PD6870 Explosion-Proof Loop-Powered Process Meter 

Instruction Manual 

 

6

 

 Product Ratings and Approvals 

FM 

Explosion-proof for use in: 

Class I, Division 1, Groups B, C and D 

Dust-ignition proof for use in: 

Class II/III, Division 1, Groups E, F and G; T6 

Flame-proof for use in: 

Class I, Zone 1, AEx d Group IIC; T6 

Protection by Enclosure: 

Zone 21, AEx tb IIIC; T85°C 

Ta = -40 to 75°C.  

Enclosure: Type 4X, IP66.  

Certificate number: 3040391 

CSA  

Explosion-proof for use in: 

Class I, Division 1, Groups B, C and D 

Dust-ignition proof for use in: 

Class II/III, Division 1, Groups E, F and G; T6 

Flame-proof for use in: 

Zone 1, Ex d IIC T6  

Ta = -40 to 75°C.  

Enclosure: Type 4X & IP66/IP68.  

Certificate number: 2325749 

ATEX  

II 2 G D. Flame-proof for use in: 

Zone 1, Ex d IIC T6 Gb 

Protection by Enclosure for use in: 

Dust Atmospheres (Zone 21) 

Ex tb IIIC T85°C Db IP68.  

Ta = -40°C to +75°C 

Certificate number: Sira 10ATEX1116X 

IECEx 

Flame-proof for use in: 

Zone 1, Ex d IIC T6 Gb 

Protection by Enclosure for use in: 

Dust Atmospheres (Zone 21) 

Ex tb IIIC T85°C Db IP68. 

Ta = -40°C to +75°C 

Certificate number: IECEx SIR 10.0056X 

 

Special Conditions for Safe Use: 

Use suitably certified and dimensioned cable entry 

device and/or plug. The equipment shall be installed 

such that the supply cable is protected from mechani-

cal damage. The cable shall not be subjected to ten-

sion or torque. If the cable is to be terminated within 

an explosive atmosphere, then appropriate protection 

of the free end of the cable shall be provided. 

Year of Construction: 

This information is contained within the serial number 

with the first four digits representing the year and 

month in the YYMM format. 

For European Community:

 The PD6870 must be  

installed in accordance with the ATEX directive 

2014/34/EU, and the product certificate Sira 

10ATEX1116X. 

 Electromagnetic Compatibility 

Emissions

 

EN 61326-1 

Safety requirements for measurement, 

control, and laboratory use – Industrial 

Group 1 Class A ISM emissions  

requirements

 

Radiated  

Emissions 

Class A 

Immunity 

EN 61326-1 

Safety requirements for measurement, 

control, and laboratory use 

ESD

  

±4 kV contact, 

±8 kV air 

RFI –  

Amplitude 

Modulated 

80-1000 MHz @ 10 V/m, 

1.4-2.0 GHz @ 3 V/m, 

2.0-2.7 GHz @ 1 V/m, 

80% AM (1 kHz) 

EFT 

±2 kV DC mains, ±1 kV other 

Telco Surge 

±1 kV 

CRFI 

3 V, 0.15-80 MHz, 1 kHz 80% AM 

Safety Information 

 

  Read complete instructions prior to installation 

and operation of the meter. 

  Installation and service should be performed only 

by trained service personnel. Service requiring 

replacement of internal components must be 

performed at the factory. 

  Disconnect from supply before opening 

enclosure. Keep cover tight while circuits are 

alive. Conduit seals must be installed within 18" 

(450mm) of the enclosure. 

  Verify that the operating atmosphere of the meter 

is consistent with the appropriate hazardous 

locations certifications. 

  If the meter is installed in a high voltage 

environment and a fault or installation error 

occurs, high voltage may be present on any lead. 

 
 

 

Содержание PD6870

Страница 1: ...nt Loop Powered Backlight Option Operating Temperature Range 40 to 75 C 40 to 167 F Zero Span Potentiometer Adjustments for Easy Field Scaling Conformal Coated PCBs for Dust and Humidity Protection FM...

Страница 2: ...t of the defective unit See Warranty Information and Terms Conditions on www predig com for complete details 2021 Precision Digital Corporation All rights reserved Introduction The ProtEX FarVu PD6870...

Страница 3: ...ag that can be customized with three lines of text Each tag comes with a stainless steel wire and lead seal for easy mounting wherever you need Dimensions Useful Tools PD9501 Multi Function Calibrator...

Страница 4: ...er Jam Screw 8 Connections 8 Wiring Diagrams 8 Setup 9 Overview 9 Scaling Controls and Display 9 Setting Up the Meter 9 Setting the Decimal Point 9 Minimum Maximum Input Span 9 Calibrating the Meter 9...

Страница 5: ...ion resistant epoxy coating Color Blue Window Glass Two NPT threaded conduit openings One NPT nickel plated brass conduit plug with 12 mm hex key fitting installed Mounting May be mounted directly to...

Страница 6: ...an explosive atmosphere then appropriate protection of the free end of the cable shall be provided Year of Construction This information is contained within the serial number with the first four digi...

Страница 7: ...t the packaging and contents for damage Report damages if any to the carrier If any part is missing or the meter malfunctions please contact your supplier or the factory for assistance Pre Installed C...

Страница 8: ...g the installed loop powered backlight op tion Refer to Figure 3 for terminal positions Observe all safety regulations Electrical wiring should be performed in accordance with all agency requirements...

Страница 9: ...hat fasten the display module Remove the display module and place the jumper on the desired pins as indicated on the board for decimal point locations of D DDD DD DD DDD D or remove it if no decimal p...

Страница 10: ...e rugged design and the user friendly interface of the meter should make it unusual for the installer or operator to refer to this section of the manual If the meter is not working as expected refer t...

Страница 11: ...EN 60079 1 2007 EN 60079 31 2009 EN 61010 1 2001 and EN 61326 1 2006 are no longer harmonized The requirements of these standards have been checked against the harmonized standard EN 60079 0 2018 EN 6...

Страница 12: ...ax 508 655 8990 www predig com LIM6870_K 06 21 Contact Precision Digital Technical Support Call 800 610 5239 or 508 655 7300 Fax 508 655 8990 Email support predig com Sales Support Call 800 343 1001 o...

Отзывы: