Quick start guide to the devices of the E product line
VERSION 1.0
10/14
Interface types:
On the front panel of the device:
EOB interface: attachable to the front panel by a proprietary magnetic connector, the
connector box ends in RJ45 8/8 plug. It is 10Base-T Full duplex interface.
On the rear side of the CPU unit (See
and
100Base-FX Ethernet: ST type, 1300nm/MM, for 50 m/125 m or 62.5 m/125 m
fiber
10/100 Base-TX Ethernet: RJ45-8/8
The embedded WEB-server supports the following actions:
Modifying user parameters
Checking events list and disturbance records
Managing the Password
Online displaying measured data and generated binary information
Performing commands
Providing remote or local firmware upgrade possibility
Performing administrative tasks
2.3.2 The Ethernet connection
There are several ways to be connected to an Ethernet network.
2.3.2.1 Using the EOB connection
Attach the magnetic EOB connector to the front panel of the device. The magnets assure the
correct position of the adapter. Connect the other end of the cable to the RJ-45 socket of a
computer:
. (The RJ-45 connector of the cable can also be connected to an
Ethernet switch. In this connection all IED-s on the network with client functionalities, e.g. a
computer, has access to the device.)
Figure 2-6 Using the EOB connection