background image

Load Shedding Control

Model LSC-08

Screen 1

Screen 2

Screen 3

Screen 4

Screen 10

Screen 6

Screens 1 to 5 and 7 to 8 are used to adjust the Amperage and time delays in the load shedding program. Note that
screen 4 “

Gen Actual Cur”

is not adjustable and is reading the amperage interpreted by the CT input. Also note that

screen 6 & 10  displays the real time state of the output relays on the controller. Screen 7 indicated the NO or NC
Mode of operation.

The LSC-08 is a standalone load shedding controller designed to work with any single or three phase generator and a
broad range of connected load types controlled by DRY CONTACTS. The controller can be set for 2 different
configurations as follows.

Normally open Mode

 is selected when

I2 = 24Vdc

 this mode is designed to work with

loads that use a normally open state for control purposes like normally closed relays. The

Normally Closed Mode

 is

selected when

 I2 = 0V

 This mode is designed to work with normally closed control circuits like low voltage HVAC

control wires and normally open contactors.

Operation:

The internal program starts to run on power up. At startup all relays will revert to their active state,

NO

Configuration

 will close and

 NC Configuration

 will open. All relays will remain in their active state for the

duration of the

Delay Shed

  period set by

DR01

. After

DR01

 times out the program will look at the value of

Gen

Full Load DR02

to determine the maximum amps available. A comparator circuit will look at the assigned amperage

rating of

DR03 Relay1

 and the

Gen Actual Cur reading

, (this will always be determined by the higher of the 3 CT

inputs). When capacity is available

Relay1

 will revert to the NORMAL STATE and turn the load on. After the load

is restored the program will pause for the number of seconds set by input setting

DR0A Stabilize Time.

After the

delay period the program will compare the

Gen Actual Cur reading,

with

Gen Full Load DR02

and the amps

assigned to

RELAY2 DR04,

 if the comparator program determined capacity is available

RELAY2

 will revert to its

normal state turning on load 2. This sequence is repeated for

RELAY 8 ~RELAY 8 .

Any time the

 Gen Actual Cur

reading

exceeds 90% of

Gen Full Load DR02

All relays will revert to their active state removing all eight of the

loads from the circuit. The program will then repeat the process restoring one load at a time until additional capacity
is no longer available.

Programming Screens

Theory Of Operation

Screen 7

Screens 8 & 9

Screens 5

Отзывы: