background image

 

 

UZK12.261, UZO12.26 

 

 

 

 

U-Series 

B

ATTERY 

M

ODULE 

12V,

 

26AH 

 

 

Mar. 2019 / Rev. 2.2a DS-UZK12.261 

All parameters are typical values specified at, 25°C ambient temperature unless otherwise noted. 

www.pulspower.com   Phone +49 89 9278 0    Germany 

1/10 

 

 

 

B

ATTERY 

M

ODULE

 

 

 

Long Life Battery: 10 to 12 Years According to 
EUROBAT 

 

Small Mounting Footprint 

 

Easy Access to the Terminals and the Fuse 

 

Heavy Duty Fuse Holder and Spare Fuse Included 

 

3 Year Warranty, Except for Batteries, Which Are 
Considered a Service Part. 
 
 

 

 
 
 

1.

 

G

ENERAL 

D

ESCRIPTION

 

 
The UZK12.261 battery module utilizes one non-
spillable maintenance-free VRLA lead-acid battery, 
which is assembled in a package with all wiring and 
fusing included. 
The battery module is available in two different 

options. It can be ordered as UZK-module with a battery 
or as UZO-module without a battery which can be 
installed at a later date to avoid outdated batteries. 
 

 

2.

 

S

HORT

-

FORM 

D

ATA

 

 

Nominal voltage 

DC 12V 

 

Nominal battery 
capacity 

26Ah 

 

Nominal battery life 

10 to 12 years 

According EUROBAT 

Battery current 

Max. 30A 

Discharging current 

 

Max. 5.5A 

Charging current 

Recommended 

charging voltage 

13.9V 

13.75V 

13.6V 
13.45V 

At 10°C 

At 20°C 

At 30°C 
At 40°C 

Self-discharge rate 

3%/month  

At 20°C 

Battery fuse 

30A 

ATOF

®

 287 030 from 

Littelfuse. 

Temperature range 

-10°C to +50°C 

For charging 

 

-15°C to +60°C 

For discharging 

Size (WxHxD) 

214x179x153mm   

Weight 

10.1kg / 22.3lb 

700g / 1.54lb 

For UZK12.261 

For UZO12.26 

 
 
 

3.

 

O

RDER 

N

UMBERS

 

Battery Module 

UZK12.261

 

Battery module with 

 

assembled batteries 

UZO12.26

 

Battery module without 

 

assembled batteries 

 

UZB12.261 

Battery replacement

 

12V, 26Ah 

 

4.

 

M

ARKINGS

 

 

IND. CONT. EQ. 

 

UL 508, planned

 

 

Marine

 

 

 

 

Class I Div 2

 

IECEx

ATEX

 

Содержание DIMENSION U Series

Страница 1: ...ptions It can be ordered as UZK module with a battery or as UZO module without a battery which can be installed at a later date to avoid outdated batteries 2 SHORT FORM DATA Nominal voltage DC 12V Nom...

Страница 2: ...en in this document is correct to the best of our knowledge and experience at the time of publication If not expressly agreed otherwise this information does not represent a warranty in the legal sens...

Страница 3: ...d lifetime may change Every 9 months or whenever the open circuit voltage OCV falls below 12 6V the battery module should be charged Apply a charging voltage of 13 8V at 25 C for 72 hours Batteries wi...

Страница 4: ...ame as the ambient or surrounding air temperature and is defined as the air temperature 2cm below the device Fig 8 1 Wiring scheme Battery Output Input Fuse BATTERY 12V Load Power Supply DC UPS UZK12...

Страница 5: ...ure in which the battery is used and on the number and depth of discharge cycles Disconnect battery fuse before replacing the battery Regarding disposal of used batteries see chapter 6 Fig 10 1 Replac...

Страница 6: ...orientation according to IEC EN 61056 1 Altitude 0 to 6000m 0 to 20 000ft Degree of pollution 2 According to IEC 62477 1 not conductive LABS compatibility The unit does not release any silicone or oth...

Страница 7: ...D systems U S A ANSI ISA 12 12 01 2015 and Canada C22 2 No 213 M1987 EN 60079 0 EN 60079 7 ATEX II 3G Ex ec IIC T4 Gc Approval for use in hazardous locations Zone 2 Category 3G Number of ATEX certifi...

Страница 8: ...spower com Phone 49 89 9278 0 Germany 8 10 16 PHYSICAL DIMENSIONS AND WEIGHT Width 214mm 8 43 Height 179mm 7 05 Depth 153mm 6 22 Weight 10 1kg 22 3lb For UZK12 261 700g 1 54lb For UZO12 26 Bracket mat...

Страница 9: ...arge cycles and depth of discharge Do not discharge batteries more than necessary Set buffer time limiter to the required buffer time The number as well as the depth of discharging cycles is limited A...

Страница 10: ...pulspower com Phone 49 89 9278 0 Germany 10 10 18 MOUNTING ORIENTATIONS The standard mounting orientation is the vertical installation onto a flat surface Fig 18 1 Standard mounting orientation The fo...

Отзывы: