Remote controls
Part 4: Installation and Start-up
54
Flow sensor VF (VFAS)
v
Installation location:
•
In the case of boiler control, in place of the boiler
sensor KF as close as possible behind the boiler on
the heating flow pipe
•
In the case of mixer operation
v
approx. 0.5 m behind
the circulation pump
Installation:
•
Thoroughly clean the flow pipe.
•
Apply heat conductive paste (A)!!
•
Secure sensor with stretch band.
Storage tank sensor SPF (SPFS)
F
Installation location:
•
In the immersed pipe of the hot-water cylinder tank
(generally on the front face of the tank)
Installation:
•
Slide the sensor as far as possible into the immersed
pipe.
!
The immersed sleeve must be dry.