UC10.241, UC10.242
UC-Series
24V,
15A,
CAPACITOR-BASED
DC-UPS
16.
E
NVIRONMENT
Operational temperature
*)
-40°C to +60°C (-40°F to 140°F)
Storage temperature
-40 to +70°C (-40°F to 158°F)
for storage and transportation
Humidity
**)
5 to 95% r.H.
IEC 60068-2-30
Vibration sinusoidal
2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
***)
2 hours / axis
IEC 60068-2-6
Shock
30g 6ms, 20g 11ms
***)
3 bumps / direction, 18 bumps in total
IEC 60068-2-27
Altitude
0 to 6000m (0 to 20 000ft)
Approvals apply only up to 2000m
Over-voltage category
II
IEC 62103, EN 50178, EN 60950, UL 840
Degree of pollution
2
IEC 62103, EN 50178, not conductive
LABS compatibility
The unit does not release any silicone or other LABS-critical substances and is suitable for
use in paint shops.
*) Operational temperature is the same as the ambient or surrounding temperature and is defined as the air temperature 2cm below the
unit.
**) Do not energize while condensation is present
***) Higher levels allowed when using the wall mounting bracket ZM2.WALL
Fig. 16-1
Output current vs. ambient temp.
0
-40
0
+40
+60°C
2.5
5.0
7.5
10.0
12.5
15A
Ambient Temperature
Allowable Output Current
May 2016 / Rev. 2.2 DS-UC10.241-EN
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany