background image

Altronix Corp.

140 58th St. Brooklyn, NY

AL602ULADAJ

NAC Power Extender

Installation Guide

(see Application Guide for additional information)

Rev. 111819

More than just power.

TM

Installing Company:  _______________ Service Rep. Name:  __________________________________  

Address:  _____________________________________________  Phone #:  __________________

Содержание AL602ULADAJ

Страница 1: ...nstallation Guide see Application Guide for additional information Rev 111819 More than just power TM Installing Company ________________ Service Rep Name ___________________________________ Address ______________________________________________ Phone ___________________ ...

Страница 2: ...g 5 Amount of Notification Appliances per NAC pg 6 Terminal Identification Table AL800LGK9E Logic Board pg 6 AL600ADA Power Supply Board pg 7 LED Diagnostics pg 7 Battery Calculation Worksheet pg 8 Hookup Diagram pg 9 Optional Hookups pg 10 Maintenance pg 10 Appendix A Compatible UL cUL Listed Devices for Synchronization A 1 Strobes Horns and Horn Strobes pg 11 Appendix B UL Listed Compatible Devi...

Страница 3: ...INP1 and INP2 8 30VDC 6 5mA max from FACP 12V 6 5mA 24V 6 5mA from FACP Output 24VDC 6 5A max total alarm current 2 5A max current per output Separate 1 0A auxiliary output Two 2 outputs may be paralleled for more power on an indicating circuit see 02 Application Guide Programmable supervised indicating circuit outputs Four 4 Class B or Two 2 Class A or One 1 Class A and Two 2 Class B see 02 Appli...

Страница 4: ...4 Stand by Specifications pg 4 Output Programming Selection Table pg 5 Sync Mode Selection Table pg 5 Terminal Identification Table pgs 6 7 LED Status Indication Table pg 7 1 Mount the unit in the desired location Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure Install two upper fasteners and screws in the wall with the screw heads protruding Place the enc...

Страница 5: ... mode is designed to work with the Amseco series of horns strobes and horn strobes to provide a means of synchronizing the Temporal coded horns synchronizing the flash timing of the strobe allowing audible notification appliances horns and visual notification appliances strobes to be silenced deactivated at the same time Gentex Sync Mode Gentex is a registered trademark of Gentex Corporation 1 2 3...

Страница 6: ...ugh OUT4 Output Programming Selection Table pg 5 Note these inputs are unidirectional and will not report a trouble condition to the FACP OUT1 OUT2 OUT3 OUT4 Supervised Notification appliances are connected to these regulated outputs see 02 Application Guide pg 2 4 Each power limited output will supply 2 5A Two 2 outputs may be connected in parallel for a maximum NAC output capability of 4A Total ...

Страница 7: ... Low battery condition will report at approximately 21VDC Battery presence detection will report with in 180 seconds after battery remains undetected missing or removed A restored battery will report within 30 seconds LED Diagnostics AL600ADA Power Supply Board Red DC Green AC Power Supply Status ON ON Normal operating condition ON OFF Loss of AC Stand by battery is supplying power OFF ON No DC ou...

Страница 8: ...Alarm mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA C Notification Appliances Current must not exceed 6 5A 6500mA 0mA mA D Total alarm current mA mA E Total current ratings converted to amperes line D x 0 001 A A F Number of standby hours 24 for NFPA 72 Chapter 1 1 5 2 5 H G Multiply lines E and F Total stand by AH AH H Alarm sounding period in hours For example 5 minutes 0 0833 hours ...

Страница 9: ... 1 ON 1 Compatible Special Application Devices See Compatibility List Non Supervised Class E This connection is used to monitor AC and Bat Fail and will cause a simultaneous trouble condition to the FACP s IN1 and IN2 Non Supervised Class E AC Local Input Fuse Power Limited Supervised Power Limited Common trouble output to Digital Communicator or Local Annunciator Dry output Contact Form C contact...

Страница 10: ...O C should connect to the host control panel for local annunciation of the trouble condition Note If common trouble input terminals marked C FAULT NC are not used these terminals must be shorted connect jumper to remain inactive For optional hookups see Fig 2b Maintenance Unit should be tested at least once a year for the proper operation as follows Output Voltage Test Under normal load conditions...

Страница 11: ...C2R UL SCRH UL SPSCWVH P UL SRHK R UL P2RHK P UL PC2R P UL SCRH P UL SPSR UL SRK UL P2RHK R UL PC2RH UL SCRH SP UL SPSR P UL SRK P UL P2RK UL PC2RH P UL SCRHK UL SPSRH UL SRK R UL P2RK P UL PC2RH SP UL SCRK UL SPSRH P UL SW UL P2RK R UL PC2RHK UL SCW UL SPSRHK UL SW ALERT UL P2W UL PC2RK UL SCW CLR ALERT UL SPSRK UL SW CLR ALERT UL P2W P UL PC2W UL SCW P UL SPSRK P UL SW P UL P2W SP UL PC2W P UL S...

Страница 12: ...75PWR UL GECG24PWR W UL WSSPK24 15 75AWR AWW UL WSSPKA24 15 75PWW UL GECR24PWR W UL GES24 177WR UL WSSPKB24 15 75PWR UL GCSA24PCR W UL GES24 177WW UL WSSPKB24 15 75PWW UL GCSB24PCR W UL GES24 15 75WR UL WSSPKG24 15 75PWR UL GCSG24PCR W UL GES24 15 75WW UL WSSPKG24 15 75PWW UL GCSR24PCR W UL GEC24 177WR UL WSSPKR24 15 75PWR UL GCCA24PCR W UL GEC24 177WW UL WSSPKR24 15 75PWW UL Potter Amseco CM24CR ...

Страница 13: ...FR UL cUL CH90 24MCC FW UL cUL E90H 24MCCH FW UL cUL LHSW A UL cUL RSS 24MCWH FW UL cUL CH90 24MCCH FR UL cUL EET90 24MCCH FR UL cUL LHSW AL UL cUL RSSA 24MCC NW UL CH90 24MCCH FW UL cUL ET 1010 R UL LHSW N UL cUL RSSA 24MCCH NW UL E50 241575W FW UL cUL ET 1010 W UL LSPSTR UL cUL RSSB 24MCC NW UL E50 24MCWH FR UL cUL ET70 241575W FR UL cUL LSPSTR AL UL cUL RSSB 24MCCH NW UL E50 24MCWH FW UL cUL ET...

Страница 14: ...B 2 below lists relays compatible with AL602ULADAJ AUX output and Outputs 1 8 when programmed as AUX Manufacturer Model Current mA Manufacturer Model Current mA System Sensor PR 1 15 System Sensor R 20T 40 PR 2 30 R 24T 40 PR 3 30 R 10E 23 EOLR 1 30 R 14E 23 R 10T 23 R 20E 40 R 14T 23 R 24E 40 ...

Страница 15: ...AL602ULADAJ Installation Guide 15 Notes ...

Страница 16: ...02ULADAJ H03U MEMBER 6 0 152 4mm 1 5 38 1mm 2 5 63 5mm 1 0 25 4mm 2 75 69 9mm 2 75 69 9mm 4 5 114 3mm 4 5 114 3mm 14 5 368 3mm 1 0 25 4mm 1 5 38 1mm 8 5 215 9mm 18 0 457 2mm 18 0 457 2mm 18 0 457 2mm 1 25 31 75mm 1 25 31 75mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 2 5 63 5mm 2 5 63 5mm 14 5 368 3mm 14 5 368 3mm 4 5 114 3mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm Enclosure Dimensions H x W...