background image

AC POWER SUPPLY 

 
Connect the primary of a 16VAC, 50/60Hz, 40VA 
Transformer to the electrical circuit and run the 
secondary to the AC input on the controller terminals. 

 

CABINET TAMPER SWITCH 
 

The tamper input 
switch should be 
connected to the 
tamper connection 
terminals as shown in 
the diagram below. The 
tamper input opens and 
closes trouble zone 
ZXxxx:01 on the 
controller. 

 

 
 
BACKUP BATTERY 

 
It is recommended that a minimum of a 4Ah battery is 
used as the main backup battery. From the accessory 
bag provided, connect the RED and BLACK battery 
termination wires to the B+ and B- terminals.  
 

 

ENCRYPTED MODULE NETWORK 

 
The Protégé 16 Zone Expander incorporates encrypted RS-
485 communications technology. The isolated 
communications interface offers full galvanic isolation to 
prevent ground loop noise and cross phase ground 
differential between network devices.  

 

 

 
Connection of the communications should be performed 
according to the diagram shown above. It is important that 
the N+ Network Communications Power be supplied from 
an independent battery backed power supply unit or a 
networked module capable of supplying the required power 
to all devices on the RS485 network. 
 
Always connect the expanders NA and NB terminals to the 
NA and NB terminals of the communication network. The 
N+ and N- must go to a 12V power supply source as shown 
in the following diagram and connected at ONLY one +12V 
power source. 
 

The EOL (End Of Line) jumper setting MUST 
be set in the ON position for the FIRST and 
LAST module on the RS485 network. EOL is 
ON when the jumper is closest to the EOL 
text.  

 

CONFIGURATION SWITCH 

 
The addressing of the Protégé Zone Expander allows up 
to 128 devices to be connected to the Protégé System 
Controller. The 'CONFIG' configuration DIP switch allows 
each PGM expander to have a unique address. 
 
The switch positions 1 to 7 select the device address from 
1 to 128. When setting an address the Zone expander 
must be powered down (Battery and AC) and restarted 
for the new address to take affect. When changing the 
address the Zone expander will automatically default the 
internal configuration and require a network update. See 
the Protégé System reference manual for information on 
performing a module update. 
 

 

 
The device address is determined by adding the value of 
each switch that is selected in the ON position and then 
adding 1 to this value. In the example below the address 
079 results in (64+8+4+2) + 1 = 079. Setting all 
address switches to OFF results in the default address of 
001. 
 

 

 
 
 

 

Отзывы: