replacement of the capacitors is nec...

Страница 2: ...he publisher TERMINOLOGY AND ABREVIATIONS Normal mode Describes a condition where the capacitor is charged the input voltage is in range and the output is loaded within the allowed limits Buffer mode...

Страница 3: ...permanently with more than 50 of the rated power Increase this clearance to 15mm in case the adjacent device is a heat source e g a power supply Fig 2 1 Typical wiring diagram buffered branches non b...

Страница 4: ...A buffer current The transfer threshold voltage describes the input voltage where the unit switches into buffer mode and delivers output voltage from the capacitors if the input was above the turn on...

Страница 5: ...15A see Fig 4 2 Short circuit current min 17 9A load impedance 100mOhm see Fig 4 2 max 21 0A load impedance 100mOhm see Fig 4 2 Output capacitance typ 1 500 F included inside the DC UPS Capacitive an...

Страница 6: ...8 12 14 200mv 300mv Voltage drop Fig 4 3 Transition from buffer mode to normal mode and vice versa definitions Fig 4 4 Transfer behavior typ 500ms DIV 0V Output Voltage Input Voltage 24V 22 25V at 10...

Страница 7: ...after discharging with 1A until buffering stops Allowed number of charging discharging cycles no limitation no limitation Initial charging means that no input voltage was applied for several hours or...

Страница 8: ...680s at 0 5A buffer current typ 200s 400s at 1A buffer current typ 68s 136s at 3A buffer current typ 39s 78s at 5A buffer current typ 26s 53s at 7A buffer current typ 16 5s 33s at 10A buffer current...

Страница 9: ...ad min 1mA at 5Vdc min permissible load Isolation voltage 500Vac signal port to power port 8 INHIBIT INPUT The inhibit input disables buffering In normal mode a static signal is required In buffer mod...

Страница 10: ...Power Supply Output DC UPS Output full empty Capacitor Ready Contact closed open Buffering Contact closed open 5s 70s Example A The buffer event is longer than 1s and ends before the buffer capacitors...

Страница 11: ...pacitor fully charged typ 5 0W During charging 0A output current Fig 10 1 Efficiency vs output current in normal mode typ Fig 10 2 Power losses vs output current in normal mode typ Power losses versus...

Страница 12: ...10A 55 C 19 000h 34 000h 19 000h 34 000h at 24V 15A 55 C MTBF UC10 241 UC10 242 MTBF SN 29500 IEC 61709 1 519 000h 1 515 000h at 24V 10A 25 C 1 443 000h 1 439 000h at 24V 15A 25 C 899 000h 895 000h a...

Страница 13: ...9 50 A Remaining capacity A 85 B 75 B 15A Output Current 12 FUNCTIONAL DIAGRAM Fig 12 1 Functional diagram 24V Power Supply Boost Converter Step up Converter Charger Balancing Safety Circuits Input E...

Страница 14: ...onnecting a wire Instructions a Use appropriate copper cables that are designed for minimum operating temperatures of 60 C for ambient up to 45 C and 75 C for ambient up to 60 C and 90 C for ambient u...

Страница 15: ...Flashing pattern for the red warning LED Check input voltage 1 0 1 0 PC Mode activated AUU Input Terminals quick connect spring clamp terminal UUBUU Output Terminals quick connect spring clamp termina...

Страница 16: ...coupling clamp Criterions A DC UPS shows normal operation behavior within the defined limits EMC Emission According generic standards EN 61000 6 3 and EN 61000 6 4 Conducted emission IEC CISPR 16 1 2...

Страница 17: ...2103 EN 50178 not conductive LABS compatibility The unit does not release any silicone or other LABS critical substances and is suitable for use in paint shops Operational temperature is the same as t...

Страница 18: ...ve balancing circuit ensures uniform capacitor voltages If necessary the charging current will be reduced to a safe value Failing of one or more capacitor in the capacitor string included Ready contac...

Страница 19: ...TEX certificate EPS 15 ATEX 1 025 X The power supply must be built in in an IP54 enclosure EN 60079 0 EN 60079 15 ATEX II 3G Ex nA nC II T4 Gc Suitable for use in Class 1 Zone 2 Groups IIa IIb and IIc...

Страница 20: ...The DIN rail height must be added to the unit depth 127mm to calculate the total required installation depth Installation Clearances See chapter XX2XX Fig 21 1 Front view UC10 241 Fig 21 2 Front view...

Страница 21: ...s bracket is used to mount the DC UPS onto a flat surface without utilizing a DIN Rail UC10 241 UC10 242 May 2016 Rev 2 2 DS UC10 241 EN All parameters are specified at 24V 10A output current 25 C amb...

Страница 22: ...the wire size that is used the wiring is considered as thermally safe regardless of whether the MCB opens or not To avoid voltage dips and under voltage situations in adjacent 24V branches which are s...

Страница 23: ...2 Wiring example for a fully redundant system redundant power supplies and redundant DC UPSs Power Supply 24V Output Power Supply 24V Output Load Failure Monitor YRM2 DIODE OUT IN 1 IN 2 IN 1 IN 2 23...

Страница 24: ...tic signal is required In buffer mode a pulse with a minimum length of 250ms is required to stop buffering The inhibit signal is stored and can be reset by cycling the input voltage For service purpos...

Страница 25: ...ontact closed External signal to start the delayed shut down Load open closed Buffering Contact open 1s full empty Capacitor Pin 7 8 open Ready Threshold 250ms Activation of the external control mode...

Страница 26: ...depends on the load current the lower the load current the lower the cut off voltage Considering this voltage range the energy can be calculated with the following formula full charge voltage U1 2 5V...

Страница 27: ...ee notes in section 2 first Symptom Action Check input voltage LED is on Check input voltage must be between 22 8V and 30V DC UPS did not buffer Inhibit input was set Capacitor did not have enough tim...

Отзывы: